Thyristor Firing Mode - Honeywell CD3000M-2PH User Manual

Thyristor unit, from 125a to 700a
Table of Contents

Advertisement

Honeywell

7. Thyristor firing mode

ZERO CROSSING
VOLTAGE SUPPLY (V)
LOAD VOLTAGE (V)
SSR from controller
www.honeywell.com/imc
CD3000M-2PH from 125A to 700A
20%
VOLTAGE SUPPLY (V)
50%
70%
100%
7.1 Zero Crossing (ZC)
ZC firing mode is used with Logic Output
from
temperature
Thyristor operates like a contactor. The Cycle
time is performed by temperature controller.
ZC
minimizes
Thyristor unit switches ON-OFF at zero
voltage.
7.2 Burst Firing (BF)
This firing performed in Digital mode in
Honeywell Thyristor unit gives a lot of
advantages because switches Thyristor at
zero voltage crossing without EMC
interferences. Analog input is necessary for
BF and can be decided how many complete
cycles we want at 50% of power demand.
This value can be implemented from 1 to 255
complete cycles doing the firing less or more
fast. When 1 is setted the firing name
becomes Single Cycle (see above).
26