AH-S22AW2
AH-S25AW2
Function
NO
8
Outdoor
Lowers the operating frequency if the
heating
temperature of the outdoor heat exchanger
exchanger
rises above 57°C during cooling. Stops the
overheating
compressor if the temperature stays above
control
57°C for 1 minute at 35 Hz or less.
9
Outdoor
Stops the compressor if an outdoor
thermistor
thermistor (excluding TH1) shorts.
short
10
Outdoor
Stops the compressor if the circuit of an
thermistor
outdoor thermistor breaks.
open
11
AC abnormal
Stops the compressor if if the operating
current error
frequency is above 85 Hz and the
compressor current is below 1.0 A.
12
Serial signal
Turns the compressor relay off if the indoor
error
unit does not receive a serial signal from
the outdoor unit for 8 minutes.
Stops the compressor if the outdoor unit
does not receive a serial signal from the
indoor unit for 30 seconds.
13
Indoor
Stop operation
terminal
The reason that the fuse operation is by
board thermal
connecion error at the inside of terminal
fuse
board.
operation
14
Outdoor
Stop operation
terminal
The reason that the fuse operation is by
board thermal
connecion error at the inside of terminal
fuse
board.
operation
Operation
Description
During
compressor
operation
When
compressor is
activated
When
compressor is
activated
During
compressor
operation
During
operation
During
operation
During
operation
During
operation
20
Detection
Restart
time
condition
Automatically
restarts after safety
time (170 seconds)
Automatically
restarts after safety
time (170 seconds)
Automatically
restarts after safety
time (170 seconds)
Automatically
restarts after safety
time (170 seconds)
Automatically
restarts less than 8
minutes after
operation stops
Restarts after
reception of serial
signal
Exchange of
terminal board
Exchange of
terminal board
Self diagnostic
display
Restart
Indoor Outdoor
times
o limit
No
No
4 times
Yes
Yes
4 times
Yes
Yes
4 times
Yes
Yes
No limit
Yes
No limit
Yes
No
No
No