When an external 24 V supply is connected to terminal X9, it must be
noted that the capacitors in the electronics power supply of the
connected Power Module must be charged when the external 24 V
supply is switched on. In other words, the 24 V supply must initially
supply a peak curren t which can amount to a multiple of the current
I
calculated according to the table, in order to charge these
DC ext
capacitors. Account must be taken of this peak current when protective
devices such as miniature circuit breakers are installed. The peak current
flows for a period t
lasting only a few 100 ms. The peak value is
e
determined by the impedance of the external 24 V supply or its
electronically limited maximum current.

4.5 Factory settings (defaults) of customer interface on SINAMICS G130

The following factory settings are provided to simplify configuring of the customer interface and commissioning. The
interfaces can also be assigned as required at any time.
1.
The converter is controlled via the PROFIBUS interface (CU320-2 DP) or the PROFINET interface (CU320-2
PN) which are integrated as standard. The digital inputs and outputs on the Control Unit are used to incorporate
external alarm and/or error messages and control signals.
Terminal block on the CU320-2 Control Unit
-X122
Factory setting
DI0
Not assigned
DI1
Not assigned
DI2
Not assigned
DI3
Acknowledge fault
DI16
Not assigned
DI17
Not assigned
M1
M (GND)
DI/DO8
Inverter enable (Run)
DI/DO9
No fault
M (GND)
DI/DO10
P24
DI/DO11
External alarm
M (GND)
-X132
DI4
OFF 2
DI5
OFF 3
DI6
External fault
DI7
Not assigned
DI20
Not assigned
DI21
Not assigned
M2
M (GND)
DI/DO12
Error message acknowledgement, Braking
Module
DI/DO13
P24
M (GND)
DI/DO14
P24
DI/DO15
P24
M (GND)
The factory settings of the bidirectional inputs/outputs are underscored.
1)
A jumper must be inserted here if these inputs are not used.
1)
1)
1)
1)
Engineering Information
Typical current waveform when the
external 24 V supply is switched on
Comment
Factory-set as output
Low active
Ramp-down along quick-stop ramp, only of relevance in
conjunction with the Braking Module
Output is used (factory-set) in conjunction with the Braking
Module
Factory-set as output
Factory-set as output
Factory-set as output
SINAMICS Engineering Manual – November 2015
SINAMICS G130