5. Operation
5.3. Transmitter PV display
Transmitter
Wireless Builder display
display
OVR LOAD
Over Load
CAL ERR
Calibration Error
LOW BAT
Low Battery
LOW PWR
Low Power
NO RADIO
Radio Interprocessor
Comm Error
BAD RADIO
Sensor Radio SPI
SPI
Communication Failure
BAD RADIO
EEPROM SPI
EEPROM
Communication Failure
RADIO WDT
WDT Reset Occurred
RESET
BAD RADIO
Radio Circuitry Failure
The following status messages have multiple meanings. Refer to Wireless Builder Device Status for exact cause.
INP FAIL
Input Failure
INP FAIL
A/D Failure
E FAIL
A/D Failure
E FAIL
Electronics Failure
18
OneWireless XYR 6000 Pressure Transmitter R120 User's Manual
Definition
The applied pressure has
exceeded the limit
defined by the meter
body characterization
data.
Calibration Data Invalid
or could not be read.
Battery Voltage Critically
Low
External Power Critically
Low
Radio Board is not
accessible.
Radio detected loss of
communication with
sensor board over the
inter-processor
communication link.
Radio EEPROM SPI
Communication failure
Radio Watch Dog
Timeout detected
Radio circuitry has failed
Input Error
Diagnostics detected
defect with Analog to
Digital Converter.
Diagnostics detected
defect with Analog to
Digital Converter.
Electronic Failure
detected on Sensor
Board. Could be caused
by one of the status
items marked by *.
What to do
Determine cause of over pressure.
Use Cal Clear, Restore, or User
Calibrate.
Replace batteries as soon as
possible. See page 34.
Check external 24V power supply
Restart both the radio and sensor.
If condition persists, replace
sensor module. See page 32.
Restart both the radio and sensor.
If condition persists, replace
sensor module. See page 32.
The radio will not be able to
perform firmware upgrades but will
operate normally using installed
code. Replace sensor module.
See page 32.
Restart both the radio and sensor.
If condition persists, replace
sensor module. See page 32.
The radio processor detected error
on internal radio circuitry. Replace
sensor module. See page 32.
Possible meter body sensor
failure.
Replace sensor module. See page
32.
Replace sensor module. See page
32.
Restart both the radio and sensor.
If condition persists, replace
sensor module. See page 32.
November 2010
Revision 8

Hide quick links: