Operation
Setup
Note:
Setup can be done in the field with the Pointek CLS 300 mounted into process, or in
the shop prior to mounting.
Dip Switch 1
•
Set ON to change alarm relay status immediately when the sensor detects a change in
frequency. Use this setting when time is critical.
•
Set OFF to change the alarm relay status with a delay by the amount set on
potentiometer #1 (P1). Use this setting when you want to slow the response to account
for turbulence or false readings.
Dip Switch 2
•
Set ON to change alarm relay status immediately when the sensor detects a change in
frequency. Use this setting when time is critical.
•
Set OFF to change the alarm relay status with a delay by the amount set on
potentiometer #1 (P1). Use this setting when you want to slow the response to account
for turbulence or false readings.
Dip Switch 3
•
Set OFF to indicate Low fail-safe selection.
•
Set ON to indicate High fail-safe selection.
Dip Switch 4
•
Set ON to test the delay of the alarm relays as set by the potentiometer #1 (P1).
•
Set OFF for normal operation.
Dip Switch 5
•
Set ON for normal sensitivity on the
sensor. Use this setting when you are
measuring dry solids or non-conductive
liquids.
•
Set OFF for low sensitivity on the
sensor. Use this setting to measure
conductive liquids or wet conductive
solids which are likely to build up.
7ML19985CK03
Pointek CLS 300 – INSTRUCTION MANUAL
Switches shown in OFF position
Delay ON
Delay OFF
Fail-safe
Delay test
Sensitivity
Page 19