Rxgoose Statistics; Channel Tests - GE L30 Instruction Manual

Line current differential system
Hide thumbs Also See for L30:
Table of Contents

Advertisement

STATUS
The L30 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
The
All RxGOOSE Online
Input.

6.3.9 RxGOOSE statistics

ACTUAL VALUES  STATUS  RxGOOSE STATISTICS  RxGOOSE 1(64)
 RxGOOSE 1
The L30 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
— State number. The most recently received value in GOOSE message field stNum. The publisher increments stNum
stNum
each time that the state of one or more of the GOOSE message members is sent with a revised value.
— Sequence number. The most recently received value in GOOSE message field sqNum. The publisher sets sqNum
sqNum
to zero each time the state of one or more of the GOOSE message members is sent with a new value, and it increments it
whenever a GOOSE message is resent without any member value change.

6.3.10 Channel tests

ACTUAL VALUES  STATUS  CHANNEL TESTS
6
 CHANNEL TESTS
6-6
actual value does not consider RxGOOSE that are not configured or are not used by any RxGOOSE
RxGOOSE 1
stNum:
RxGOOSE 1
sqNum:
CHANNEL 1
STATUS: n/a
CHANNEL 1 LOST
PACKETS:
CHANNEL 1 LOCAL
LOOPBCK STATUS: n/a
CHANNEL 1 REMOTE
LOOPBCK STATUS: n/a
CHANNEL 1
LOOP DELAY: 0.0 ms
CHNL 1 ASYMMETRY:
+0.0 ms
CHANNEL 2
STATUS: n/a
CHANNEL 2 LOST
PACKETS:
CHANNEL 2 LOCAL
LOOPBCK STATUS: n/a
CHANNEL 2 REMOTE
LOOPBCK STATUS: n/a
CHANNEL 2
LOOP DELAY: 0.0 ms
Range: 0 up to 4,294,967,295
0
Range: 0 up to 4,294,967,295
0
Range: n/a, FAIL, OK
Range: 0 to 65535 in steps of 1. Reset count to 0
0
through the COMMANDS  CLEAR RECORDS menu.
Range: n/a, FAIL, OK
Range: n/a, FAIL, OK
Range: –10 to 10 ms in steps of 0.1
Range: n/a, FAIL, OK
Range: 0 to 65535 in steps of 1. Reset count to 0
0
through the COMMANDS  CLEAR RECORDS menu.
Range: n/a, FAIL, OK
Range: n/a, FAIL, OK