Honeywell Sensepoint XCD RTD Technical Manual page 21

Remote toxic detector
Table of Contents

Advertisement

Sensepoint XCD RTD Technical Manual
Displayed
Gas Name
Name
Hydrogen Sulfide
H
Carbon Monoxide
Chlorine
Ammonia
NH
Hydrogen
Nitrogen Monoxide
NO
SO
Sulphur Dioxide
SO
Nitrogen Dioxide
NO
Oxygen
For details of how to change the configuration of the Sensepoint XCD please refer
to section 13.
Range
Lower Alarm
20.0 ppm
4.0ppm
S
50.0 ppm
10.0ppm
2
100 ppm
20ppm
100 ppm
30ppm
CO
200 ppm
40ppm
500 ppm
100ppm
5.0 ppm
0.5 ppm
Cl
2
15.0 ppm
1.5 ppm
50.0 ppm
20.0ppm
100 ppm
20ppm
3
1000 ppm
200ppm
H
1000 ppm
200ppm
2
H
9999 ppm
2000ppm
2
100 ppm
20ppm
15.0 ppm
2.0ppm
2
50.0 ppm
5.0ppm
2
10.0 ppm
2.0ppm
2
O
25.0% V/V
19.5%Vol
2
Table 4: Gas Type and measuring range
Lower Alarm
Higher Alarm
Type
Rising
8.0ppm
Rising
20.0ppm
Rising
40ppm
Rising
60ppm
Rising
80ppm
Rising
200ppm
Rising
2.0ppm
Rising
6.0ppm
Rising
30.0ppm
Rising
40ppm
Rising
400ppm
Rising
400ppm
Rising
4000ppm
Rising
40ppm
Rising
6.0ppm
Rising
20.0ppm
Rising
4.0ppm
Falling
23.5%Vol
21
SPXCDHMRTEN Issue 1
Lowest
Higher Alarm
alarm
Type
level
Rising
2.0ppm
Rising
5.0ppm
Rising
10ppm
Rising
10ppm
Rising
20ppm
Rising
50ppm
Rising
0.5ppm
Rising
1.5ppm
Rising
5.0ppm
Rising
10ppm
Rising
100ppm
Rising
100ppm
Rising
1000ppm
Rising
10ppm
Rising
1.5ppm
Rising
5.0ppm
Rising
1.0ppm
Rising
10.0%Vol