Chapter 6. Communication

6.1 MODBUS

6.1.1 Introduction

The AT600 flow meter generally follows the standard MODBUS communications protocol defined by the
MODBUS APPLICATION PROTOCOL SPECIFICATION V1.1b , which is available at www.modbus.org. With this
reference as a guide, an operator can use any MODBUS master to communicate with the AT600 flow meter.
For the AT600, there are two limits of this implementation:
1. The AT600 supports only four of the standard function codes. These are Read Holding Registers
(0x03), Read Input Registers (0x04), Write Multiple Registers (0x10), and Read File Record (0x14).
2. The AT600 needs a 15 ms gap between Modbus requests. The prime objective of the flow meter is to
measure flow and drive the output, so the Modbus server has a low priority.

6.1.2 MODBUS Register Map

Register
Register (in
(in Hex)
100
100
108
118
128
140
140
148
150
158
300
300
304
308
500
500
502
504
506
508
50A
50C
AquaTrans™ AT600 User's Manual
Table 7: MODBUS Register Map
Decimal)
Access Level
256
User
264
User
280
User
296
User
320
User
328
User
336
User
344
User
768
RO
772
RO
776
RO
1280
User
1282
User
1284
User
1286
User
1288
User
1290
User
1292
User
Description
Product Short Tag
Product Long Tag
Product message (for HART)
Product descriptor (for HART)
Product Electronic serial
number
Product fixture serial number
Product transducer1 serial
number
Product transducer2 serial
number
Main Hardware version
Option Hardware version
Main Software version
Global Unit group 1 for Actual
Volumetric
Global Unit group 2 for Day
Global Unit group 3 for dB
Global Unit group 4 for Density
Global Unit group 5 for
Dimension
Global Unit group 6 for Hz
Global Unit group 7 for
Viscosity
Chapter 6. Communication
RO/RW
Format
RW
CHAR * 16
RW
CHAR * 32
RW
CHAR * 32
RW
CHAR * 16
RW
CHAR * 16
RW
CHAR * 16
RW
CHAR * 16
RW
CHAR * 16
RO
CHAR * 8
RO
CHAR * 8
RO
CHAR * 8
RW
INT32
RW
INT32
RW
INT32
RW
INT32
RW
INT32
RW
INT32
RW
INT32
97