(a) IPC5000S
Analog output
AO1
AO2
(2) SOURCE set: The Combo box for selecting analog output source
If pushing this button, the items for selection like figure 3.5.2 appear in next page. If the
OUT TYPE is 4~20mA, (A) appears and if it is PWM, (B) appears.
IPC5000D : selecting one of PV1, PV2, SP1, SP2, DV1 and DV2
IPC5000S : selecting one of PV1, SP1 and DV1
When setting in figure 3.5.2, (4) item in figure 3.5.1 for setting output scale of 4~20mA is
displayed.
PWM Selection : PWM means Pulse Width Modulation and it is four pulse outputs
IPC5000 supports. The MV1, MV2, MV3 and MV4 of IPC5000D and MV1 and MV2 of
IPC5000S can be assigned to each pulse. Refer to figure 3.4.1 and 3.4.2 for the assigning.
(3) OUT TYPE set : Sets the output type to analog output terminal.
Anlaog output channel 1 and 2 supports 4~20mA and Voltage pulse(PWM) and Anlaog
output channel 3 and 4 only supports 4~20mA. Analog output channel 3 and 4 is option.
(a) IPC5000D
Control output for heating of channel 1
Control output for heating of channel 2
Control output for cooling of channel 1
Control output for cooling of channel 2
Process Value of channel 1
Process Value of channel 2
Deviation Value of channel 1
Deviation Value of channel 2
Terminal number
(Analog I/O Group)
1
1(+), 2(-)
2
3(+), 4(-)
Set Point of channel 1
Set Point of channel 2
4~20mA/ Voltage Pulse
4~20mA/ Voltage Pulse
MV1
SOURCE
MV1
MV2
MV3
MV4
PV1
PV2
SP1
SP2
DV1
DV2
(i) OUT TYPE = 4~20mA (ii) OUT TYPE = PWM
- 38 -
OPT: Option
Output Type
MV1
SOURCE
MV1
MV2
MV3
MV4
Basic/OPT
Spec.
Basic
Basic