Capacitance Values - Siemens SINAMICS G130 Engineering Manual

Sinamics - low voltage sinamics drives
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

SINAMICS S120
Engineering Information
6.6.2

Capacitance values

In order to check that the overall capacitance does not exceed the limit values, all individual capacitance values at
the DC link (including the internal capacitance of the Line Module) must be added. To facilitate system configuration,
the possible additional capacitance of the drive configuration has been incorporated into the tables below without the
internal capacitance of the Line Module. This is named "Reserve Precharging".
The following capacitance values apply:
Basic Line Modules
Order No.
Supply voltage 380 V to 480 V 3AC
1
6SL3x30-1TE34-2AA3
1
6SL3x30-1TE35-3AA3
2
6SL3x35-1TE37-4AA3
1
6SL3x30-1TE38-2AA3
1
6SL3x30-1TE41-2AA3
3
6SL3730-1TE41-2BA3
3
6SL3730-1TE41-2BC3
2
6SL3x35-1TE41-2AA3
1
6SL3x30-1TE41-5AA3
3
6SL3730-1TE41-5BA3
3
6SL3730-1TE41-5BC3
2
6SL3x35-1TE41-7AA3
1
6SL3x30-1TE41-8AA3
3
6SL3730-1TE41-8BA3
3
6SL3730-1TE41-8BC3
Supply voltage 500 V to 690 V 3AC
1
6SL3x30-1TG33-0AA3
2
6SL3x35-1TG34-2AA3
1
6SL3x30-1TG34-3AA3
1
6SL3x30-1TG36-8AA3
2
6SL3x35-1TG37-3AA3
1
6SL3x30-1TG41-1AA3
3
6SL3730-1TG41-1BA3
3
6SL3730-1TG41-1BC3
2
6SL3x35-1TG41-3AA3
1
6SL3x30-1TG41-4AA3
3
6SL3730-1TG41-4BA3
3
6SL3730-1TG41-4BC3
2
6SL3x35-1TG41-7AA3
1
6SL3x30-1TG41-8AA3
3
6SL3730-1TG41-8BA3
3
6SL3730-1TG41-8BC3
1
The order number 6SL3x30 stands for the air-cooled S120 Chassis and Cabinet Modules.
2
The order number 6SL3x35 stands for the liquid-cooled S120 Chassis and Cabinet Modules
3
These units are exclusive to the air-cooled S120 Cabinet Modules range.
4
The value in front of the "/" applies to S120 diode-based BLMs with one precharging resistor per phase, the value after the "/"
to S120 diode-based BLMs with two precharging resistors connected in parallel per phase, see section "Precharging of the DC
link and precharging currents", subsection "Basic Infeed: Diode-based Basic Line Modules".
SINAMICS Engineering Manual – November 2015
364/528
Ó Siemens AG
Output at
Rated DC link current
400 V or 690 V
[kW]
[A]
200
420
250
530
360
740
400
820
560
1200
560
1200
560
1200
600
1220
710
1500
710
1500
710
1500
830
1730
900
1880
900
1880
900
1880
250
300
355
420
355
430
560
680
630
730
900
1100
900
1100
900
1100
1100
1300
1100
1400
1100
1400
1100
1400
1370
1650
1500
1880
1500
1880
1500
1880
DC link
Maximum DC link
capacitance
capacitance
[µF]
[µF]
7200
57600
9600
76800
12000
96000
14600
116800
23200
185600
23200
185600
23200
185600
20300
162400
29000
232000
29000
232000
29000
232000
26100
208800
34800
139200/278400
34800
139200/278400
34800
139200/278400
3200
25600
4800
38400
4800
38400
7300
58400
7700
61600
11600
92800
11600
92800
11600
92800
15500
124000
15470
123760
15470
123760
15470
123760
19300
154400
19500
78000/156000
19500
78000/156000
19500
78000/156000
Precharging reserve
[µF]
50400
67200
84000
102200
162400
162400
162400
142100
203000
203000
203000
182700
4
4
104400/243600
4
4
104400/243600
4
4
104400/243600
22400
33600
33600
51100
53900
81200
81200
81200
108500
108290
108290
108290
135100
4
4
58500/136500
4
4
58500/136500
4
4
58500/136500

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g150Sinamics s120Sinamics s150

Table of Contents