Case 1
Preparation
• Ensure that L3 (green) is ON
• Turn both potentiometers, P1 and P2, fully CCW (counter-clockwise)
• Set S1 switches 1 to 4 to OFF and S1 switch 5 to ON (normal sensitivity)
Configuration
With sensor uncovered and a minimum 100mm free space all around, turn P2 CW until
1.
L1 (yellow) goes ON.
Turn P2 CCW until L1 goes OFF.
2.
Case 2
Preparation
• Ensure that L3 (green) is ON
• Turn potentiometer P1 fully CCW (counter-clockwise)
• Turn P2 fully CW (clockwise)
• Set S1 switches 1 through 5 to OFF
Configuration
Immerse the sensor in the material that has the lowest dielectric constant. L1 (yellow)
1.
should be ON. (If L1 does not light, set S1 switch 5 to ON [normal sensitivity].)
Adjust P2 CCW until L1 goes OFF.
2.
Immerse the sensor in the material that has the highest dielectric constant; L1 should
3.
come ON.
Page 22
Pointek CLS 300 – INSTRUCTION MANUAL
Trip Amplifier
7ML19985CK03