10.4 SLOPES AND HIGH SET THRESHOLD
The following table presents the results of analysis of an external fault on circuit C-2 (C-2 is connected to the North bus; C-
3, C-4 and C-5 are connected to the South bus).
By comparing the secondary currents (column 3 in the following table) with the limits of linear operation for the CTs (column
4 shown earlier in the Limits of Linear Operations of the CTs table) it is concluded that CT-2 will saturate during this fault
producing a spurious differential signal. All other CTs will not saturate due to the AC components. The amount of the spuri-
ous differential current (magnetizing current of CT-2) can be calculated using the burden, magnetizing characteristic and
the primary current of the said CT.
For I
= 116.67 A, R
s
ure, the solution is I
The magnetizing current of the saturated CT-2 will appear to the differential element protecting the North bus as a differen-
tial signal of 27.69 A, while the restraint signal will be the maximum of the bus currents (113.3 A). Consequently, the higher
slope of the characteristic should not be lower than 27.69 A / 113.3 A, or 24% and the pick up of the high-set differential
elements should not be lower than 27.69 A, or 2.77 pu.
Columns 6 and 7 of the following table summarize the DC saturation threat for the fault on C-2. CT-4, CT-6, CT-7, and CT-
8 may saturate due to the DC components and may generate spurious differential signal for both the North and South bus
relays depending on the bus configuration. The saturation will not occur before 4.7 ms and will be detected by the Satura-
tion Detector.
Table 10–5: EXTERNAL FAULT CALCULATIONS ON C-2
CT
CT-1
CT-2
CT-3
CT-4
CT-6
CT-7, CT-8
The following table presents the results of analysis of an external fault on circuit C-3 (C-3 is connected to the North bus; C-
4 and C-5 are connected to the South bus).
By comparing the secondary currents (column 3 in the table below) with the limits of linear operation for the CTs (column 4
in the Limits of Linear Operations of the CTs table shown earlier), it is concluded that none of the CTs will saturate due to
the AC currents during this fault.
Columns 6 and 7 of the table below summarize the DC saturation threat for the fault on C-3. CT-3, CT-4, CT-6, CT-7, and
CT-8 may saturate due to the DC components and may generate a spurious differential signal for both the North and South
bus relays depending on the bus configuration. The saturation will not occur before 11.18 ms and will be detected by the
Saturation Detector.
Table 10–6: CALCULATIONS FOR THE EXTERNAL FAULTS ON C-3
CT
CT-1
CT-2
CT-3
CT-4
10
CT-6
CT-7, CT-8
10-8
= 1.23 and the characteristic shown earlier in the Approximate CT Magnetizing Characteristics fig-
s
= 27.69 A, I
= 113.3 A.
magnetizing
relay
I
(KA)
I
(A SEC)
FAULT
FAULT
0
0.00
14.0
116.67
6.0
25.00
5.0
25.00
3.0
15.00
14.0
58.33
I
(KA)
I
(A SEC)
FAULT
FAULT
0
0.00
0
0.00
8.0
33.33
5.0
25.00
3.0
15.00
8.0
33.33
B30 Bus Differential System
T
(MS)
AC
DC
SATURATION
N/A
No
40
Yes
5
No
30
No
40
No
40
No
T
(MS)
AC
DC
SATURATION
N/A
No
N/A
No
40
No
30
No
40
No
40
No
10 APPLICATION OF SETTINGS
10.4.3 EXTERNAL FAULTS ON C-2
DC
T
(MS)
SAT
SATURATION
No
N/A
Yes
N/A
No
N/A
Yes
15.19
Yes
35.25
Yes
4.70
10.4.4 EXTERNAL FAULTS ON C-3
DC
T
(MS)
SAT
SATURATION
No
N/A
No
N/A
Yes
11.18
Yes
15.19
Yes
35.25
Yes
11.18
GE Multilin