Siemens SINAMICS G130 Engineering Manual page 40

Sinamics - low voltage sinamics drives
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Fundamental Principles and System Description
Engineering Information
Output
Frame
power
size
SINAMICS
G130
at 400V /
500V / 690V
[ kW ]
[ - ]
SINAMICS G130 / 380 V – 480 V 3AC
110
FX
132
FX
160
GX
200
GX
250
GX
315
HX
400
HX
450
HX
560
JX
SINAMICS G130 / 500 V – 600 V 3AC
110
GX
132
GX
160
GX
200
GX
250
HX
315
HX
400
HX
500
JX
560
JX
SINAMICS G130 / 660 V – 690 V 3AC
75
FX
90
FX
110
FX
132
FX
160
GX
200
GX
250
GX
315
GX
400
HX
450
HX
560
HX
710
JX
800
JX
1) These values apply to G130 Chassis units and do not take in account line-side fuse switch disconnectors or circuit breakers
SINAMICS G130: Maximum and minimum line-side short-circuit currents
SINAMICS Engineering Manual – November 2015
40/528
Ó Siemens AG
Rated
Maximum
input current
short-circuit current
[ A ]
[ kA ]
1
229
65
1
284
65
1
338
65
1
395
65
1
509
65
1
629
65
1
775
65
1
873
84
1
1024
84
1
191
65
1
224
65
1
270
65
1
343
65
1
426
65
1
483
65
1
598
65
1
764
84
1
842
84
1
93
65
1
109
65
1
131
65
1
164
65
1
191
65
1
224
65
1
270
65
1
343
65
1
426
65
1
483
65
1
598
65
1
764
84
1
842
84
Minimum
Min. relative
short-circuit
short-circuit
current
power
RSC
min
[ kA ]
[ - ]
3.0
13.1
3.6
12.7
4.4
13.0
4.4
11.1
8.0
15.7
10.0
15.9
10.5
13.6
16.0
18.3
18.4
18.0
2.4
12.6
3.0
13.4
3.6
13.3
5.2
15.2
5.2
12.2
6.2
12.8
8.4
14.0
10.5
13.7
10.4
12.4
1.1
11.8
1.1
10.1
1.2
9.2
1.6
9.8
2.4
12.6
3.0
13.4
3.6
13.3
5.2
15.2
5.2
12.2
6.2
12.8
8.4
14.0
10.5
13.7
10.4
12.4
Max. relative
short-circuit
voltage
v
k max
[ % ]
7.6
7.9
7.7
9.0
6.4
6.3
7.4
5.5
5.6
8.0
7.5
7.5
6.6
8.2
7.8
7.1
7.3
8.1
8.5
10.0
11.0
10.2
8.0
7.5
7.5
6.6
8.2
7.8
7.1
7.3
8.1

Hide quick links: