Honeywell SmartDrive Compact User Manual page 25

Table of Contents

Advertisement

5
24
Fault
Fault name
code
51
External fault
53
Fieldbus fault
57
Identification fault
Table 5.1 : Fault codes
Fault Tracing
Possible cause
Digital input fault. Digital input
has been programmed as exter-
nal fault input and this input is
active
The data connection between the
fieldbus Master and the fieldbus
of the drive broken
Identification run has failed
Honeywell
Correcting actions
Check the programming and
the device indicated by the
external fault information.
Check also the cabling of
this device.
Check installation.
If installation is correct con-
tact the nearest Honeywell
technical support.
Run command was
removed before completion
of identification run.
Motor is not connected to
inverter. There is load on
motor shaft.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents