Honeywell IPC5000 Installation Manual page 40

Universal programmable controller
Table of Contents

Advertisement

(2) Sensor Input Display Setup.
(2-1) UNIT: PV UNIT Setup
Indicates unit by temperature input. Celsius: C / Fahrenheit: F / etc.: NONE
If the unit is selected by Volt/Current(0~10V, 0~5V, 1~5V, 0~20mA, 4~20mA), the
unit is fixed by NONE automatically.
If the sensor type is selected by RTD or TC, the mean of the unit(NONE) is same
with Celsius(C).
(2-2) TYPE: Code indicates ready-setup type of sensor.
Sensor type & Code Table (See Chart below).
Input type
DC Voltage
Linear
DC Current
Pt100
RTD
(JIS/IEC
.00385)
RTD
JPt100
(JIS)
Input
Instrument input range
range
DEG C
code
DCV1
0~10V
DCV2
0~5V
DCV3
1~5V
MA1
0~20mA
MA2
4~20mA
Pt1
-200.0~500.0
Pt2
-200.0~200.0
Pt3
-100.0~150.0
Pt4
-50.0~200.0
Pt5
-40.0~60.0
Pt6
0.0~100.0
Pt7
0.0~300.0
Pt8
0.0~500.0
JPt1
-200.0~500.0
JPt2
-200.0~200.0
JPt3
-100.0~150.0
JPt4
-50.0~200.0
JPt5
-40.0~60.0
JPt6
0.0~100.0
JPt7
0.0~300.0
JPt8
0.0~500.0
- 30 -
Default = VOLT 0 ~ 10V
(-19999 ~ 20000)
(-19999 ~ 20000)
(-19999 ~ 20000)
(-19999 ~ 20000)
(-19999 ~ 20000)
-328.0~932.0
-328.0~392.0
-148.0~302.0
-58.0~392.0
-40.0~140.0
32.0~212.0
32.0~572.0
32.0~932.0
-328.0~932.0
-328.0~392.0
-148.0~302.0
-58.0~392.0
-40.0~140.0
32.0~212.0
32.0~572.0
32.0~932.0
DEG F

Advertisement