Please report any deviations to our hotline (see Page 5).
The original packing materials provide effective protection
against impacts and should be retained to ensure secure
transport at a later date.
4.2

Set-up location

The Protect B. PRO was designed to be set up in a protected
environment. When setting up the device, take factors such as
sufficient ventilation and appropriate ambient conditions into
consideration.
The installation site must be sufficiently strong and stable to
avoid vibrations and impacts.
Ensure sufficient load-bearing capacity, especially when
used
accessories).
Position the devices in such a way that sufficient air
circulation is ensured. There must be at least 100 mm
clearance behind the back fan for ventilation purposes. Do
not block supply air openings on the front. A clearance of
50 mm must be ensured here.
Position external battery units directly next to the UPS
system. To preserve maximum mechanical stability in case
of rack installation, place each drawer on its own pair of rack
rails.
Avoid extreme temperatures! To maximise the service life of
the batteries, we recommend an ambient temperature of
15°C to 25°C. Do not expose the devices to direct sunlight or
operate them near other heat sources, e.g. radiators.
To rule out the risk of suffocation, keep the plastic
packaging bags out of the reach of babies and
children.
Handle the components with care. Be especially
mindful of their weight. Obtain the help of another
person when moving the Protect B. 2300 PRO, the
Protect B. 3000 PRO and the external battery units
Protect B. 1800 BP PRO and Protect B.3000 BP PRO.
together
with
external
battery
22
units
(special
EN