Honeywell SmartDrive Compact User Manual page 57

Table of Contents

Advertisement

9
56
4.7
DC
BRAKING TIME AT STOP
Determines if braking is ON or OFF and the braking time of the DC-brake
when the motor is stopping. The function of the DC-brake depends on the stop
function, par. 2.3.
Par. 2.3 = 0 (Stop function = Coasting):
After the stop command, the motor coasts to a stop without control from the
inverter.
With the DC injection, the motor can be electrically stopped in the shortest
possible time, without using an optional external braking resistor.
The braking time is scaled by the frequency when the DC-braking starts. If the
frequency is greater than the nominal frequency of the motor, the set value of
parameter 4.7 determines the braking time. When the frequency is 10% of the
nominal, the braking time is 10% of the set value of parameter 4.7.
f out
f n
DC-braking ON
RUN
STOP
Figure 9.8: DC-braking time when Stop mode = Coasting
Par. 2.3 = 1 (Stop function = Ramp):
After the Stop command, the speed of the motor is reduced according to the
set deceleration parameters, if the inertia of of the motor and load allows that,
to the speed defined with parameter 4.6, where the DC-braking starts.
Parameter Descriptions
0 = DC brake is not in use
>0 = DC brake is in use and its function depends on the Stop function,
(par. 2.3). The DC braking time is determined with this parameter.
Output frequency
Motor speed
t = 1 x par. 4.7
f out
f n
0,1 x f n
t
RUN
STOP
Honeywell
Output frequency
Motor speed
DC-braking ON
t
t = 0,1 x par. 4.7