The B30 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supported
over two protocol stacks: TCP/IP over ethernet and TP4/CLNP (OSI) over ethernet. The B30 operates as an IEC 61850
server. The Remote inputs and outputs section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme.
The EnerVista software includes an interface that is compatible with firmware versions 5.0 to 7.2 to configure subscribers.
Use the Simplified GOOSE Configurator in the Offline Window area.
The GSSE/GOOSE configuration main menu is divided into two areas: transmission and reception.
PATH: SETTINGS
PRODUCT SETUP
 GSSE / GOOSE
 CONFIGURATION
MESSAGE
The main transmission menu is shown below:
PATH: SETTINGS
PRODUCT SETUP
 TRANSMISSION
MESSAGE
MESSAGE
MESSAGE
The general transmission settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
 GENERAL
The
DEFAULT GSSE/GOOSE UPDATE TIME
put state changes to be sent. When remote output data changes, GSSE or GOOSE messages are sent immediately. This
setting controls the steady-state heartbeat time interval.
The
DEFAULT GSSE/GOOSE UPDATE TIME
The GSSE settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
 GSSE
MESSAGE
MESSAGE
These settings are applicable to GSSE only. If the fixed GOOSE function is enabled, GSSE messages are not transmitted.
The
setting represents the IEC 61850 GSSE application ID name string sent as part of each GSSE message. This
GSSE ID
string identifies the GSSE message to the receiving device. In B30 releases previous to 5.0x, this name string was repre-
sented by the
setting.
RELAY NAME
GE Multilin


COMMUNICATIONS
IEC 61850 PROTOCOL
 TRANSMISSION
 RECEPTION


COMMUNICATIONS
IEC 61850 PROTOCOL
 GENERAL
 GSSE
 FIXED GOOSE
 CONFIGURABLE GOOSE


COMMUNICATIONS
IEC 61850...
DEFAULT GSSE/GOOSE
UPDATE TIME: 60 s
sets the time between GSSE or GOOSE messages when there are no remote out-
setting is applicable to GSSE, fixed B30 GOOSE, and configurable GOOSE.


COMMUNICATIONS
IEC 61850...
GSSE FUNCTION:
Enabled
GSSE ID:
GSSEOut
DESTINATION MAC:
000000000000
B30 Bus Differential System
5.2 PRODUCT SETUP
GSSE/GOOSE CONFIGURATION
GSSE/GOOSE...
GSSE/GOOSE...
TRANSMISSION
Range: 1 to 60 s in steps of 1
GSSE/GOOSE...
TRANSMISSION
Range: Enabled, Disabled