Operation; Setup; Dip Switch 1; Dip Switch 2 - Siemens POINTEK CLS 300 Instruction Manual

Capacitance; liquids/solids
Hide thumbs Also See for POINTEK CLS 300:
Table of Contents

Advertisement

Operation

Setup

Note:
Setup can be done in the field with the Pointek CLS 300 mounted into process, or in
the shop prior to mounting.

Dip Switch 1

Set ON to change alarm relay status immediately when the sensor detects a change in
frequency. Use this setting when time is critical.
Set OFF to change the alarm relay status with a delay by the amount set on
potentiometer #1 (P1). Use this setting when you want to slow the response to account
for turbulence or false readings.

Dip Switch 2

Set ON to change alarm relay status immediately when the sensor detects a change in
frequency. Use this setting when time is critical.
Set OFF to change the alarm relay status with a delay by the amount set on
potentiometer #1 (P1). Use this setting when you want to slow the response to account
for turbulence or false readings.

Dip Switch 3

Set OFF to indicate Low fail-safe selection.
Set ON to indicate High fail-safe selection.

Dip Switch 4

Set ON to test the delay of the alarm relays as set by the potentiometer #1 (P1).
Set OFF for normal operation.
Dip Switch 5
Set ON for normal sensitivity on the
sensor. Use this setting when you are
measuring dry solids or non-conductive
liquids.
Set OFF for low sensitivity on the
sensor. Use this setting to measure
conductive liquids or wet conductive
solids which are likely to build up.
7ML19985CK03
Pointek CLS 300 – INSTRUCTION MANUAL
Switches shown in OFF position
Delay ON
Delay OFF
Fail-safe
Delay test
Sensitivity
Page 19