Operation
MiCOM P741, P742, P743
It should be noted that when an InterMiCOM signal is sent from the local relay, only the
remote end relay will react to this command. The local end relay will only react to
InterMiCOM commands initiated at the remote end. InterMiCOM is thus suitable for
teleprotection schemes requiring Duplex signaling.
1.5.8
InterMiCOM statistics & diagnostics
It is possible to hide the channel diagnostics and statistics from view by setting the "Ch
Statistics" and/or "Ch Diagnostics" cells to "Invisible". All channel statistics are reset when
the relay is powered up, or by user selection using the "Reset Statistics" cell.
P74x/EN OP/Na7
(OP) 5-33
OP