System Sizing and Availability Summary

Specification
Combined Analog and Digital I/O
Analog Inputs
Analog Outputs
Block inputs
Block parameters
Block values
FDB worksheets
Function blocks
Local I/O
Loop blocks
Modbus registers used by slave blocks
Modbus slave blocks
Numeric constants
Page connectors
Peer blocks (including both SAFPDE blocks
& PDE Blocks)
Peer data exchange items (including both
PDE items and safety peer import items)
Safety Peer Export Signals
Position proportional output blocks
Profiles in Pool
Ramp blocks
Recipes in Pool
Redundancy capability
Redundant host comms.
Schedules in Pool
Segments per profile
Sequencer blocks
Sequences in Pool
Setpoint programmer blocks
Setpoint scheduler blocks
Signal tags
Soft Wire bytes
Stage blocks
Steps per schedule
Steps per sequence
Support of dual port scanner
Tag descriptor
Text bytes
214
Table 42 – System Size and Availability Summary
C30
384 points
142 points
40 points
375,000
20
400
Yes
1024
32
200
32
2240
300
No
No
50
50
64
No
HC900 Process & Safety Controller User and Installation Manual
C50
C70
4608 points
4608 points
2304 points
2304 points
400 points
400 points
Quantity based on available memory
Quantity based on available memory
375,000
375,000
20
40
2000
5000
Yes
Yes
Quantity based on available memory
1024
1024
32
32
Quantity based on available memory
1000
2500
32
32
2240
2240
300
300
Quantity based on available memory
User Configurable
Quantity based on available memory
User Configurable
No
No
No
Yes
User Configurable
50
50
Quantity based on available memory
User Configurable
Quantity based on available memory
Quantity based on available memory
Quantity based on available memory
Quantity based on available memory
Quantity based on available memory
50
50
64
64
No
No
Quantity based on available memory
Quantity based on available memory
C75
4608 points
2304 points
400 points
124,998
40
5000
No
1024
32
2500
32
2240
300
Yes
Yes
50
50
64
Yes
Revision 6
21 April 2017

Advertisement

Table of Contents
loading

Table of Contents