Siemens SINAMICS G130 Engineering Manual page 150

Sinamics - low voltage sinamics drives
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Fundamental Principles and System Description
Engineering Information
A method of calculating the permissible cable lengths for multi-motor drives l
motor drives is described below.
The diagram explains the quantities and terms used for both single-motor and multi-motor drives.
Block diagram of single-motor drive and multi-motor drive with relevant quantities and terms
The permissible motor cable length per motor on a multi-motor drive is calculated with the fomula:
n
=
S
l
M
Definition and meaning of applied quantities:
·
l
Permissible cable length between the subdistributor and each motor in a multi-motor drive.
M
·
n
Maximum number of motor cables which can be connected in parallel in a single-motor drive. This
S max
value can be found in the chapters on specific units or in the relevant catalogs.
·
C
(A
) Capacitance per unit length of a shielded motor cable with the maximum permissible cross-section
S max
max
A
for a single-motor drive. This value can be found in the table on the next page and is
max
depending on the maximum permissible cross-section A
units or the relevant catalogs.
·
l
Permissible motor cable length for single-motor drive as specified in the tables on the previous
S max
page (depending on the number of motor reactors (1 or 2) and whether the cable is shielded or
unshielded).
·
n
Number of parallel cables between the converter and subdistributor on a multi-motor drive.
D
·
C
(A)
Capacitance per unit length of the cable between the converter and subdistributor on a multi-motor
D
drive.
·
l
Length of the cable between the converter and subdistributor on a multi-motor drive.
D
·
n
Number of parallel cables on motor side of subdistributor = number of motors.
M
·
C
(A)
Capacitance per unit length of cables on motor side of subdistributor.
M
SINAMICS Engineering Manual – November 2015
150/528
Ó Siemens AG
×
×
C
(
A
)
l
max
S
max
max
S
max
×
n
C
(
A
M
M
M
-
×
×
n
C
(
A
)
l
D
D
D
)
max
based on the catalog data for single-
specified in the chapters on specific

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g150Sinamics s120Sinamics s150

Table of Contents