GE B90 Instruction Manual
GE B90 Instruction Manual

GE B90 Instruction Manual

Ur series low impedance bus differential system
Hide thumbs Also See for B90:
Table of Contents

Advertisement

Title Page
GE
Digital Energy
GE Digital Energy
650 Markland Street
Markham, Ontario
Canada L6C 0M1
Tel: +1 905 927 7070 Fax: +1 905 927 5098
Internet:
http://www.GEDigitalEnergy.com
*1601-0115-U4*
B90 Low Impedance Bus Differential
UR Series Instruction Manual
Manual P/N: 1601-0115-U4 (GEK-113514C)
IND.CONT. EQ.
System
B90 revision: 5.7x
E83849
LISTED
52TL
836771A2.CDR
GE Multilin's Quality Management
System is registered to
ISO9001:2008
QMI # 005094
UL # A3775

Advertisement

Table of Contents
loading

Summary of Contents for GE B90

  • Page 1 Title Page Digital Energy B90 Low Impedance Bus Differential System UR Series Instruction Manual B90 revision: 5.7x Manual P/N: 1601-0115-U4 (GEK-113514C) 836771A2.CDR E83849 GE Digital Energy LISTED 650 Markland Street IND.CONT. EQ. 52TL Markham, Ontario GE Multilin's Quality Management Canada L6C 0M1...
  • Page 2 The contents of this manual are the property of GE Multilin Inc. This documentation is furnished on license and may not be reproduced in whole or in part without the permission of GE Multilin. The content of this manual is for informational use only and is subject to change without notice.
  • Page 3 ADDENDUM This addendum contains information that relates to the B90 Low Impedance Bus Differential System, version 5.7x. It outlines items that appear in the instruction manual GEK-113514C (revision U4) that are not included in the current B90 operations. The following functions and items are not yet available with the current version of the B90 relay: •...
  • Page 5: Table Of Contents

    1.3 ENERVISTA UR SETUP SOFTWARE 1.3.1 REQUIREMENTS ....................1-5 1.3.2 SOFTWARE INSTALLATION ................1-5 1.3.3 CONFIGURING THE B90 FOR SOFTWARE ACCESS ........1-6 1.3.4 USING THE QUICK CONNECT FEATURE............1-9 1.3.5 CONNECTING TO THE B90 RELAY............... 1-15 1.4 UR HARDWARE 1.4.1...
  • Page 6 USER-DEFINABLE DISPLAYS ................5-45 5.2.16 DIRECT INPUTS AND OUTPUTS..............5-47 5.2.17 INSTALLATION ....................5-55 5.3 SYSTEM SETUP 5.3.1 AC INPUTS.......................5-56 5.3.2 POWER SYSTEM ....................5-57 5.3.3 FLEXCURVES™ ....................5-58 5.3.4 BUS ........................5-65 5.4 FLEXLOGIC™ 5.4.1 INTRODUCTION TO FLEXLOGIC™..............5-67 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 7 DIRECT DEVICES STATUS................6-7 6.3 METERING 6.3.1 METERING CONVENTIONS ................6-8 6.3.2 BUS ZONE......................6-8 6.3.3 CURRENTS ....................... 6-9 6.3.4 VOLTAGES......................6-9 6.3.5 FREQUENCY..................... 6-9 6.3.6 IEC 61580 GOOSE ANALOG VALUES............6-10 GE Multilin B90 Low Impedance Bus Differential System...
  • Page 8 9.4 DIRECTIONAL PRINCIPLE 9.4.1 CURRENT DIRECTIONAL PROTECTION............9-6 9.5 SATURATION DETECTOR 9.5.1 CT SATURATION DETECTION .................9-7 9.6 OUTPUT LOGIC AND EXAMPLES 9.6.1 OUTPUT LOGIC ....................9-8 9.6.2 INTERNAL AND EXTERNAL FAULT EXAMPLE ..........9-8 viii B90 Low Impedance Bus Differential System GE Multilin...
  • Page 9 DATA FORMATS .....................B-50 C. IEC 61850 C.1 OVERVIEW COMMUNICATIONS C.1.1 INTRODUCTION....................C-1 C.1.2 COMMUNICATION PROFILES .................C-1 C.2 SERVER DATA ORGANIZATION C.2.1 OVERVIEW......................C-2 C.2.2 GGIO1: DIGITAL STATUS VALUES ..............C-2 C.2.3 GGIO2: DIGITAL CONTROL VALUES ..............C-2 GE Multilin B90 Low Impedance Bus Differential System...
  • Page 10 E.2.3 ANALOG INPUTS.................... E-10 F. MISCELLANEOUS F.1 CHANGE NOTES F.1.1 REVISION HISTORY..................F-1 F.1.2 CHANGES TO THE B90 MANUAL ..............F-1 F.2 ABBREVIATIONS F.2.1 STANDARD ABBREVIATIONS ................. F-6 F.3 WARRANTY F.3.1 GE MULTILIN WARRANTY................F-8 B90 Low Impedance Bus Differential System...
  • Page 11 TABLE OF CONTENTS INDEX GE Multilin B90 Low Impedance Bus Differential System...
  • Page 12 TABLE OF CONTENTS B90 Low Impedance Bus Differential System GE Multilin...
  • Page 13: Getting Started

    • Mounting screws For product information, instruction manual updates, and the latest software updates, please visit the GE Digital Energy website. If there is any noticeable physical damage, or any of the contents listed are missing, please contact GE Multilin immediately. NOTE...
  • Page 14: Ur Overview

    This new generation of equipment must also be easily incorporated into automation systems, at both the station and enterprise levels. The GE Multilin Universal Relay (UR) has been developed to meet these goals. B90 Low Impedance Bus Differential System...
  • Page 15: Hardware Architecture

    (dual) ring configuration. This feature is optimized for speed and intended for pilot- aided schemes, distributed logic applications, or the extension of the input/output capabilities of a single relay chassis. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 16: Ur Software Architecture

    Employing OOD/OOP in the software architecture of the B90 achieves the same features as the hardware architecture: modularity, scalability, and flexibility. The application software for any UR-series device (for example, feeder protection, transformer protection, distance protection) is constructed by combining objects from the various functionality classes.
  • Page 17: Enervista Ur Setup Software

    Video capable of displaying 800 x 600 or higher in high-color mode (16-bit color) • RS232 and/or Ethernet port for communications to the relay The following qualified modems have been tested to be compliant with the B90 and the EnerVista UR Setup software. • US Robotics external 56K FaxModem 5686 •...
  • Page 18: Configuring The B90 For Software Access

    OVERVIEW The user can connect remotely to the B90 through the rear RS485 port or the rear Ethernet port with a PC running the EnerVista UR Setup software. The B90 can also be accessed locally with a laptop computer through the front panel RS232 port or the rear Ethernet port using the Quick Connect feature.
  • Page 19 • To configure the B90 for local access with a laptop through either the front RS232 port or rear Ethernet port, refer to the Using the Quick Connect Feature section. An Ethernet module must be specified at the time of ordering for Ethernet communications.
  • Page 20 COMMUNICATIONS SERIAL PORTS 10. Click the Read Order Code button to connect to the B90 device and upload the order code. If an communications error occurs, ensure that the EnerVista UR Setup serial communications values entered in the previous step correspond to the relay setting values.
  • Page 21: Using The Quick Connect Feature

    B90. This ensures that configuration of the EnerVista UR Setup software matches the B90 model number. b) USING QUICK CONNECT VIA THE REAR ETHERNET PORTS To use the Quick Connect feature to access the B90 from a laptop through Ethernet, first assign an IP address to the relay from the front panel keyboard.
  • Page 22 Now, assign the laptop computer an IP address compatible with the relay’s IP address. From the Windows desktop, right-click the My Network Places icon and select Properties to open the network connections window. Right-click the Local Area Connection icon and select Properties. 1-10 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 23 Select the Internet Protocol (TCP/IP) item from the list provided and click the Properties button. Click on the “Use the following IP address” box. Enter an IP address with the first three numbers the same as the IP address of the B90 relay and the last number different (in this example, 1.1.1.2).
  • Page 24 Minimum = 0ms, Maximum = 0ms, Average = 0 ms Pinging 1.1.1.1 with 32 bytes of data: Verify the physical connection between the B90 and the laptop computer, and double-check the programmed IP address in setting, then repeat step 2 in the above procedure.
  • Page 25 If this computer is used to connect to the Internet, re-enable any proxy server settings after the laptop has been discon- nected from the B90 relay. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE enerVista CD or online from http://www.gedigitalenergy.com/multilin). See the Software Installation section for installation details.
  • Page 26 Device Setup menu, for the purpose of communicating to multiple relays. This feature allows the user to identify and interrogate, in seconds, all UR-series devices in a particular location. 1-14 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 27: Connecting To The B90 Relay

    The EnerVista UR Setup software has several new quick action buttons that provide users with instant access to several functions that are often performed when using B90 relays. From the online window, users can select which relay to interro- gate from a pull-down window, then click on the button for the action they wish to perform. The following quick action func- tions are available: •...
  • Page 28: Ur Hardware

    Figure 1–7: RELAY COMMUNICATIONS OPTIONS To communicate through the B90 rear RS485 port from a PC RS232 port, the GE Multilin RS232/RS485 converter box is required. This device (catalog number F485) connects to the computer using a “straight-through” serial cable. A shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the B90 rear communications port.
  • Page 29: Using The Relay

    LED off. The relay in the “Not Programmed” state will block signaling of any output relay. These conditions will remain until the relay is explicitly put in the “Programmed” state. Select the menu message    SETTINGS PRODUCT SETUP INSTALLATION RELAY SETTINGS RELAY SETTINGS: Not Programmed GE Multilin B90 Low Impedance Bus Differential System 1-17...
  • Page 30: Relay Passwords

    NOTE 1.5.6 FLEXLOGIC™ CUSTOMIZATION FlexLogic™ equation editing is required for setting up user-defined logic for customizing the relay operations. See the Flex- Logic™ section in Chapter 5 for additional details. 1-18 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 31: Commissioning

    1.5 USING THE RELAY 1.5.7 COMMISSIONING The B90 requires a minimum amount of maintenance when it is commissioned into service. Since the B90 is a micropro- cessor-based relay, its characteristics do not change over time. As such, no further functional tests are required.
  • Page 32 1.5 USING THE RELAY 1 GETTING STARTED 1-20 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 33: Product Description

    24 feeders. The B90 protection system is a centralized architecture built on three, four, or more B90 IEDs as per requirements of a particular application. Each IED of the B90 system is a full-featured B90 and as such can be accessed and programmed individually.
  • Page 34 User-programmable fault reports Event recorder User-programmable LEDs FlexLogic™ equations User-programmable pushbuttons IEC 61850 communications (optional) User-programmable self-tests Metering: current, voltage, frequency Virtual inputs (64 per IED) Modbus communications Virtual outputs (96 per IED) B90 Low Impedance Bus Differential System GE Multilin...
  • Page 35 2.1 INTRODUCTION The main protection functions of the B90 are provided on a per-phase basis. The AC signals of a given phase, both cur- rents and voltages, are connected and processed by a single IED. These IEDs provide for all the protection and monitoring functions that require the AC information.
  • Page 36 2.1 INTRODUCTION 2 PRODUCT DESCRIPTION The following figures show sample applications of the B90 protection system: ZONE 1 B90-A B90-B B90-C 836760A2.CDR Figure 2–3: SINGLE BUS ZONE 1 B90-A ZONE 2 B90-B B90-C B90-Logic 836761A2.CDR Figure 2–4: DOUBLE BUS ZONE 1...
  • Page 37 ZONE 1 B90-A B90-B B90-C B90-Logic ZONE 2 836764A2.CDR Figure 2–7: BREAKER-AND-A-HALF CONFIGURATION BUS ZONE 2 B90-A ZONE 1 B90-B B90-C B90-Logic 836765A2.CDR Figure 2–8: SINGLE BUS WITH A SINGLE TIE BREAKER GE Multilin B90 Low Impedance Bus Differential System...
  • Page 38 B90 SYSTEM NO. 2: ZONE 2 B90 SYSTEM NO. 1: ZONE 2 B90-A B90-A B90-B B90-B B90-C B90-C B90-Logic B90-Logic B90-Logic B90-Logic 836767A2.CDR Figure 2–10: APPLICATION INVOLVING TWO OR MORE B90 SYSTEMS B90 Low Impedance Bus Differential System GE Multilin...
  • Page 39: Ordering

    Before ordering the B90 system, an analysis of the required protection and monitoring functions is required. Please refer to the UR overview section in chapter 1 for details of the B90 architecture. Also, detailed analyses of required AC inputs and input/output contacts must be performed to select appropriate hardware configurations for each of the B90's IEDs.
  • Page 40: Replacement Modules

    Replacement modules can be ordered separately as shown below. When ordering a replacement CPU module or face- plate, please provide the serial number of your existing unit. Not all replacement modules may be applicable to the B90 relay. Only the modules specified in the order codes are available as replacement modules.
  • Page 41 2 PRODUCT DESCRIPTION 2.1 INTRODUCTION Replacement module codes are subject to change without notice. Refer to the GE Multilin ordering page at http:// http://www.gedigitalenergy.com/multilin/order.htm for the latest details concerning B90 ordering options. NOTE The replacement module order codes for the horizontal mount units are shown below.
  • Page 42: Specifications

    Instantaneous or Timed (per IEEE) Number of inputs: Time accuracy: ±3% or ±40 ms, whichever is greater Operate time: <2 ms at 60 Hz Time accuracy: ±3% or 10 ms, whichever is greater 2-10 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 43: User-Programmable Elements

    Pre-fault trigger: any FlexLogic™ operand input state; digital output state Fault trigger: any FlexLogic™ operand Data storage: in non-volatile memory Recorder quantities: 32 (any FlexAnalog value) EVENT RECORDER Capacity: 1024 events GE Multilin B90 Low Impedance Bus Differential System 2-11...
  • Page 44: Metering

    Unreturned message alarm: Responding to: Rate of unreturned messages in the ring configuration Monitoring message count: 10 to 10000 in steps of 1 Alarm threshold: 1 to 1000 in steps of 1 2-12 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 45: Power Supply

    95% voltage drop across the load impedance. Trickle current: approx. 1 to 2.5 mA Operate time: < 0.6 ms FORM-A CURRENT MONITOR Internal Limiting Resistor: 100 Ω, 2 W Threshold current: approx. 80 to 100 mA GE Multilin B90 Low Impedance Bus Differential System 2-13...
  • Page 46: Communications

    Maximum input –7.6 dBm –14 dBm –7 dBm power Typical distance 1.65 km 2 km 15 km Duplex full/half full/half full/half Redundancy The UR-2S and UR-2T only support 100 Mb multimode 2-14 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 47: Inter-Relay Communications

    Pollution degree: impaired at temperatures less than – Overvoltage category: 20°C Ingress protection: IP20 front, IP10 back HUMIDITY Humidity: operating up to 95% (non-condensing) at 55°C (as per IEC60068-2-30 variant 1, 6days). GE Multilin B90 Low Impedance Bus Differential System 2-15...
  • Page 48: Type Tests

    UL508 e83849 NKCR Safety UL C22.2-14 e83849 NKCR7 Safety UL1053 e83849 NKCR 2.2.12 PRODUCTION TESTS THERMAL Products go through an environmental test based upon an Accepted Quality Level (AQL) sampling process. 2-16 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 49: Approvals

    Units that are stored in a de-energized state should be powered up once per year, for one hour continuously, to avoid deterioration of electrolytic capacitors. NOTE GE Multilin B90 Low Impedance Bus Differential System 2-17...
  • Page 50 2.2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2-18 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 51: Hardware

    3.1.1 PANEL CUTOUT The B90 Low Impedance Bus Differential System is available as a 19-inch rack horizontal mount unit with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains additional user-programmable pushbuttons and LED indicators.
  • Page 52 [466,60 mm] 0.280” [7,11 mm] Typ. x 4 CUT-OUT 4.000” [101,60 mm] 17.750” [450,85 mm] 842808A1.CDR Figure 3–2: B90 HORIZONTAL MOUNTING (ENHANCED PANEL) Figure 3–3: B90 HORIZONTAL MOUNTING AND DIMENSIONS (STANDARD PANEL) B90 Low Impedance Bus Differential System GE Multilin...
  • Page 53: Module Withdrawal And Insertion

    The enhanced faceplate can be opened to the left, once the thumb screw has been removed, as shown below. This allows for easy accessibility of the modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens completely and allows easy access to all modules in the B90. 842812A1.CDR Figure 3–4: UR MODULE WITHDRAWAL AND INSERTION (ENHANCED FACEPLATE)
  • Page 54: Rear Terminal Layout

    NOTE The 4.0x release of the B90 relay includes new hardware modules.The new CPU modules are specified with codes 9E and higher. The new CT/VT modules are specified with the codes 8F and higher.
  • Page 55 3 HARDWARE 3.1 DESCRIPTION Figure 3–7: EXAMPLE OF MODULES IN F AND H SLOTS GE Multilin B90 Low Impedance Bus Differential System...
  • Page 56: Wiring

    CONTACT INPUT F7c CONTACT INPUT F8a CONTACT INPUT F8c COMMON F7b GE Consumer & Industrial Multilin SURGE B90 BUS DIFFERENTIAL RELAY IED 4 836780A2.CDR Figure 3–8: B90 IS A MULTI-IED PROTECTION SYSTEM B90 Low Impedance Bus Differential System GE Multilin...
  • Page 57 The wiring diagrams on the next four pages are based on the following order code: B90-H02-HCL-F8H-H6H-L8H-N6A-S8H-U6H-W7H. The purpose of these diagrams is to provide examples of how the B90 is typically wired, not specifically how to wire your own relay. Please refer to the sections following the wiring dia- grams for examples on connecting your relay correctly based on your relay configuration and order code.
  • Page 58 FILTER No. 10AWG Minimum 836776A4.CDR GROUND BUS MODULE ARRANGEMENT MODULES MUST BE GROUNDED IF TERMINAL IS PROVIDED Inputs/ Inputs/ Power Inputs/ outputs outputs Supply outputs Figure 3–9: TYPICAL WIRING DIAGRAM (PHASE A) B90 Low Impedance Bus Differential System GE Multilin...
  • Page 59 FILTER No. 10AWG Minimum 836777A4.CDR GROUND BUS MODULE ARRANGEMENT MODULES MUST BE GROUNDED IF TERMINAL IS PROVIDED Inputs/ Inputs/ Power Inputs/ outputs outputs Supply outputs Figure 3–10: TYPICAL WIRING DIAGRAM (PHASE B) GE Multilin B90 Low Impedance Bus Differential System...
  • Page 60 No. 10AWG Minimum 836778A4.CDR GROUND BUS MODULE ARRANGEMENT MODULES MUST BE GROUNDED IF TERMINAL IS PROVIDED Inputs/ Inputs/ Power Inputs/ outputs outputs Supply outputs Figure 3–11: TYPICAL WIRING DIAGRAM (PHASE C) 3-10 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 61 836779A4.CDR GROUND BUS MODULE ARRANGEMENT MODULES MUST BE GROUNDED IF TERMINAL Inputs/ Inputs/ Power Inputs/ IS PROVIDED supply outputs outputs outputs Figure 3–12: TYPICAL WIRING DIAGRAM (BREAKER FAIL AND ISOLATOR MONITORING) GE Multilin B90 Low Impedance Bus Differential System 3-11...
  • Page 62: Dielectric Strength

    (see the Self-test errors section in chapter 7) or control power is lost, the relay will de-energize. For high reliability systems, the B90 has a redundant option in which two B90 power supplies are placed in parallel on the bus.
  • Page 63: Ct And Vt Modules

    1 to 50000 A primaries and 1 A or 5 A secondaries may be used. Each B90 voltage input is intended for monitoring a single-phase voltage. The may include phase voltages or neutral volt- age from the open-delta VT.
  • Page 64: Contact Inputs And Outputs

    The terminal configuration for contact inputs is different for the two applications. The contact inputs are grouped with a common return. The B90 has two versions of grouping: four inputs per common return and two inputs per common return. When a contact input/output module is ordered, four inputs per common is used.
  • Page 65 Logic™ operand driving the contact output should be given a reset delay of 10 ms to prevent damage of NOTE the output contact (in situations when the element initiating the contact output is bouncing, at values in the region of the pickup value). GE Multilin B90 Low Impedance Bus Differential System 3-15...
  • Page 66 ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs 3-16 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 67 ~5a, ~5c 2 Inputs 2 Outputs Solid-State Solid-State ~6a, ~6c 2 Inputs 2 Outputs Not Used Not Used ~7a, ~7c 2 Inputs 2 Outputs Solid-State Solid-State ~8a, ~8c 2 Inputs Not Used GE Multilin B90 Low Impedance Bus Differential System 3-17...
  • Page 68 3.2 WIRING 3 HARDWARE Figure 3–16: CONTACT INPUT AND OUTPUT MODULE WIRING (1 of 2) 3-18 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 69 COMMON SURGE 842763A2.CDR Figure 3–17: CONTACT INPUT AND OUTPUT MODULE WIRING (2 of 2) For proper functionality, observe the polarity shown in the figures for all contact input and output connections. GE Multilin B90 Low Impedance Bus Differential System 3-19...
  • Page 70 There is no provision in the relay to detect a DC ground fault on 48 V DC control power external output. We recommend using an external DC supply. 3-20 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 71 = ON 842751A1.CDR Figure 3–20: AUTO-BURNISH DIP SWITCHES The auto-burnish circuitry has an internal fuse for safety purposes. During regular maintenance, the auto-burnish functionality can be checked using an oscilloscope. NOTE GE Multilin B90 Low Impedance Bus Differential System 3-21...
  • Page 72: Rs232 Faceplate Port

    3.2.6 RS232 FACEPLATE PORT A 9-pin RS232C serial port is located on the B90 faceplate for programming with a personal computer. All that is required to use this interface is a personal computer running the EnerVista UR Setup software provided with the relay. Cabling for the RS232 port is shown in the following figure for both 9-pin and 25-pin connectors.
  • Page 73 3 HARDWARE 3.2 WIRING Figure 3–22: CPU MODULE COMMUNICATIONS WIRING GE Multilin B90 Low Impedance Bus Differential System 3-23...
  • Page 74 To ensure maximum reliability, all equipment should have similar transient protection devices installed. Both ends of the RS485 circuit should also be terminated with an impedance as shown below. Figure 3–23: RS485 SERIAL CONNECTION 3-24 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 75: Irig-B

    RG58/59 COAXIAL CABLE RECEIVER TIME CODE GENERATOR BNC (IN) (DC SHIFT OR AMPLITUDE MODULATED SIGNAL CAN BE USED) REPEATER BNC (OUT) TO OTHER DEVICES (DC-SHIFT ONLY) 827756A5.CDR Figure 3–24: IRIG-B CONNECTION GE Multilin B90 Low Impedance Bus Differential System 3-25...
  • Page 76 UR-series relays can be synchronized. The IRIG-B repeater has a bypass function to maintain the time signal even when a relay in the series is powered down. Figure 3–25: IRIG-B REPEATER Using an amplitude modulated receiver will cause errors up to 1 ms in event time-stamping. NOTE 3-26 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 77: Direct Input/Output Communications

    3.3.1 DESCRIPTION The B90 direct inputs and outputs feature makes use of the type 7 series of communications modules. These modules are also used by the L90 Line Differential Relay for inter-relay communications. The direct input and output feature uses the communications channels provided by these modules to exchange digital state information between relays.
  • Page 78 These modules are listed in the following table. All fiber modules use ST type connectors. Not all the direct input and output communications modules may be applicable to the B90 relay. Only the modules specified in the order codes are available as direct input and output communications modules.
  • Page 79: Fiber: Led And Eled Transmitters

    2 Channels Figure 3–30: LASER FIBER MODULES When using a laser Interface, attenuators may be necessary to ensure that you do not exceed the maximum optical input power to the receiver. GE Multilin B90 Low Impedance Bus Differential System 3-29...
  • Page 80: Interface

    Remove the top cover by sliding it towards the rear and then lift it upwards. Set the timing selection switches (channel 1, channel 2) to the desired timing modes. Replace the top cover and the cover screw. 3-30 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 81 For connection to a higher order system (UR- to-multiplexer, factory defaults), set to octet timing (S1 = ON) and set timing mode to loop timing (S5 = OFF and S6 = OFF). GE Multilin B90 Low Impedance Bus Differential System 3-31...
  • Page 82 G.703 line side of the interface while the other lies on the differential Manchester side of the interface. DMR = Differential Manchester Receiver DMX = Differential Manchester Transmitter G7X = G.703 Transmitter G7R = G.703 Receiver 842775A1.CDR Figure 3–35: G.703 DUAL LOOPBACK MODE 3-32 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 83: Rs422 Interface

    1 as shown below. If the terminal timing feature is not available or this type of connection is not desired, the G.703 interface is a viable option that does not impose timing restrictions. GE Multilin B90 Low Impedance Bus Differential System 3-33...
  • Page 84 Figure 3–38: TIMING CONFIGURATION FOR RS422 TWO-CHANNEL, 3-TERMINAL APPLICATION Data module 1 provides timing to the B90 RS422 interface via the ST(A) and ST(B) outputs. Data module 1 also provides timing to data module 2 TT(A) and TT(B) inputs via the ST(A) and AT(B) outputs. The data module pin numbers have been omitted in the figure above since they may vary depending on the manufacturer.
  • Page 85: Rs422 And Fiber Interface

    Shield Tx – G.703 Rx – channel 1 Tx + Rx + Surge Fiber channel 2 842778A1.CDR Figure 3–41: G.703 AND FIBER INTERFACE CONNECTION GE Multilin B90 Low Impedance Bus Differential System 3-35...
  • Page 86: Ieee C37.94 Interface

    5.60. For customers using firmware release 5.60 and higher, the module can be identified with "Rev D" printed on the module and is to be used on all ends of B90 communi- cation for two and three terminal applications.
  • Page 87 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted. GE Multilin B90 Low Impedance Bus Differential System 3-37...
  • Page 88 3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS 3 HARDWARE Figure 3–42: IEEE C37.94 TIMING SELECTION SWITCH SETTING 3-38 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 89: C37.94Sm Interface

    5.60. For customers using firmware release 5.60 and higher, the module can be identified with "Rev D" printed on the module and is to be used on all ends of B90 communi- cation for two and three terminal applications.
  • Page 90 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted. 3-40 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 91 3 HARDWARE 3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS Figure 3–43: C37.94SM TIMING SELECTION SWITCH SETTING GE Multilin B90 Low Impedance Bus Differential System 3-41...
  • Page 92 3.3 DIRECT INPUT/OUTPUT COMMUNICATIONS 3 HARDWARE 3-42 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 93: Human Interfaces

    To start using the EnerVista UR Setup software, a site definition and device definition must first be created. See the EnerV- ista UR Setup Help File or refer to the Connecting EnerVista UR Setup with the B90 section in Chapter 1 for details.
  • Page 94 Site List window will automatically be sent to the on-line communicating device. g) FIRMWARE UPGRADES The firmware of a B90 device can be upgraded, locally or remotely, via the EnerVista UR Setup software. The correspond- ing instructions are provided by the EnerVista UR Setup Help file under the topic “Upgrading Firmware”.
  • Page 95: Enervista Ur Setup Main Window

    Device data view windows, with common tool bar. Settings file data view windows, with common tool bar. Workspace area with data view tabs. Status bar. 10. Quick action hot links. 842786A2.CDR Figure 4–1: ENERVISTA UR SETUP SOFTWARE MAIN WINDOW GE Multilin B90 Low Impedance Bus Differential System...
  • Page 96: Extended Enervista Ur Setup Features

    (settings file templates) and online devices (online settings templates). The func- tionality is identical for both purposes. The settings template feature requires that both the EnerVista UR Setup software and the B90 firmware are at ver- sions 5.40 or higher.
  • Page 97 The following procedure describes how to add password protection to a settings file template. Select a settings file from the offline window on the left of the EnerVista UR Setup main screen. Selecting the Template Mode > Password Protect Template option. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 98 The template specifies that only the Pickup Curve Phase time overcurrent settings window without template applied. settings be available. 842858A1.CDR Figure 4–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND B90 Low Impedance Bus Differential System GE Multilin...
  • Page 99 Select an installed device or settings file from the tree menu on the left of the EnerVista UR Setup main screen. Select the Template Mode > Remove Settings Template option. Enter the template password and click OK to continue. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 100: Securing And Locking Flexlogic™ Equations

    Click on Save to save and apply changes to the settings template. Select the Template Mode > View In Template Mode option to view the template. Apply a password to the template then click OK to secure the FlexLogic™ equation. B90 Low Impedance Bus Differential System GE Multilin...
  • Page 101 FlexLogic™ entries in a settings file have been secured, use the following procedure to lock the settings file to a specific serial number. Select the settings file in the offline window. Right-click on the file and select the Edit Settings File Properties item. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 102: Settings File Traceability

    When a settings file is transfered to a B90 device, the date, time, and serial number of the B90 are sent back to EnerVista UR Setup and added to the settings file on the local PC. This infor- mation can be compared with the B90 actual values at any later date to determine if security has been compromised.
  • Page 103 4.2 EXTENDED ENERVISTA UR SETUP FEATURES The transfer date of a setting file written to a B90 is logged in the relay and can be viewed via EnerVista UR Setup or the front panel display. Likewise, the transfer date of a setting file saved to a local PC is logged in EnerVista UR Setup.
  • Page 104 ONLINE DEVICE TRACEABILITY INFORMATION The B90 serial number and file transfer date are available for an online device through the actual values. Select the Actual Values > Product Info > Model Information menu item within the EnerVista UR Setup online window as shown in the example below.
  • Page 105: Faceplate Interface

    LED panel 2 LED panel 3 Display Front panel RS232 port Small user-programmable User-programmable Keypad (control) pushbuttons 1 to 7 pushbuttons 1 to 12 827801A7.CDR Figure 4–16: UR-SERIES STANDARD HORIZONTAL FACEPLATE PANELS GE Multilin B90 Low Impedance Bus Differential System 4-13...
  • Page 106: Led Indicators

    OTHER: This LED indicates a composite function was involved. • PHASE A: This LED indicates phase A was involved. • PHASE B: This LED indicates phase B was involved. • PHASE C: This LED indicates phase C was involved. 4-14 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 107 Support for applying a customized label beside every LED is provided. Default labels are shipped in the label pack- age of every B90, together with custom templates. The default labels can be replaced by user-printed labels. User customization of LED operation is of maximum benefit in installations where languages other than English are used to communicate with operators.
  • Page 108: Custom Labeling Of Leds

    SETTINGS IN USE 842783A1.CDR Figure 4–20: LED PANEL 2 (DEFAULT LABELS) 4.3.3 CUSTOM LABELING OF LEDS a) ENHANCED FACEPLATE The following procedure requires the pre-requisites listed below. 4-16 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 109 Enter the text to appear next to each LED and above each user-programmable pushbuttons in the fields provided. Feed the B90 front panel label cutout sheet into a printer and press the Print button in the front panel report window.
  • Page 110 Bend the tabs at the left end of the tool upwards as shown below. Bend the tab at the center of the tool tail as shown below. The following procedure describes how to remove the LED labels from the B90 enhanced front panel and insert the custom labels.
  • Page 111 Slide the new LED label inside the pocket until the text is properly aligned with the LEDs, as shown below. The following procedure describes how to remove the user-programmable pushbutton labels from the B90 enhanced front panel and insert the custom labels.
  • Page 112 Slide the label tool under the user-programmable pushbutton label until the tabs snap out as shown below. This will attach the label tool to the user-programmable pushbutton label. Remove the tool and attached user-programmable pushbutton label as shown below. 4-20 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 113 The panel templates provide relative LED locations and located example text (x) edit boxes. The following procedure demonstrates how to install/uninstall the custom panel labeling. Remove the clear Lexan Front Cover (GE Multilin part number: 1501-0014). Push in...
  • Page 114: Display

    Microsoft Word 97 or later software for editing the template. • 1 each of: 8.5" x 11" white paper, exacto knife, ruler, custom display module (GE Multilin Part Number: 1516-0069), and a custom module cover (GE Multilin Part Number: 1502-0015).
  • Page 115: Changing Settings

    4.3.7 CHANGING SETTINGS a) ENTERING NUMERICAL DATA Each numerical setting has its own minimum, maximum, and increment value associated with it. These parameters define what values are acceptable for a setting. GE Multilin B90 Low Impedance Bus Differential System 4-23...
  • Page 116 For example: to enter the text, “Breaker #1”. Press the decimal to enter text edit mode. Press the VALUE keys until the character 'B' appears; press the decimal key to advance the cursor to the next position. 4-24 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 117 In Service LED will turn on. e) ENTERING INITIAL PASSWORDS The B90 supports password entry from a local or remote connection. Local access is defined as any access to settings or commands via the faceplate interface. This includes both keypad entry and the faceplate RS232 connection.
  • Page 118 FlexLogic™ operand will be set to “On” and REMOTE ACCESS DENIED the B90 will not allow Settings or Command access via the any external communications interface for the next ten minutes. FlexLogic™ operand will be set to “Off” after the expiration of the ten-minute timeout.
  • Page 119: Overview

      SETTINGS  AC INPUTS See page 5-56.  SYSTEM SETUP   POWER SYSTEM See page 5-57.   FLEXCURVES See page 5-58.   BUS See page 5-65.  GE Multilin B90 Low Impedance Bus Differential System...
  • Page 120 See page 5-117.   VIRTUAL OUTPUTS See page 5-119.   REMOTE DEVICES See page 5-120.   REMOTE INPUTS See page 5-121.   REMOTE DPS INPUTS See page 5-122.  B90 Low Impedance Bus Differential System GE Multilin...
  • Page 121: Introduction To Elements

    For current elements, the ‘base quantity’ is the nominal secondary or primary current of the CT. For voltage elements the ‘base quantity’ is the nominal primary voltage of the protected system which corresponds (based on VT ratio and connection) to secondary VT voltage applied to the relay. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 122 The DPO event is created when the measure and decide comparator output transits from the pickup state (logic 1) to the dropout state (logic 0). This could happen when the element is in the operate state if the reset delay time is not ‘0’. B90 Low Impedance Bus Differential System GE Multilin...
  • Page 123: Product Setup

    (both protection B90 FUNCTION and logic), download the same file to all the B90 IEDs, and modify the settings accordingly to finalize the application. Com- munications and settings are typically modified when downloading the common B90 setting file.
  • Page 124 When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond- ing connection password. If the connection is to the back of the B90, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.
  • Page 125 The new password is accepted and a value is assigned to the item. ENCRYPTED PASSWORD If a command or setting password is lost (or forgotten), consult the factory with the corresponding Encrypted Password value. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 126 INVALID ATTEMPS BEFORE LOCKOUT The B90 provides a means to raise an alarm upon failed password entry. Should password verification fail while accessing a password-protected level of the relay (either settings or commands), the FlexLogic™ operand is UNAUTHORIZED ACCESS asserted.
  • Page 127 If access is permitted and an off-to-on transition of the FlexLogic™ operand is detected, the timeout is restarted. The status of this timer is updated every 5 seconds. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 128: Display Properties

    Some customers prefer very low currents to display as zero, while others prefer the current be displayed even when the value reflects noise rather than the actual signal. The B90 applies a cut- off value to the magnitudes and angles of the measured currents.
  • Page 129: Clear Relay Records

    Selected records can be cleared from user-programmable conditions with FlexLogic™ operands. Assigning user-program- mable pushbuttons to clear specific records are typical applications for these commands. Since the B90 responds to rising edges of the configured FlexLogic™ operands, they must be asserted for at least 50 ms to take effect.
  • Page 130: Communications

    0 ms The B90 is equipped with up to three independent serial communication ports. The faceplate RS232 port is intended for local use and is fixed at 19200 baud and no parity. The rear COM1 port type is selected when ordering: either an Ethernet or RS485 port.
  • Page 131 MODBUS SLAVE ADDRESS grammed. For the RS485 ports each B90 must have a unique address from 1 to 254. Address 0 is the broadcast address which all Modbus slave devices listen to. Addresses do not have to be sequential, but no two devices can have the same address or conflicts resulting in errors will occur.
  • Page 132 Range: 0 to 100000000 in steps of 1 DNP OTHER DEFAULT MESSAGE DEADBAND: 30000 Range: 1 to 10080 min. in steps of 1 DNP TIME SYNC IIN MESSAGE PERIOD: 1440 min 5-14 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 133 TIMEOUT: 120 s The B90 supports the Distributed Network Protocol (DNP) version 3.0. The B90 can be used as a DNP slave device con- nected to multiple DNP masters (usually an RTU or a SCADA master station). Since the B90 maintains two sets of DNP data change buffers and connection information, two DNP masters can actively communicate with the B90 at one time.
  • Page 134 DNP analog input points that are voltages will be returned with values 1000 times smaller (for example, a value of 72000 V on the B90 will be returned as 72). These settings are useful when analog input values must be adjusted to fit within cer- tain ranges in DNP masters.
  • Page 135 (for circuit breakers) or raise/lower (for tap changers) using a single control point. That is, the DNP master can operate a single point for both trip and close, or raise and lower, operations. The B90 can be configured to sup- port paired control points, with each paired control point operating two virtual inputs.
  • Page 136 The B90 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supported over two protocol stacks: TCP/IP over ethernet and TP4/CLNP (OSI) over ethernet. The B90 operates as an IEC 61850 server. The Remote inputs and outputs section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme.
  • Page 137 IEC 61850 GSSE application ID name string sent as part of each GSSE message. This GSSE ID string identifies the GSSE message to the receiving device. In B90 releases previous to 5.0x, this name string was repre- sented by the setting.
  • Page 138 DESTINATION MAC address; the least significant bit of the first byte must be set. In B90 releases previous to 5.0x, the destination Ethernet MAC address was determined automatically by taking the sending MAC address (that is, the unique, local MAC address of the B90) and setting the multicast bit.
  • Page 139 The B90 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station components.
  • Page 140 GGIO1 INDICATION 1 a contact input, virtual input, a protection element status, etc.). The B90 must be rebooted (control power removed and re-applied) before these settings take effect. The following procedure illustrates the reception configuration. Configure the reception dataset by making the following changes in the ...
  • Page 141 DNA and UserSt bit pairs that are included in GSSE messages. To set up a B90 to receive a configurable GOOSE dataset that contains two IEC 61850 single point status indications, the following dataset items can be selected (for example, for configurable GOOSE dataset 1): “GGIO3.ST.Ind1.stVal” and “GGIO3.ST.Ind2.stVal”.
  • Page 142 CPU resources. When server scanning is disabled, there will be not updated to the IEC 61850 logical node sta- tus values in the B90. Clients will still be able to connect to the server (B90 relay), but most data values will not be updated.
  • Page 143 5 SETTINGS 5.2 PRODUCT SETUP The main menu for the IEC 61850 MMXU deadbands is shown below. The IEC 61850 MMXU deadband settings cannot be used with the B90 Low Impedance Bus Differential System. NOTE     PATH: SETTINGS...
  • Page 144 The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0” (status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the B90 virtual inputs.
  • Page 145 Internet Explorer or Mozilla Firefox. This feature is available only if the B90 has the ethernet option installed. The web pages are organized as a series of menus that can be accessed starting at the B90 “Main Menu”. Web pages are available showing DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, etc.
  • Page 146 NUMBER: The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the B90 over a network. The B90 operates as a TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file obtained from the B90 contains a list and description of all available files (event records, oscillography, etc.).
  • Page 147: Modbus User Map

    B90 clock is closely synchronized with the SNTP/NTP server. It may take up to two minutes for the B90 to signal an SNTP self-test error if the server is offline.
  • Page 148: Real Time Clock

    SNTP, the offset is used to determine the local time for the B90 clock, since SNTP provides UTC time. The daylight savings time (DST) settings can be used to allow the B90 clock can follow the DST rules of the local time zone.
  • Page 149: User-Programmable Fault Report

    The user programmable record contains the following information: the user-programmed relay name, detailed firmware revision (5.7x, for example) and relay model (B90), the date and time of trigger, the name of pre-fault trigger (a specific FlexLogic™ operand), the name of fault trigger (a specific FlexLogic™ operand), the active setting group at pre-fault trig- ger, the active setting group at fault trigger, pre-fault values of all programmed analog channels (one cycle before pre-fault trigger), and fault values of all programmed analog channels (at the fault trigger).
  • Page 150: Oscillography

    Reducing the sampling rate allows longer records to be stored. This setting has no effect on the internal sampling rate of the relay which is always 64 samples per cycle; that is, it has no effect on the fundamental calculations of the device. 5-32 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 151 - entering this number via the relay keypad will cause the corresponding parameter to be displayed. If there are no CT/VT modules and analog input modules, no analog traces will appear in the file; only the digital traces will appear. GE Multilin B90 Low Impedance Bus Differential System 5-33...
  • Page 152: User-Programmable Leds

    The test responds to the position and rising edges of the control input defined by the set- LED TEST CONTROL ting. The control pulses must last at least 250 ms to take effect. The following diagram explains how the test is executed. 5-34 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 153 2. Once stage 2 has started, the pushbutton can be released. When stage 2 is completed, stage 3 will automatically start. The test may be aborted at any time by pressing the pushbutton. GE Multilin B90 Low Impedance Bus Differential System 5-35...
  • Page 154 LED 19 operand LED 8 operand LED 20 operand LED 9 operand LED 21 operand LED 10 operand LED 22 operand LED 11 operand LED 23 operand LED 12 operand LED 24 operand 5-36 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 155: User-Programmable Self Tests

    Refer to the Relay self-tests section in chapter 7 for additional information on major and minor self-test alarms. self-test is not applicable to the B90 device. ETHERNET SWITCH FAIL FUNCTION NOTE 5.2.12 CONTROL PUSHBUTTONS...
  • Page 156 The location of the control pushbuttons are shown in the following figures. Control pushbuttons 842813A1.CDR Figure 5–3: CONTROL PUSHBUTTONS (ENHANCED FACEPLATE) An additional four control pushbuttons are included on the standard faceplate when the B90 is ordered with the twelve user- programmable pushbutton option. STATUS EVENT CAUSE...
  • Page 157: User-Programmable Pushbuttons

    FlexLogic™ equations, protection elements, and control elements. Typical applications include breaker control, autorecloser blocking, and setting groups changes. The user-programmable pushbuttons are under the control level of password protection. The user-configurable pushbuttons for the enhanced faceplate are shown below. GE Multilin B90 Low Impedance Bus Differential System 5-39...
  • Page 158 The pulse duration of the remote set, remote reset, or local pushbutton must be at least 50 ms to operate the push- button. This allows the user-programmable pushbuttons to properly operate during power cycling events and vari- ous system disturbances that may cause transient assertion of the operating signals. NOTE 5-40 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 159 PUSHBTN 1 RESET • PUSHBTN 1 LOCAL: This setting assigns the FlexLogic™ operand serving to inhibit pushbutton operation from the front panel pushbuttons. This locking functionality is not applicable to pushbutton autoreset. GE Multilin B90 Low Impedance Bus Differential System 5-41...
  • Page 160 “High Priority” or “Normal”. PUSHBTN 1 MESSAGE • PUSHBUTTON 1 EVENTS: If this setting is enabled, each pushbutton state change will be logged as an event into event recorder. 5-42 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 161 SETTING SETTING Autoreset Delay Autoreset Function = Enabled = Disabled SETTING Drop-Out Timer TIMER FLEXLOGIC OPERAND 200 ms PUSHBUTTON 1 ON 842021A3.CDR Figure 5–8: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 1 of 2) GE Multilin B90 Low Impedance Bus Differential System 5-43...
  • Page 162: Flex State Parameters

    16 states may be read out in a single Modbus register. The state bits can be configured so that all of the states which are of interest to the user are available in a minimum number of Modbus registers. 5-44 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 163: User-Definable Displays

    INVOKE AND SCROLL play, not at the first user-defined display. The pulses must last for at least 250 ms to take effect. INVOKE AND SCROLL GE Multilin B90 Low Impedance Bus Differential System 5-45...
  • Page 164 4 seconds. While viewing a user display, press the ENTER key and then select the ‘Yes” option to remove the display from the user display list. Use the MENU key again to exit the user displays menu. 5-46 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 165: Direct Inputs And Outputs

    On type 7 cards that sup- port two channels, direct output messages are sent from both channels simultaneously. This effectively sends direct output GE Multilin B90 Low Impedance Bus Differential System 5-47...
  • Page 166 0.2 of a power system cycle at 128 kbps and 0.4 of a power system cycle at 64 kbps, per each ‘bridge’. For B90 applications, the should be set to 128 kbps. DIRECT I/O DATA RATE 5-48 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 167 The following application examples illustrate the basic concepts for direct input and output configuration. Please refer to the Inputs and outputs section in this chapter for information on configuring FlexLogic™ operands (flags, bits) to be exchanged. GE Multilin B90 Low Impedance Bus Differential System 5-49...
  • Page 168 BLOCK UR IED 4 UR IED 2 UR IED 3 842712A1.CDR Figure 5–11: SAMPLE INTERLOCKING BUSBAR PROTECTION SCHEME For increased reliability, a dual-ring configuration (shown below) is recommended for this application. 5-50 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 169 The complete application requires addressing a number of issues such as failure of both the communications rings, failure or out-of-service conditions of one of the relays, etc. Self-monitoring flags of the direct inputs and outputs feature would be primarily used to address these concerns. GE Multilin B90 Low Impedance Bus Differential System 5-51...
  • Page 170 Inputs and outputs section. A blocking pilot-aided scheme should be implemented with more security and, ideally, faster message delivery time. This could be accomplished using a dual-ring configuration as shown below. 5-52 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 171 EVENTS: Disabled The B90 checks integrity of the incoming direct input and output messages using a 32-bit CRC. The CRC alarm function is available for monitoring the communication medium noise by tracking the rate of messages failing the CRC check. The monitoring function counts all incoming messages, including messages that failed the CRC check.
  • Page 172 MESSAGE EVENTS: Disabled The B90 checks integrity of the direct input and output communication ring by counting unreturned messages. In the ring configuration, all messages originating at a given device should return within a pre-defined period of time. The unreturned messages alarm function is available for monitoring the integrity of the communication ring by tracking the rate of unre- turned messages.
  • Page 173: Installation

    This name will appear on generated reports. This name RELAY NAME is also used to identify specific devices which are engaged in automatically sending/receiving data over the Ethernet com- munications channel using the IEC 61850 protocol. GE Multilin B90 Low Impedance Bus Differential System 5-55...
  • Page 174: System Setup

    CT F1 SECONDARY: MESSAGE This menu configures the AC current inputs. Upon power up, the B90 recognizes all the AC modules loaded in its chassis and populates the above menu accordingly. The current terminals are denoted in the following format: Xa, where X = {F, L, S} and a = (1, 2,..., 8}. X represents the chassis slot containing the AC input module and a represents the AC channel of each module.
  • Page 175: Power System

    UR-series relays provided the relays have an IRIG-B connection. should only be set to "Disabled" in very unusual circumstances; consult the factory for spe- FREQUENCY TRACKING cial variable-frequency applications. NOTE GE Multilin B90 Low Impedance Bus Differential System 5-57...
  • Page 176: Flexcurves

    1; that is, 0.98 pu and 1.03 pu. It is recommended to set the two times to a similar value; otherwise, the lin- NOTE ear approximation may result in undesired behavior for the operating quantity that is close to 1.00 pu. 5-58 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 177 The multiplier and adder settings only affect the curve portion of the characteristic and not the MRT and HCT set- tings. The HCT settings override the MRT settings for multiples of pickup greater than the HCT ratio. NOTE GE Multilin B90 Low Impedance Bus Differential System 5-59...
  • Page 178 EnerVista UR Setup software generates an error message and discards the proposed changes. NOTE e) STANDARD RECLOSER CURVES The standard recloser curves available for the B90 are displayed in the following graphs. 5-60 B90 Low Impedance Bus Differential System...
  • Page 179 Figure 5–19: RECLOSER CURVES GE101 TO GE106 GE142 GE138 GE120 GE113 0.05 7 8 9 10 12 CURRENT (multiple of pickup) 842725A1.CDR Figure 5–20: RECLOSER CURVES GE113, GE120, GE138 AND GE142 GE Multilin B90 Low Impedance Bus Differential System 5-61...
  • Page 180 Figure 5–21: RECLOSER CURVES GE134, GE137, GE140, GE151 AND GE201 GE152 GE141 GE131 GE200 7 8 9 10 12 CURRENT (multiple of pickup) 842728A1.CDR Figure 5–22: RECLOSER CURVES GE131, GE141, GE152, AND GE200 5-62 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 181 Figure 5–23: RECLOSER CURVES GE133, GE161, GE162, GE163, GE164 AND GE165 GE132 GE139 GE136 GE116 0.05 GE117 GE118 0.02 0.01 7 8 9 10 12 CURRENT (multiple of pickup) 842726A1.CDR Figure 5–24: RECLOSER CURVES GE116, GE117, GE118, GE132, GE136, AND GE139 GE Multilin B90 Low Impedance Bus Differential System 5-63...
  • Page 182 Figure 5–25: RECLOSER CURVES GE107, GE111, GE112, GE114, GE115, GE121, AND GE122 GE202 GE135 GE119 7 8 9 10 12 CURRENT (multiple of pickup) 842727A1.CDR Figure 5–26: RECLOSER CURVES GE119, GE135, AND GE202 5-64 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 183: Bus

    Please refer to the Ordering section in chapter 2 for detailed infor- mation on the maximum number of zones and inputs for a given B90 model. Four bus differential zones are available. Each zone is associated with its own bus differential protection and CT trouble monitoring elements.
  • Page 184 5.3 SYSTEM SETUP 5 SETTINGS For example, assume that B90 IED 4 is used for isolator monitoring while IEDs 1, 2, and 3 are used for protection. Conse- quently, the setting of IED 4 must be set to “Logic” while...
  • Page 185: Flexlogic

    Figure 5–29: UR ARCHITECTURE OVERVIEW The states of all digital signals used in the B90 are represented by flags (or FlexLogic™ operands, which are described later in this section). A digital “1” is represented by a 'set' flag. Any external contact change-of-state can be used to block an element from operating, as an input to a control feature in a FlexLogic™...
  • Page 186 Some types of operands are present in the relay in multiple instances; e.g. contact and remote inputs. These types of oper- ands are grouped together (for presentation purposes only) on the faceplate display. The characteristics of the different types of operands are listed in the table below. Table 5–6: B90 FLEXLOGIC™ OPERAND TYPES OPERAND TYPE STATE...
  • Page 187 5 SETTINGS 5.4 FLEXLOGIC™ The operands available for this relay are listed alphabetically by types in the following table. Table 5–7: B90 FLEXLOGIC™ OPERANDS (Sheet 1 of 4) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION CONTROL CONTROL PUSHBTN 1 ON Control pushbutton 1 is being pressed...
  • Page 188 5.4 FLEXLOGIC™ 5 SETTINGS Table 5–7: B90 FLEXLOGIC™ OPERANDS (Sheet 2 of 4) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT LATCH 1 ON Non-volatile latch 1 is ON (Logic = 1) Non-volatile latches LATCH 1 OFF Non-volatile latch 1 is OFF (Logic = 0)
  • Page 189 5 SETTINGS 5.4 FLEXLOGIC™ Table 5–7: B90 FLEXLOGIC™ OPERANDS (Sheet 3 of 4) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION LED INDICATORS: LED IN SERVICE Asserted when the front panel IN SERVICE LED is on. Fixed front panel LED TROUBLE Asserted when the front panel TROUBLE LED is on.
  • Page 190 5.4 FLEXLOGIC™ 5 SETTINGS Table 5–7: B90 FLEXLOGIC™ OPERANDS (Sheet 4 of 4) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION USER- PUSHBUTTON 1 ON Pushbutton number 1 is in the “On” position PROGRAMMABLE PUSHBUTTON 1 OFF Pushbutton number 1 is in the “Off” position...
  • Page 191: Flexlogic™ Rules

    If it is necessary to re-initialize FlexLogic™ during testing, for example, it is suggested to power the unit down and then back up. GE Multilin B90 Low Impedance Bus Differential System 5-73...
  • Page 192: Flexlogic™ Example

    Dropout State=Pickup (200 ms) DIGITAL ELEMENT 2 Timer 1 State=Operated Time Delay on Pickup (800 ms) CONTACT INPUT H1c State=Closed VIRTUAL OUTPUT 3 827026A2.VSD Figure 5–31: LOGIC EXAMPLE WITH VIRTUAL OUTPUTS 5-74 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 193 Following the procedure outlined, start with parameter 99, as follows: 99: The final output of the equation is virtual output 3, which is created by the operator "= Virt Op n". This parameter is therefore "= Virt Op 3." GE Multilin B90 Low Impedance Bus Differential System 5-75...
  • Page 194 87: The input just below the upper input to OR #1 is operand “Virt Op 2 On". 86: The upper input to OR #1 is operand “Virt Op 1 On". 85: The last parameter is used to set the latch, and is operand “Virt Op 4 On". 5-76 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 195 In the following equation, virtual output 3 is used as an input to both latch 1 and timer 1 as arranged in the order shown below: DIG ELEM 2 OP Cont Ip H1c On AND(2) GE Multilin B90 Low Impedance Bus Differential System 5-77...
  • Page 196: Flexlogic™ Equation Editor

    TIMER 1 TYPE: This setting is used to select the time measuring unit. • TIMER 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set this function to "0". 5-78 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 197: Non-Volatile Latches

    LATCH N LATCH N LATCH N TYPE RESET Reset Dominant Previous Previous State State Dominant Previous Previous State State Figure 5–37: NON-VOLATILE LATCH OPERATION TABLE (N = 1 to 16) AND LOGIC GE Multilin B90 Low Impedance Bus Differential System 5-79...
  • Page 198: Overview

    Each of the six setting group menus is identical. Setting group 1 (the default active group) automatically becomes active if no other group is active (see Section 5.6.3: Setting Groups on page 5–106 for further details). 5-80 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 199: Bus Differential

    The biased bus differential function has a dual-slope operating characteristic (see figure below) operating in conjunction with saturation detection and a directional comparison principle (refer to the Bus zone 1 differential scheme logic figure in this section). GE Multilin B90 Low Impedance Bus Differential System 5-81...
  • Page 200 CTs operating in their linear mode, i.e. in load conditions and during distant external faults. When adjusting this setting, it must be kept in mind that the restraining signal used by the biased bus differential protection element is created as the maximum of all the input currents. 5-82 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 201 BF function to iso- late the entire zone of busbar protection. More information on the bus zone differential settings can be found in the Application of settings chapter. GE Multilin B90 Low Impedance Bus Differential System 5-83...
  • Page 202 5.5 GROUPED ELEMENTS 5 SETTINGS Figure 5–39: BUS ZONE 1 DIFFERENTIAL SCHEME LOGIC 5-84 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 203: Breaker Failure

    Range: Yes, No BF1 USE TIMER 2: MESSAGE Range: 0.000 to 65.535 s in steps of 0.001 BF1 TIMER 2 PICKUP MESSAGE DELAY: 0.000 s Range: Yes, No BF1 USE TIMER 3: MESSAGE GE Multilin B90 Low Impedance Bus Differential System 5-85...
  • Page 204 Range: Enabled, Disabled BF1 EVENTS: MESSAGE Disabled  BREAKER FAILURE  CURRENT SUPV 2  BREAKER FAILURE 2  ↓  BREAKER FAILURE  CURRENT SUPV 24  BREAKER FAILURE 24  5-86 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 205 PRODUCT SETUP B90 FUNCTION setting is “Logic”. The Breaker failure element requires B90 fiber optic interconnection and proper configura- B90 FUNCTION tion of the breaker failure and direct input/output settings. Refer to the Application of settings chapter for additional details.
  • Page 206 BF1 USE SEAL-IN: If set to "Yes", the element will only be sealed-in if current flowing through the breaker is above the supervision pickup level. • BF1 AMP SUPV OP A through C: This setting selects the B90 Remote Inputs that represent operation of the current supervision elements on phase A, B, or C. •...
  • Page 207 BF1 AMP LOSET PICKUP: This setting is used to set the phase current fault detection level. Generally this setting should detect the lowest expected fault current on the protected breaker, after a breaker opening resistor is inserted approximately 90% of resistor current). Figure 5–40: BREAKER FAILURE CURRENT SUPERVISION LOGIC GE Multilin B90 Low Impedance Bus Differential System 5-89...
  • Page 208 5.5 GROUPED ELEMENTS 5 SETTINGS Figure 5–41: BREAKER FAILURE LOGIC 5-90 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 209 DIRECT INPUT 6 BIT NUMBER : "3" (message received from IED 3) DIRECT INPUT 7 DEVICE : "13" (this is BKRSUPV 3 SUPV OP for Phase C) DIRECT INPUT 7 BIT NUMBER GE Multilin B90 Low Impedance Bus Differential System 5-91...
  • Page 210 BF 3 AMP LOSET OP C The B90 current supervision elements reset in less than 0.7 of a power cycle up to the multiple of pickup of 100 (threshold set at 0.01 of the actual fault current) as shown below.
  • Page 211: Voltage Elements

    The undervoltage element supervises (low-voltage check) current based main protection (that is, differential, breaker fail- ure, end fault, and time overcurrent backup protection). The B90 accepts phase-to-ground or phase-to-phase voltage input configurations. If the intention is to operate all three phases for any one phase voltage collapse, appropriate FlexLogic™...
  • Page 212: Current Elements

    See page 5-99.  OVERCURRENT 24  TIME MESSAGE See page 5-100.  OVERCURRENT  TIME MESSAGE See page 5-100.  OVERCURRENT ↓  TIME MESSAGE See page 5-100.  OVERCURRENT 24 5-94 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 213 5.5 GROUPED ELEMENTS b) INVERSE TOC CURVE CHARACTERISTICS The inverse time overcurrent curves used by the time overcurrent elements are the IEEE, IEC, GE Type IAC, and I t stan- dard curve shapes. This allows for simplified coordination with downstream devices.
  • Page 214 38.634 22.819 14.593 11.675 10.130 9.153 8.470 7.960 7.562 7.241 51.512 30.426 19.458 15.567 13.507 12.204 11.294 10.614 10.083 9.654 10.0 64.390 38.032 24.322 19.458 16.883 15.255 14.117 13.267 12.604 12.068 5-96 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 215 1.067 0.668 0.526 0.451 0.404 0.371 0.346 0.327 0.311 0.80 2.446 1.423 0.890 0.702 0.602 0.538 0.494 0.461 0.435 0.415 1.00 3.058 1.778 1.113 0.877 0.752 0.673 0.618 0.576 0.544 0.518 GE Multilin B90 Low Impedance Bus Differential System 5-97...
  • Page 216 = characteristic constant, and T = reset time in seconds (assuming energy capacity is 100% RESET is “Timed”) RESET Table 5–15: GE TYPE IAC INVERSE TIME CURVE CONSTANTS IAC CURVE SHAPE IAC Extreme Inverse 0.0040 0.6379 0.6200 1.7872 0.2461...
  • Page 217 Range: 0.000 to 65.535 s in steps of 0.001 IOC1 RESET DELAY: MESSAGE 0.000 s Range: FlexLogic™ operand IOC1 BLOCK: MESSAGE Range: Self-Reset, Latched, Disabled IOC1 TARGET: MESSAGE Self-Reset Range: Enabled, Disabled IOC1 EVENTS: MESSAGE Disabled GE Multilin B90 Low Impedance Bus Differential System 5-99...
  • Page 218 FlexLogic™ operands are passed between the IEDs using the B90 fiber optic communications (Direct I/Os). Instantaneous Overcurrent supervision can also be used to prevent tripping feeders with low currents or for definite time backup protection.
  • Page 219: End Fault Protection

    The End Fault Protection (EFP) element operates for dead-zone faults; i.e., faults between the CT and an open feeder breaker. Since a bus protection zone terminates on the CTs, faults between the CT and breaker require special consider- ation. GE Multilin B90 Low Impedance Bus Differential System 5-101...
  • Page 220 • EFP1 BREAKER OPEN: This setting is a FlexLogic™ operand indicating an open breaker. The operand shall be "On" when the breaker is open. Typically, this setting is a position of an appropriately wired input contact of the B90. •...
  • Page 221 Off = 0 EFP 1 OP SETTINGS EFP 1 DPO SETTING EFP 1 BRK DELAY: EFP PKP EFP 1 BREAKER OPEN: Off = 0 836004A1.vsd Figure 5–49: END FAULT PROTECTION LOGIC GE Multilin B90 Low Impedance Bus Differential System 5-103...
  • Page 222: Overview

    If more than one operate-type operand is required, it may be assigned directly from the trip bus menu. 5-104 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 223 = Enabled TRIP BUS 1 BLOCK = Off SETTINGS TRIP BUS 1 LATCHING = Enabled TRIP BUS 1 RESET = Off FLEXLOGIC OPERAND RESET OP 842023A1.CDR Figure 5–51: TRIP BUS LOGIC GE Multilin B90 Low Impedance Bus Differential System 5-105...
  • Page 224: Setting Groups

    SETTING GROUP 1 NAME SETTING GROUP 6 NAME groups. Once programmed, this name will appear on the second line of the  GROUPED ELEMENTS SETTING GROUP 1(6) menu display. 5-106 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 225: Digital Elements

    DIGITAL ELEMENT 1 RESET DELAY: Sets the time delay to reset. If a reset delay is not required, set to “0”. • DIGITAL ELEMENT 1 PICKUP LED: This setting enables or disabled the digital element pickup LED. When set to “Disabled”, the operation of the pickup LED is blocked. GE Multilin B90 Low Impedance Bus Differential System 5-107...
  • Page 226 In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact which is open when the breaker is open (see diagram below). To prevent unwanted alarms in this situation, the trip circuit monitoring logic must include the breaker position. Figure 5–53: TRIP CIRCUIT EXAMPLE 1 5-108 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 227 In this case, it is not required to supervise the monitoring circuit with the breaker position – the setting is BLOCK selected to “Off”. In this case, the settings are as follows (EnerVista UR Setup example shown). GE Multilin B90 Low Impedance Bus Differential System 5-109...
  • Page 228: Monitoring Elements

    TARGET: Self-reset Range: Disabled, Enabled CT TROUBLE ZONE 1 MESSAGE EVENTS: Disabled The CT Trouble feature is available only when   is set to "Protection". PRODUCT SETUP B90 FUNCTION B90 FUNCTION 5-110 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 229 0.00 to 10.00 s in steps of 0.05 ISOLATOR 1 ALARM MESSAGE DELAY: 0.05 s Range: FlexLogic™ operand ISOLATOR 1 RESET: MESSAGE Range: Self-Reset, Latched, Disabled ISOLATOR 1 MESSAGE TARGET: Self-Reset GE Multilin B90 Low Impedance Bus Differential System 5-111...
  • Page 230 Bus protection zone discrimination depends heavily on reliable isolator position feedback. Therefore, two isolator auxiliary contacts – normally open and normally closed – must confirm the status of the isolator via the B90 contact inputs. This element responds to both normally open and normally closed auxiliary contacts of an isolator or a tie-breaker in order to assert the actual position of the isolator for the dynamic bus image.
  • Page 231 ISOLATOR 1 BLOCK delay isolator position valid alarm ISOLATOR 1 ALARM acknowledged alarm acknowledging ISOLATOR 1 RESET signal 836744A1.vsd Figure 5–58: ISOLATOR MONITORING SAMPLE TIMING DIAGRAM GE Multilin B90 Low Impedance Bus Differential System 5-113...
  • Page 232: Contact Inputs

    The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a user- settable debounce time in order for the B90 to validate the new contact state. In the figure below, the debounce time is set at 2.5 ms;...
  • Page 233 "Breaker Closed (52b)" CONTACT INPUT H5A ID: "Enabled" CONTACT INPUT H5A EVENTS: Note that the 52b contact is closed when the breaker is open and open when the breaker is closed. GE Multilin B90 Low Impedance Bus Differential System 5-115...
  • Page 234: Virtual Inputs

    “Virtual Input 1 to OFF = 0” VIRTUAL INPUT 1 ID: (Flexlogic Operand) SETTING Virt Ip 1 VIRTUAL INPUT 1 TYPE: Latched Self - Reset 827080A2.CDR Figure 5–60: VIRTUAL INPUTS SCHEME LOGIC 5-116 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 235: Contact Outputs

    The most dependable protection of the initiating contact is provided by directly measuring current in the tripping circuit, and using this parameter to control resetting of the initiating relay. This scheme is often called trip seal-in. This can be realized in the B90 using the FlexLogic™ operand to seal-in the contact output as follows: CONT OP 1 ION “Cont Op 1"...
  • Page 236 5 SETTINGS The B90 latching output contacts are mechanically bi-stable and controlled by two separate (open and close) coils. As such they retain their position even if the relay is not powered up. The relay recognizes all latching output contact cards and pop- ulates the setting menu accordingly.
  • Page 237: Virtual Outputs

    FlexLogic™ equations. Any change of state of a virtual output can be logged as an event if programmed to do so. For example, if Virtual Output 1 is the trip signal from FlexLogic™ and the trip relay is used to signal events, the settings would be programmed as follows: GE Multilin B90 Low Impedance Bus Differential System 5-119...
  • Page 238: Remote Devices

    The remote input/output facility provides for 32 remote inputs and 64 remote outputs. b) LOCAL DEVICES: ID OF DEVICE FOR TRANSMITTING GSSE/GOOSE MESSAGES In a B90 relay, the device ID that represents the IEC 61850 GOOSE application ID (GoID) name string sent as part of each GOOSE message is programmed in the ...
  • Page 239: Remote Inputs

    This setting identifies the Ethernet application identification in the GOOSE message. It should match the corre- sponding settings on the sending device. setting provides for the choice of the B90 fixed (DNA/UserSt) dataset (that is, containing REMOTE DEVICE 1 DATASET DNA and UserSt bit pairs), or one of the configurable datasets.
  • Page 240: Remote Double-Point Status Inputs

    REMOTE OUTPUTS DNA BIT PAIRS REMOTE OUPUTS DNA- 1(32) BIT PAIR Range: FlexLogic™ operand  REMOTE OUTPUTS DNA- 1 OPERAND:  DNA- 1 BIT PAIR Range: Disabled, Enabled DNA- 1 EVENTS: MESSAGE Disabled 5-122 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 241: Resetting

    The setting RESET OP (PUSHBUTTON) RESET OP (COMMS) RESET OP (OPERAND) shown above selects the operand that will create the operand. RESET OP (OPERAND) GE Multilin B90 Low Impedance Bus Differential System 5-123...
  • Page 242: Direct Inputs And Outputs

    APPLICATION EXAMPLES The examples introduced in the earlier Direct inputs and outputs section (part of the Product Setup section) are continued below to illustrate usage of the direct inputs and outputs. 5-124 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 243 5 SETTINGS 5.7 INPUTS/OUTPUTS EXAMPLE 1: EXTENDING INPUT/OUTPUT CAPABILITIES OF A B90 RELAY Consider an application that requires additional quantities of digital inputs or output contacts or lines of programmable logic that exceed the capabilities of a single UR-series chassis. The problem is solved by adding an extra UR-series IED, such as the C30, to satisfy the additional inputs/outputs and programmable logic requirements.
  • Page 244 DIRECT INPUT 6 BIT NUMBER: UR IED 2: "1" DIRECT INPUT 5 DEVICE ID: "2" DIRECT INPUT 5 BIT NUMBER: "3" DIRECT INPUT 6 DEVICE ID: "2" DIRECT INPUT 6 BIT NUMBER: 5-126 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 245: Iec 61850 Goose Analogs

    The following text must be used in the UNITS setting, to represent these types of analogs: A, V, W, var, VA, Hz, deg, and no text (blank setting) for power factor. GE Multilin B90 Low Impedance Bus Differential System 5-127...
  • Page 246: Iec 61850 Goose Integers

    GOOSE ANALOG 1 PU: This setting specifies the per-unit base factor when using the GOOSE analog input FlexAna- log™ values in other B90 features, such as FlexElements™. The base factor is applied to the GOOSE analog input FlexAnalog quantity to normalize it to a per-unit quantity. The base units are described in the following table.
  • Page 247: Test Mode

    TEST MODE FORCING: MESSAGE The B90 provides a test facility to verify the functionality of contact inputs and outputs, some communication channels and the phasor measurement unit (where applicable), using simulated conditions. The test mode is indicated on the relay face- plate by a Test Mode LED indicator.
  • Page 248: Force Contact Inputs

    Following a restart, power up, settings TEST MODE FUNCTION upload, or firmware upgrade, the test mode will remain at the last programmed value. This allows a B90 that has been placed in isolated mode to remain isolated during testing and maintenance activities. On restart, the TEST MODE FORCING setting and the force contact input and force contact output settings all revert to their default states.
  • Page 249: Force Contact Outputs

    PUSHBUTTON 1 FUNCTION input 1 to initiate the Test mode, make the following changes in the menu:   SETTINGS TESTING TEST MODE “Enabled” and “ ” TEST MODE FUNCTION: TEST MODE INITIATE: GE Multilin B90 Low Impedance Bus Differential System 5-131...
  • Page 250 5.8 TESTING 5 SETTINGS 5-132 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 251: Actual Values Main Menu

    See page 6-9.   IEC 61850 See page 6-10.  GOOSE ANALOGS  ACTUAL VALUES  USER-PROGRAMMABLE See page 6-11.  RECORDS  FAULT REPORTS  EVENT RECORDS See page 6-11.  GE Multilin B90 Low Impedance Bus Differential System...
  • Page 252 6.1 OVERVIEW 6 ACTUAL VALUES  OSCILLOGRAPHY See page 6-11.   ACTUAL VALUES  MODEL INFORMATION See page 6-12.  PRODUCT INFO   FIRMWARE REVISIONS See page 6-12.  B90 Low Impedance Bus Differential System GE Multilin...
  • Page 253: Contact Inputs

    The state displayed will be that of the remote point unless the remote device has been established to be “Offline” in which case the value shown is the programmed default state for the remote input. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 254: Remote Double-Point Status Inputs

    For example, ‘Virt Op 1’ refers to the virtual output in terms of the default name-array index. The second line of the display indicates the logic state of the virtual output, as calculated by the FlexLogic™ equation for that output. B90 Low Impedance Bus Differential System GE Multilin...
  • Page 255: Remote Devices

    Range: Off, On PARAM 2: Off MESSAGE ↓ Range: Off, On PARAM 256: Off MESSAGE There are 256 FlexState bits available. The second line value indicates the state of the given FlexState bit. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 256: Ethernet

    UINT INPUT 16 MESSAGE The B90 Low Impedance Bus Differential System is provided with optional IEC 61850 communications capability. This feature is specified as a software option at the time of ordering. Refer to the Ordering sec- tion of chapter 2 for additional details. The IEC 61850 protocol features are not available if CPU type E is ordered.
  • Page 257: Direct Inputs

    STATUS: Offline Range: Offline, Online DIRECT DEVICE 2 MESSAGE STATUS: Offline ↓ Range: Offline, Online DIRECT DEVICE 16 MESSAGE STATUS: Offline These actual values represent the state of direct devices 1 through 16. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 258: Metering Conventions

    (see chapter 8: Theory of operation for additional details). There is no cutoff level applied to the differential and restraint currents computed by the B90. Therefore, a small dif- ferential current reflecting CT inaccuracies and bus leakage current could be present during balanced conditions.
  • Page 259: Currents

     FREQUENCY AND PHASE REFERENCE SETTINGS  menu. Refer to the Power System section of chapter 5 for additional details. SYSTEM SETUP POWER SYSTEM GE Multilin B90 Low Impedance Bus Differential System...
  • Page 260: Iec 61580 Goose Analog Values

    MESSAGE 0.000 The B90 Low Impedance Bus Differential System is provided with optional IEC 61850 communications capability. This feature is specified as a software option at the time of ordering. Refer to the Ordering sec- tion of chapter 2 for additional details. The IEC 61850 protocol features are not available if CPU type E is ordered.
  • Page 261: User-Programmable Fault Reports

    A trigger can be forced here at any time by setting “Yes” to the command. Refer to the  FORCE TRIGGER? COMMANDS menu for information on clearing the oscillography records. CLEAR RECORDS GE Multilin B90 Low Impedance Bus Differential System 6-11...
  • Page 262: Model Information

    6.5PRODUCT INFORMATION 6.5.1 MODEL INFORMATION   PATH: ACTUAL VALUES PRODUCT INFO MODEL INFORMATION Range: standard GE multilin order code format;  MODEL INFORMATION ORDER CODE LINE 1: example order code shown  B90-E00-HCL-F8H-H6A Range: standard GE multilin order code format...
  • Page 263: Virtual Inputs

    The states of up to 64 virtual inputs are changed here. The first line of the display indicates the ID of the virtual input. The second line indicates the current or selected status of the virtual input. This status will be a state off (logic 0) or on (logic 1). GE Multilin B90 Low Impedance Bus Differential System...
  • Page 264: Clear Records

    24-hour clock. The complete date, as a minimum, must be entered to allow execution of this com- mand. The new time will take effect at the moment the ENTER key is clicked. B90 Low Impedance Bus Differential System GE Multilin...
  • Page 265: Relay Maintenance

    Various self-checking diagnostics are performed in the background while the B90 is running, and diagnostic information is stored on the non-volatile memory from time to time based on the self-checking result. Although the diagnostic information is cleared before the B90 is shipped from the factory, the user may want to clear the diagnostic information for themselves under certain circumstances.
  • Page 266: Targets Menu

    The critical fail relay on the power supply module is de-energized. • All other output relays are de-energized and are prevented from further operation. • The faceplate In Service LED indicator is turned off. • event is recorded. RELAY OUT OF SERVICE B90 Low Impedance Bus Differential System GE Multilin...
  • Page 267 Contact Factory (xxx) • Latched target message: Yes. • Description of problem: One or more installed hardware modules is not compatible with the B90 order code. • How often the test is performed: Module dependent. • What to do: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed mod- ule (for example, F8L).
  • Page 268 What to do: Check Ethernet connections. Port 1 is the primary port and port 2 is the secondary port. MAINTENANCE ALERT: SNTP Failure • Latched target message: No. • Description of problem: The SNTP server is not responding. • How often the test is performed: Every 10 to 60 seconds. B90 Low Impedance Bus Differential System GE Multilin...
  • Page 269 Description of problem: The ambient temperature is greater than the maximum operating temperature (+80°C). • How often the test is performed: Every hour. • What to do: Remove the B90 from service and install in a location that meets operating temperature standards. UNEXPECTED RESTART: Press “RESET” key •...
  • Page 270 7.2 TARGETS 7 COMMANDS AND TARGETS • Description of problem: Abnormal restart from modules being removed or inserted while the B90 is powered-up, when there is an abnormal DC supply, or as a result of internal relay failure. • How often the test is performed: Event driven.
  • Page 271: Overview

    When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond- ing connection password. If the connection is to the back of the B90, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.
  • Page 272: Password Security Menu

    If an entered password is lost (or forgotten), consult the factory with the corresponding ENCRYPTED PASSWORD If the setting and command passwords are identical, then this one password allows access to both com- mands and settings. NOTE B90 Low Impedance Bus Differential System GE Multilin...
  • Page 273: Remote Passwords

     SUPERVISION  TIMEOUTS Range: 2 to 5 in steps of 1 INVALID ATTEMPTS MESSAGE BEFORE LOCKOUT: 3 Range: 5 to 60 minutes in steps of 1 PASSWORD LOCKOUT MESSAGE DURATION: 5 min GE Multilin B90 Low Impedance Bus Differential System...
  • Page 274: Dual Permission Security Access

    INVALID ATTEMPS BEFORE LOCKOUT The B90 provides a means to raise an alarm upon failed password entry. Should password verification fail while accessing a password-protected level of the relay (either settings or commands), the FlexLogic™ operand is UNAUTHORIZED ACCESS asserted.
  • Page 275 If access is permitted and an off-to-on transition of the FlexLogic™ operand is detected, the timeout is restarted. The status of this timer is updated every 5 seconds. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 276: Settings Templates

    (settings file templates) and online devices (online settings templates). The func- tionality is identical for both purposes. The settings template feature requires that both the EnerVista UR Setup software and the B90 firmware are at ver- sions 5.40 or higher.
  • Page 277 The following procedure describes how to add password protection to a settings file template. Select a settings file from the offline window on the left of the EnerVista UR Setup main screen. Selecting the Template Mode > Password Protect Template option. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 278 The template specifies that only the Pickup Curve Phase time overcurrent settings window without template applied. settings be available. 842858A1.CDR Figure 8–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND B90 Low Impedance Bus Differential System GE Multilin...
  • Page 279 Select an installed device or settings file from the tree menu on the left of the EnerVista UR Setup main screen. Select the Template Mode > Remove Settings Template option. Enter the template password and click OK to continue. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 280: Securing And Locking Flexlogic™ Equations

    Click on Save to save and apply changes to the settings template. Select the Template Mode > View In Template Mode option to view the template. Apply a password to the template then click OK to secure the FlexLogic™ equation. 8-10 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 281 FlexLogic™ entries in a settings file have been secured, use the following procedure to lock the settings file to a specific serial number. Select the settings file in the offline window. Right-click on the file and select the Edit Settings File Properties item. GE Multilin B90 Low Impedance Bus Differential System 8-11...
  • Page 282: Settings File Traceability

    When a settings file is transfered to a B90 device, the date, time, and serial number of the B90 are sent back to EnerVista UR Setup and added to the settings file on the local PC. This infor- mation can be compared with the B90 actual values at any later date to determine if security has been compromised.
  • Page 283 8.2 SETTINGS SECURITY The transfer date of a setting file written to a B90 is logged in the relay and can be viewed via EnerVista UR Setup or the front panel display. Likewise, the transfer date of a setting file saved to a local PC is logged in EnerVista UR Setup.
  • Page 284 ONLINE DEVICE TRACEABILITY INFORMATION The B90 serial number and file transfer date are available for an online device through the actual values. Select the Actual Values > Product Info > Model Information menu item within the EnerVista UR Setup online window as shown in the example below.
  • Page 285: Overview

    Select the Security > User Management menu item to open the user management configuration window. Enter a username in the User field. The username must be between 4 and 20 characters in length. GE Multilin B90 Low Impedance Bus Differential System 8-15...
  • Page 286: Modifying User Privileges

    The following procedure describes how to modify user privileges. Select the Security > User Management menu item to open the user management configuration window. Locate the username in the User field. 8-16 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 287 When this box is checked, the user will become an EnerVista URPlus Setup administrator, therefore receiving all of the administrative rights. Exercise caution when granting administrator rights. Click OK to save the changes to user to the security management system. GE Multilin B90 Low Impedance Bus Differential System 8-17...
  • Page 288 8.3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8-18 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 289 9 THEORY OF OPERATION 9.1INTRODUCTION 9.1.1 BUS DIFFERENTIAL PROTECTION Referring to the figure below, input currents defining (through the dynamic bus replica) the bus differential zone are received by the B90 from current transformers (CTs) associated with the power system. Measuring Unit Unbiased Differential...
  • Page 290: Ct Ratio Matching

    9.2.1 DYNAMIC BUS REPLICA MECHANISM The bus differential zones of the B90 allow for protecting bus sections that include circuits that are switchable between dif- ferent sections. Proper relay operation is achieved by associating a status signal with each input current. This mechanism is referred to as a dynamic bus replica.
  • Page 291: Biased Differential Characteristic

    Figure 9–2: BIASED OPERATING CHARACTERISTIC The higher slope used by the B90 acts as an actual percentage bias regardless of the value of the restraining signal. This is so because the boundary of the operating characteristic in the higher slope region is a straight line intersecting the origin of the ‘differential - restraining’...
  • Page 292: Differential And Restraining Currents

    HIGH BPNT 5000A : 1000A = 5 pu (1000A is the base unit; see page 8–2 for the example). The same approach applies to the setting of the lower breakpoint, LOW BPNT B90 Low Impedance Bus Differential System GE Multilin...
  • Page 293: Enhanced Security

    9.3 DIFFERENTIAL PRINCIPLE 9.3.3 ENHANCED SECURITY In order to enhance the performance of the B90, the differential characteristic is divided into two regions having diverse operating modes as shown in following diagram. The first region applies to comparatively low differential currents and has been introduced to deal with CT saturation on low- current external faults.
  • Page 294: Current Directional Protection

    9.4.1 CURRENT DIRECTIONAL PROTECTION For better security, the B90 uses the current directional protection principle to dynamically supervise the main current differ- ential function. The directional principle is in effect permanently for low differential currents (Region 1 in Figure 9–3: Two Regions of Differential Characteristic) and is switched on dynamically for large differential currents (Region 2 in the same figure) by the saturation detector (see Section 9.5: Saturation Detector) upon detecting CT saturation.
  • Page 295: Ct Saturation Detection

    9.5.1 CT SATURATION DETECTION The saturation detector of the B90 takes advantage of the fact that any CT operates correctly for a short period of time even under very large primary currents that would subsequently cause a very deep saturation. As a result of that, in the case of an external fault, the differential current stays very low during the initial period of linear operation of the CTs while the restraining signal develops rapidly.
  • Page 296: Output Logic

    Figure 8-10 presents the bus currents and the most important logic signals for the case of an external fault. Despite very fast and severe CT saturation, the B90 remains stable. Figure 8-11 presents the same signals but for the case of an internal fault. The B90 trips in 10 ms (fast form-C output con- tact).
  • Page 297 9 THEORY OF OPERATION 9.6 OUTPUT LOGIC AND EXAMPLES Figure 9–9: EXTERNAL FAULT EXAMPLE GE Multilin B90 Low Impedance Bus Differential System...
  • Page 298 9.6 OUTPUT LOGIC AND EXAMPLES 9 THEORY OF OPERATION Figure 9–10: INTERNAL FAULT EXAMPLE 9-10 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 299: Introduction

    It is also assumed that the CTs have been selected without considering a B90 application, but the B90 settings are to be calculated for proper relay application. The CT data used in this example are kept to a minimum and in a generic form. The CT data does not reflect any particular notation or national standards.
  • Page 300 (Ω) LEADS (M) CTSEC CT-1 600:5 0.34 CT-2 600:5 0.34 CT-3 1200:5 0.64 CT-4 1000:5 0.54 CT-5, CT-6 1000:5 0.54 CT-7, CT-8 1200:5 0.64 836732A4.CDR Figure 10–2: APPROXIMATE CT MAGNETIZING CHARACTERISTICS 10-2 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 301: North Bus Zone

    CT-6 and CT-7. The South bus protection should operate the following breakers: B-2 (if S-2 closed), B-3 (if S-4 closed), B-4 (if S-6 closed), B-6 and B-7. NORTH BUS CT-1 CT-7 CT-2 CT-4 CT-3 CT-5 CT-6 CT-8 SOUTH BUS 836734A1.CDR Figure 10–4: SOUTH BUS ZONE GE Multilin B90 Low Impedance Bus Differential System 10-3...
  • Page 302: Description

    Assuming 0.003 Ω/m lead resistance and approximating the B90 input resistance for the 5A input CTs as 0.2 VA / (5 A) 0.008 Ω, the limits of the linear operation of the CTs have been calculated and presented in the Limits of Linear Operations of the CTs table.
  • Page 303: Low Breakpoint

    A combination of very high residual magnetism and a DC component with a long time constant may saturate a given CT even with the AC current below the suggested value of the lower breakpoint. The relay copes with this threat by using a 2- out-of-2 operating mode for low differential currents. GE Multilin B90 Low Impedance Bus Differential System 10-5...
  • Page 304: Description

    Table 10–4: EXTERNAL FAULT CALCULATIONS ON C-1 (KA) (A SEC) (MS) (MS) FAULT FAULT SATURATION SATURATION CT-1 14.0 116.67 CT-2 0.00 CT-3 25.00 CT-4 25.00 15.19 CT-6 15.00 35.25 CT-7, CT-8 14.0 58.33 4.70 10-6 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 305: External Faults On C-2

    Table 10–6: CALCULATIONS FOR THE EXTERNAL FAULTS ON C-3 (KA) (A SEC) (MS) (MS) FAULT FAULT SATURATION SATURATION CT-1 0.00 CT-2 0.00 CT-3 33.33 11.18 CT-4 25.00 15.19 CT-6 15.00 35.25 CT-7, CT-8 33.33 11.18 GE Multilin B90 Low Impedance Bus Differential System 10-7...
  • Page 306: External Faults On C-4

    Table 10–8: EXTERNAL FAULT CALCULATIONS ON C-5 (KA) (A SEC) (MS) (MS) FAULT FAULT SATURATION SATURATION CT-1 0.00 CT-2 0.00 CT-3 25.00 CT-4 25.00 15.19 CT-5 11.0 55.00 4.83 CT-7, CT-8 11.0 45.83 7.16 10-8 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 307: Description

    HIGH BPNT 8.96 None of the CTs will saturate for ac currents below 8.96 pu. The dc component, however, may saturate some CTs even for currents below 8.96 pu. The B90 copes with saturation using the current directional principle. HIGH SET 5.94...
  • Page 308: Using Setting Groups

    CTs in any particular bus configuration. 10-10 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 309: A.1.1 Flexanalog Items

    Degrees Terminal 20 current angle 28476 S5 Curr Mag Amps Terminal 21 current magnitude 28478 S5 Curr Ang Degrees Terminal 21 current angle 28479 S6 Curr Mag Amps Terminal 22 current magnitude GE Multilin B90 Low Impedance Bus Differential System...
  • Page 310 GOOSE Analog In 8 IEC 61850 GOOSE analog input 8 45600 GOOSE Analog In 9 IEC 61850 GOOSE analog input 9 45602 GOOSE Analog In 10 IEC 61850 GOOSE analog input 10 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 311: A.1.2 Flexinteger Items

    IEC61850 GOOSE UInteger input 13 9994 GOOSE UInt Input 14 IEC61850 GOOSE UInteger input 14 9996 GOOSE UInt Input 15 IEC61850 GOOSE UInteger input 15 9998 GOOSE UInt Input 16 IEC61850 GOOSE UInteger input 16 GE Multilin B90 Low Impedance Bus Differential System...
  • Page 312 A.1 PARAMETER LISTS APPENDIX A B90 Low Impedance Bus Differential System GE Multilin...
  • Page 313: B.1.1 Introduction

    Broadcast mode is only recognized when associated with function code 05h. For any other function code, a packet with broadcast mode slave address 0 will be ignored. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 314: B.1.4 Crc-16 Algorithm

    No: go to 8; Yes: G (+) A --> A and continue. Is j = 8? No: go to 5; Yes: continue i + 1 --> i Is i = N? No: go to 3; Yes: continue A --> CRC B90 Low Impedance Bus Differential System GE Multilin...
  • Page 315: B.2.1 Supported Function Codes

    125. See the Modbus memory map table for exact details on the data registers. Since some PLC implementations of Modbus only support one of function codes 03h and 04h. The B90 interpretation allows either function code to be used for reading one or more consecutive data registers.
  • Page 316: B.2.3 Execute Operation (Function Code 05H)

    DATA STARTING ADDRESS - low DATA STARTING ADDRESS - low DATA - high DATA - high DATA - low DATA - low CRC - low CRC - low CRC - high CRC - high B90 Low Impedance Bus Differential System GE Multilin...
  • Page 317: B.2.5 Store Multiple Settings (Function Code 10H)

    EXAMPLE (HEX) SLAVE ADDRESS SLAVE ADDRESS FUNCTION CODE FUNCTION CODE CRC - low order byte ERROR CODE CRC - high order byte CRC - low order byte CRC - high order byte GE Multilin B90 Low Impedance Bus Differential System...
  • Page 318: B.3.1 Obtaining Relay Files Via Modbus

    To read binary COMTRADE oscillography files, read the following filenames: OSCnnnn.CFG and OSCnnn.DAT Replace “nnn” with the desired oscillography trigger number. For ASCII format, use the following file names OSCAnnnn.CFG and OSCAnnn.DAT B90 Low Impedance Bus Differential System GE Multilin...
  • Page 319: B.3.2 Modbus Password Operation

    When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond- ing connection password. If the connection is to the back of the B90, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.
  • Page 320: B.4.1 Modbus Memory Map

    Virtual Input 26 State 0 to 1 F108 0 (Off) 041A Virtual Input 27 State 0 to 1 F108 0 (Off) 041B Virtual Input 28 State 0 to 1 F108 0 (Off) B90 Low Impedance Bus Differential System GE Multilin...
  • Page 321 Element Targets (Read Only) 14C3 Target Message F200 “.” Digital Input/Output States (Read Only) 1500 Contact Input States (6 items) 0 to 65535 F500 1508 Virtual Input States (8 items) 0 to 65535 F500 GE Multilin B90 Low Impedance Bus Differential System...
  • Page 322 IEC 61850 GGIO5 uinteger input 2 operand F612 26B2 IEC 61850 GGIO5 uinteger input 3 operand F612 26B3 IEC 61850 GGIO5 uinteger input 4 operand F612 26B4 IEC 61850 GGIO5 uinteger input 5 operand F612 B-10 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 323 0 to 4294967295 F050 User Programmable Fault Report (Read/Write Setting) (2 modules) 3090 Fault Report 1 Fault Trigger 0 to 65535 F300 3091 Fault Report 1 Function 0 to 1 F102 0 (Disabled) GE Multilin B90 Low Impedance Bus Differential System B-11...
  • Page 324 1 to 65535 F001 4055 Current Cutoff Level 0.002 to 0.02 0.001 F001 4056 Voltage Cutoff Level 0.1 to 1 F001 Communications (Read/Write Setting) 407E COM1 minimum response time 0 to 1000 F001 B-12 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 325 IEC 60870-5-104 power default threshold 0 to 65535 F001 30000 40EA IEC 60870-5-104 energy default threshold 0 to 65535 F001 30000 40EC IEC 60870-5-104 power default threshold 0 to 65535 F001 30000 GE Multilin B90 Low Impedance Bus Differential System B-13...
  • Page 326 ...Repeated for User-Programmable LED 3 4286 ...Repeated for User-Programmable LED 4 4288 ...Repeated for User-Programmable LED 5 428A ...Repeated for User-Programmable LED 6 428C ...Repeated for User-Programmable LED 7 428E ...Repeated for User-Programmable LED 8 B-14 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 327 0 to 1 F102 1 (Enabled) 4448 User Programmable IRIG-B Fail Function 0 to 1 F102 1 (Enabled) 4449 User Programmable Ethernet Switch Fail Function 0 to 1 F102 0 (Disabled) GE Multilin B90 Low Impedance Bus Differential System B-15...
  • Page 328 ...Repeated for User Programmable Pushbutton 6 4EFC ...Repeated for User Programmable Pushbutton 7 4F26 ...Repeated for User Programmable Pushbutton 8 4F50 ...Repeated for User Programmable Pushbutton 9 4F7A ...Repeated for User Programmable Pushbutton 10 B-16 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 329 Setting Group 1 Name F203 (none) 5F94 Setting Group 2 Name F203 (none) 5F9C Setting Group 3 Name F203 (none) 5FA4 Setting Group 4 Name F203 (none) 5FAC Setting Group 5 Name F203 (none) GE Multilin B90 Low Impedance Bus Differential System B-17...
  • Page 330 ...Repeated for Undervoltage 4 6B5C ...Repeated for Undervoltage 5 6B67 ...Repeated for Undervoltage 6 6B72 ...Repeated for Undervoltage 7 6B7D ...Repeated for Undervoltage 8 6B88 ...Repeated for Undervoltage 9 6B93 ...Repeated for Undervoltage 10 B-18 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 331 ...Repeated for Isolator 3 6CDA ...Repeated for Isolator 4 6CE4 ...Repeated for Isolator 5 6CEE ...Repeated for Isolator 6 6CF8 ...Repeated for Isolator 7 6D02 ...Repeated for Isolator 8 6D0C ...Repeated for Isolator 9 GE Multilin B90 Low Impedance Bus Differential System B-19...
  • Page 332 ...Repeated for Terminal Current 8 6F18 ...Repeated for Terminal Current 9 6F1B ...Repeated for Terminal Current 10 6F1E ...Repeated for Terminal Current 11 6F21 ...Repeated for Terminal Current 12 6F24 ...Repeated for Terminal Current 13 B-20 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 333 ...Repeated for Terminal Current 23 6F9A ...Repeated for Terminal Current 24 VT Terminal Settings (Read/Write Setting) (12 modules) 6F9C Terminal Voltage Ratio 1 to 24000 0.01 F060 6F9E Terminal Voltage Secondary 50 to 240 F001 GE Multilin B90 Low Impedance Bus Differential System B-21...
  • Page 334 Breaker Failure 1 Amp Supervision OpA 0 to 65535 F300 7105 Breaker Failure 1 Amp Supervision OpB 0 to 65535 F300 7106 Breaker Failure 1 Amp Supervision OpC 0 to 65535 F300 B-22 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 335 7405 Instantaneous Overcurrent 1 Block 0 to 65535 F300 7406 Instantaneous Overcurrent 1 Target 0 to 2 F109 0 (Self-reset) 7407 Instantaneous Overcurrent 1 Events 0 to 1 F102 0 (Disabled) GE Multilin B90 Low Impedance Bus Differential System B-23...
  • Page 336 ...Repeated for Time Overcurrent 15 75B4 ...Repeated for Time Overcurrent 16 75C0 ...Repeated for Time Overcurrent 17 75CC ...Repeated for Time Overcurrent 18 75D8 ...Repeated for Time Overcurrent 19 75E4 ...Repeated for Time Overcurrent 20 B-24 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 337 F001 8A14 ...Repeated for Digital Element 2 8A28 ...Repeated for Digital Element 3 8A3C ...Repeated for Digital Element 4 8A50 ...Repeated for Digital Element 5 8A64 ...Repeated for Digital Element 6 GE Multilin B90 Low Impedance Bus Differential System B-25...
  • Page 338 F300 8E08 Trip Bus 1 Input 5 0 to 65535 F300 8E09 Trip Bus 1 Input 6 0 to 65535 F300 8E0A Trip Bus 1 Input 7 0 to 65535 F300 B-26 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 339 ...Repeated for Direct Input/Output 28 9550 ...Repeated for Direct Input/Output 29 955C ...Repeated for Direct Input/Output 30 9568 ...Repeated for Direct Input/Output 31 9574 ...Repeated for Direct Input/Output 32 9580 ...Repeated for Direct Input/Output 33 GE Multilin B90 Low Impedance Bus Differential System B-27...
  • Page 340 ...Repeated for Direct Input/Output 82 97D8 ...Repeated for Direct Input/Output 83 97E4 ...Repeated for Direct Input/Output 84 97F0 ...Repeated for Direct Input/Output 85 97FC ...Repeated for Direct Input/Output 86 9808 ...Repeated for Direct Input/Output 87 B-28 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 341 ...Repeated for Non-Volatile Latch 9 A75A ...Repeated for Non-Volatile Latch 10 A764 ...Repeated for Non-Volatile Latch 11 A76E ...Repeated for Non-Volatile Latch 12 A778 ...Repeated for Non-Volatile Latch 13 A782 ...Repeated for Non-Volatile Latch 14 GE Multilin B90 Low Impedance Bus Differential System B-29...
  • Page 342 (none) ADE2 IEC 61850 logical node CSWIx name prefix (6 items) 0 to 65534 F206 (none) AE3C IEC 61850 logical node XSWIx name prefix (6 items) 0 to 65534 F206 (none) B-30 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 343 ...Repeated for IEC 61850 GGIO4 analog input 18 AF8E ...Repeated for IEC 61850 GGIO4 analog input 19 AF95 ...Repeated for IEC 61850 GGIO4 analog input 20 AF9C ...Repeated for IEC 61850 GGIO4 analog input 21 GE Multilin B90 Low Impedance Bus Differential System B-31...
  • Page 344 0.001 to 100 0.001 F003 10000 B0C6 IEC 61850 MMXU TotPF Deadband 1 0.001 to 100 0.001 F003 10000 B0C8 IEC 61850 MMXU Hz Deadband 1 0.001 to 100 0.001 F003 10000 B-32 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 345 IEC 61850 GGIO1 Indication operands (128 items) F300 IEC 61850 Configurable GOOSE Transmission (Read/Write Setting) (8 modules) B5A0 IEC 61850 Configurable GOOSE Function 0 to 1 F102 0 (None) B5A1 IEC 61850 Configurable GOOSE ID F209 “GOOSEOut_x_” GE Multilin B90 Low Impedance Bus Differential System B-33...
  • Page 346 ...Repeated for Contact Input 22 BBB0 ...Repeated for Contact Input 23 BBB8 ...Repeated for Contact Input 24 BBC0 ...Repeated for Contact Input 25 BBC8 ...Repeated for Contact Input 26 BBD0 ...Repeated for Contact Input 27 B-34 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 347 ...Repeated for Contact Input 76 BD60 ...Repeated for Contact Input 77 BD68 ...Repeated for Contact Input 78 BD70 ...Repeated for Contact Input 79 BD78 ...Repeated for Contact Input 80 BD80 ...Repeated for Contact Input 81 GE Multilin B90 Low Impedance Bus Differential System B-35...
  • Page 348 ...Repeated for Virtual Input 27 BF74 ...Repeated for Virtual Input 28 BF80 ...Repeated for Virtual Input 29 BF8C ...Repeated for Virtual Input 30 BF98 ...Repeated for Virtual Input 31 BFA4 ...Repeated for Virtual Input 32 B-36 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 349 ...Repeated for Virtual Output 14 C1A0 ...Repeated for Virtual Output 15 C1A8 ...Repeated for Virtual Output 16 C1B0 ...Repeated for Virtual Output 17 C1B8 ...Repeated for Virtual Output 18 C1C0 ...Repeated for Virtual Output 19 GE Multilin B90 Low Impedance Bus Differential System B-37...
  • Page 350 ...Repeated for Virtual Output 68 C350 ...Repeated for Virtual Output 69 C358 ...Repeated for Virtual Output 70 C360 ...Repeated for Virtual Output 71 C368 ...Repeated for Virtual Output 72 C370 ...Repeated for Virtual Output 73 B-38 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 351 ...Repeated for Contact Output 13 C4DC ...Repeated for Contact Output 14 C4E8 ...Repeated for Contact Output 15 C4F4 ...Repeated for Contact Output 16 C500 ...Repeated for Contact Output 17 C50C ...Repeated for Contact Output 18 GE Multilin B90 Low Impedance Bus Differential System B-39...
  • Page 352 0 (Disabled) C761 Control Pushbutton 1 Events 0 to 1 F102 0 (Disabled) C762 ...Repeated for Control Pushbutton 2 C764 ...Repeated for Control Pushbutton 3 C766 ...Repeated for Control Pushbutton 4 B-40 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 353 ...Repeated for Direct Input 24 C8F0 ...Repeated for Direct Input 25 C8F4 ...Repeated for Direct Input 26 C8F8 ...Repeated for Direct Input 27 C8FC ...Repeated for Direct Input 28 C900 ...Repeated for Direct Input 29 GE Multilin B90 Low Impedance Bus Differential System B-41...
  • Page 354 ...Repeated for Direct Input 78 C9C8 ...Repeated for Direct Input 79 C9CC ...Repeated for Direct Input 80 C9D0 ...Repeated for Direct Input 81 C9D4 ...Repeated for Direct Input 82 C9D8 ...Repeated for Direct Input 83 B-42 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 355 ...Repeated for Direct Output 34 CA54 ...Repeated for Direct Output 35 CA56 ...Repeated for Direct Output 36 CA58 ...Repeated for Direct Output 37 CA5A ...Repeated for Direct Output 38 CA5C ...Repeated for Direct Output 39 GE Multilin B90 Low Impedance Bus Differential System B-43...
  • Page 356 ...Repeated for Direct Output 88 CAC0 ...Repeated for Direct Output 89 CAC2 ...Repeated for Direct Output 90 CAC4 ...Repeated for Direct Output 91 CAC6 ...Repeated for Direct Output 92 CAC8 ...Repeated for Direct Output 93 B-44 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 357 1 to 64 F205 “Rem Ip 1” CFAA ...Repeated for Remote Input 2 CFB4 ...Repeated for Remote Input 3 CFBE ...Repeated for Remote Input 4 CFC8 ...Repeated for Remote Input 5 GE Multilin B90 Low Impedance Bus Differential System B-45...
  • Page 358 ...Repeated for Remote Output 19 D26C ...Repeated for Remote Output 20 D270 ...Repeated for Remote Output 21 D274 ...Repeated for Remote Output 22 D278 ...Repeated for Remote Output 23 D27C ...Repeated for Remote Output 24 B-46 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 359 0 to 2 F001 D327 IEC 61850 GGIO2.CF.SPCSO8.ctlModel Value 0 to 2 F001 D328 IEC 61850 GGIO2.CF.SPCSO9.ctlModel Value 0 to 2 F001 D329 IEC 61850 GGIO2.CF.SPCSO10.ctlModel Value 0 to 2 F001 GE Multilin B90 Low Impedance Bus Differential System B-47...
  • Page 360 0 to 2 F001 D35C IEC 61850 GGIO2.CF.SPCSO61.ctlModel Value 0 to 2 F001 D35D IEC 61850 GGIO2.CF.SPCSO62.ctlModel Value 0 to 2 F001 D35E IEC 61850 GGIO2.CF.SPCSO63.ctlModel Value 0 to 2 F001 B-48 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 361 FlexLogic™ displays active 0 to 1 F102 1 (Enabled) ED01 Reserved (6 items) ED07 Last settings change date 0 to 4294967295 F050 ED09 Template bitmask (750 items) 0 to 65535 F001 GE Multilin B90 Low Impedance Bus Differential System B-49...
  • Page 362: B.4.2 Data Formats

    ENUMERATION: VT CONNECTION TYPE 0 = Wye; 1 = Delta F050 UR_UINT32 TIME and DATE (UNSIGNED 32 BIT INTEGER) Gives the current time in seconds elapsed since 00:00:00 January 1, 1970. B-50 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 363 ENUMERATION: OFF/ON ENUMERATION: OSCILLOGRAPHY MODE 0 = Off, 1 = On 0 = Automatic Overwrite, 1 = Protected F109 ENUMERATION: CONTACT OUTPUT OPERATION 0 = Self-reset, 1 = Latched, 2 = Disabled GE Multilin B90 Low Impedance Bus Differential System B-51...
  • Page 364 Breaker Supervision 16 Bus Zone 1 Breaker Supervision 17 Bus Zone 2 Breaker Supervision 18 Bus Zone 3 Breaker Supervision 19 Bus Zone 4 Breaker Supervision 20 Phase Undervoltage 1 Breaker Supervision 21 B-52 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 365 User-Programmable Pushbutton 8 Digital Element 10 User-Programmable Pushbutton 9 Digital Element 11 User-Programmable Pushbutton 10 Digital Element 12 User-Programmable Pushbutton 11 Digital Element 13 User-Programmable Pushbutton 12 Digital Element 14 User-Programmable Pushbutton 13 GE Multilin B90 Low Impedance Bus Differential System B-53...
  • Page 366 SNTP Failure Primary Ethernet Fail F135 ENUMERATION: GAIN CALIBRATION Secondary Ethernet Fail Temperature Monitor 0 = 0x1, 1 = 1x16 Field RTD Trouble Field TDR Trouble Remote Device Offline Direct Device Offline B-54 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 367 0 = Active Group, 1 = Group 1, 2 = Group 2, 3 = Group 3 4 = Group 4, 5 = Group 5, 6 = Group 6 F155 ENUMERATION: REMOTE DEVICE STATE 0 = Offline, 1 = Online GE Multilin B90 Low Impedance Bus Differential System B-55...
  • Page 368 0 = 3-Pole, 1 = 1-Pole F183 ENUMERATION: AC INPUT WAVEFORMS F159 bitmask definition ENUMERATION: BREAKER AUX CONTACT KEYING 0 = 52a, 1 = 52b, 2 = None 8 samples/cycle 16 samples/cycle 32 samples/cycle 64 samples/cycle B-56 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 369 TEXT2: 2-CHARACTER ASCII TEXT Menu User 4 (control pushbutton) Help User 5 (control pushbutton) F210 Escape User 6 (control pushbutton) ENUMERATION: DIRECT ENUMERATION User 7 (control pushbutton) 0 = IN, 1 = OUT GE Multilin B90 Low Impedance Bus Differential System B-57...
  • Page 370 MMXU2.MX.PhV.phsC.cVal.mag.f MMXU1.MX.TotW.mag.f MMXU2.MX.PhV.phsC.cVal.ang.f MMXU2.MX.A.phsA.cVal.mag.f MMXU1.MX.TotVAr.mag.f MMXU1.MX.TotVA.mag.f MMXU2.MX.A.phsA.cVal.ang.f MMXU1.MX.TotPF.mag.f MMXU2.MX.A.phsB.cVal.mag.f MMXU1.MX.Hz.mag.f MMXU2.MX.A.phsB.cVal.ang.f MMXU1.MX.PPV.phsAB.cVal.mag.f MMXU2.MX.A.phsC.cVal.mag.f MMXU1.MX.PPV.phsAB.cVal.ang.f MMXU2.MX.A.phsC.cVal.ang.f MMXU1.MX.PPV.phsBC.cVal.mag.f MMXU2.MX.A.neut.cVal.mag.f MMXU1.MX.PPV.phsBC.cVal.ang.f MMXU2.MX.A.neut.cVal.ang.f MMXU1.MX.PPV.phsCA.cVal.mag.f MMXU2.MX.W.phsA.cVal.mag.f MMXU1.MX.PPV.phsCA.cVal.ang.f MMXU2.MX.W.phsB.cVal.mag.f MMXU1.MX.PhV.phsA.cVal.mag.f MMXU2.MX.W.phsC.cVal.mag.f MMXU1.MX.PhV.phsA.cVal.ang.f MMXU2.MX.VAr.phsA.cVal.mag.f MMXU1.MX.PhV.phsB.cVal.mag.f MMXU2.MX.VAr.phsB.cVal.mag.f MMXU1.MX.PhV.phsB.cVal.ang.f MMXU2.MX.VAr.phsC.cVal.mag.f B-58 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 371 MMXU5.MX.PPV.phsCA.cVal.ang.f MMXU3.MX.VA.phsB.cVal.mag.f MMXU5.MX.PhV.phsA.cVal.mag.f MMXU3.MX.VA.phsC.cVal.mag.f MMXU5.MX.PhV.phsA.cVal.ang.f MMXU3.MX.PF.phsA.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.mag.f MMXU3.MX.PF.phsB.cVal.mag.f MMXU5.MX.PhV.phsB.cVal.ang.f MMXU3.MX.PF.phsC.cVal.mag.f MMXU5.MX.PhV.phsC.cVal.mag.f MMXU4.MX.TotW.mag.f MMXU5.MX.PhV.phsC.cVal.ang.f MMXU4.MX.TotVAr.mag.f MMXU5.MX.A.phsA.cVal.mag.f MMXU4.MX.TotVA.mag.f MMXU5.MX.A.phsA.cVal.ang.f MMXU4.MX.TotPF.mag.f MMXU5.MX.A.phsB.cVal.mag.f MMXU4.MX.Hz.mag.f MMXU5.MX.A.phsB.cVal.ang.f MMXU4.MX.PPV.phsAB.cVal.mag.f MMXU5.MX.A.phsC.cVal.mag.f MMXU4.MX.PPV.phsAB.cVal.ang.f MMXU5.MX.A.phsC.cVal.ang.f MMXU4.MX.PPV.phsBC.cVal.mag.f MMXU5.MX.A.neut.cVal.mag.f MMXU4.MX.PPV.phsBC.cVal.ang.f MMXU5.MX.A.neut.cVal.ang.f MMXU4.MX.PPV.phsCA.cVal.mag.f MMXU5.MX.W.phsA.cVal.mag.f GE Multilin B90 Low Impedance Bus Differential System B-59...
  • Page 372 GGIO5.ST.UIntIn6.q MMXU6.MX.W.phsC.cVal.mag.f GGIO5.ST.UIntIn6.stVal MMXU6.MX.VAr.phsA.cVal.mag.f GGIO5.ST.UIntIn7.q MMXU6.MX.VAr.phsB.cVal.mag.f GGIO5.ST.UIntIn7.stVal MMXU6.MX.VAr.phsC.cVal.mag.f GGIO5.ST.UIntIn8.q MMXU6.MX.VA.phsA.cVal.mag.f GGIO5.ST.UIntIn8.stVal MMXU6.MX.VA.phsB.cVal.mag.f GGIO5.ST.UIntIn9.q MMXU6.MX.VA.phsC.cVal.mag.f GGIO5.ST.UIntIn9.stVal MMXU6.MX.PF.phsA.cVal.mag.f GGIO5.ST.UIntIn10.q MMXU6.MX.PF.phsB.cVal.mag.f GGIO5.ST.UIntIn10.stVal MMXU6.MX.PF.phsC.cVal.mag.f GGIO5.ST.UIntIn11.q GGIO4.MX.AnIn1.mag.f GGIO5.ST.UIntIn11.stVal GGIO4.MX.AnIn2.mag.f GGIO5.ST.UIntIn12.q GGIO4.MX.AnIn3.mag.f GGIO5.ST.UIntIn12.stVal GGIO4.MX.AnIn4.mag.f GGIO5.ST.UIntIn13.q GGIO4.MX.AnIn5.mag.f GGIO5.ST.UIntIn13.stVal B-60 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 373 ENUMERATION: REAL TIME CLOCK MONTH GGIO3.MX.AnIn20.mag.f GGIO3.MX.AnIn21.mag.f value month GGIO3.MX.AnIn22.mag.f January GGIO3.MX.AnIn23.mag.f February GGIO3.MX.AnIn24.mag.f March GGIO3.MX.AnIn25.mag.f April GGIO3.MX.AnIn26.mag.f GGIO3.MX.AnIn27.mag.f June GGIO3.MX.AnIn28.mag.f July GGIO3.MX.AnIn29.mag.f August GGIO3.MX.AnIn30.mag.f September GGIO3.MX.AnIn31.mag.f October GGIO3.MX.AnIn32.mag.f November GGIO3.ST.IndPos1.stVal December GE Multilin B90 Low Impedance Bus Differential System B-61...
  • Page 374 LED and bit 7 the bottom LED. A bit value of 1 indicates [4] VIRTUAL INPUTS (1 to 64) the LED is on, 0 indicates the LED is off. [6] VIRTUAL OUTPUTS (1 to 96) B-62 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 375 BITFIELD: 3-PHASE SIMPLE ELEMENT STATE 0 = Operate, 1 = Operate A, 2 = Operate B, 3 = Operate C bitmask default variation F515 ENUMERATION ELEMENT INPUT MODE 0 = Signed, 1 = Absolute GE Multilin B90 Low Impedance Bus Differential System B-63...
  • Page 376 Analogs (basically all metering quantities used in protection). F612 UR_UINT16: FLEXINTEGER PARAMETER This 16-bit value corresponds to the Modbus address of the selected FlexInteger paramter. Only certain values may be used as FlexIntegers. B-64 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 377: C.1.1 Introduction

    The B90 relay supports IEC 61850 server services over both TCP/IP and TP4/CLNP (OSI) communication protocol stacks. The TP4/CLNP profile requires the B90 to have a network address or Network Service Access Point (NSAP) to establish a communication link. The TCP/IP profile requires the B90 to have an IP address to establish communications. These addresses are located in the ...
  • Page 378: C.2.1 Overview

    C.2.2 GGIO1: DIGITAL STATUS VALUES The GGIO1 logical node is available in the B90 to provide access to as many 128 digital status points and associated time- stamps and quality flags. The data content must be configured before the data can be used. GGIO1 provides digital status points for access by clients.
  • Page 379: C.2.6 Mmxn: Analog Measured Values

    C.2.6 MMXN: ANALOG MEASURED VALUES A limited number of measured analog values are available through the MMXN logical nodes. Each MMXN logical node provides data from a B90 current and voltage terminal. There is one MMXN available for each configurable terminal (programmed in the ...
  • Page 380 IEC 61850 control model. • XCBR1.CO.BlkCls: This is where IEC 61850 clients can issue block close commands to the breaker. Direct control with normal security is the only supported IEC 61850 control model. B90 Low Impedance Bus Differential System GE Multilin...
  • Page 381: C.3.1 Buffered And Unbuffered Reporting

    C.3.4 LOGICAL DEVICE NAME The logical device name is used to identify the IEC 61850 logical device that exists within the B90. This name is composed of two parts: the IED name setting and the logical device instance. The complete logical device name is the combination of the two character strings programmed in the settings.
  • Page 382: C.3.6 Logical Node Name Prefixes

    A built-in TCP/IP connection timeout of two minutes is employed by the B90 to detect ‘dead’ connections. If there is no data traffic on a TCP connection for greater than two minutes, the connection will be aborted by the B90. This frees up the con- nection to be used by other clients.
  • Page 383: C.4.1 Overview

    MAC address for GSSE messages. If GSSE DESTINATION MAC ADDRESS a valid multicast Ethernet MAC address is not entered (for example, 00 00 00 00 00 00), the B90 will use the source Ether- net MAC address as the destination, with the multicast bit set.
  • Page 384 The B90 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station components.
  • Page 385: C.4.5 Ethernet Mac Address For Gsse/Goose

    REMOTE IN 1 ITEM item to remote input 1. Remote input 1 can now be used in FlexLogic™ equations or other settings. The B90 must be rebooted (control power removed and re-applied) before these settings take effect. The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value in the sending device.
  • Page 386: C.4.6 Gsse Id And Goose Id Settings

    GSSE and GOOSE messages must have multicast destination MAC addresses. By default, the B90 is configured to use an automated multicast MAC scheme. If the B90 destination MAC address setting is not a valid multicast address (that is, the least significant bit of the first byte is not set), the address used as the destina- tion MAC will be the same as the local MAC address, but with the multicast bit set.
  • Page 387: C.5.1 Overview

    An ICD file is generated for the B90 by the EnerVista UR Setup software that describe the capabilities of the IED. The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other ven- dors) for system configuration.
  • Page 388: C.5.2 Configuring Iec 61850 Settings

    Transmission GOOSE dataset may be added or deleted, or prefixes of some logical nodes may be changed. While all new configurations will be mapped to the B90 settings file when importing an SCD file, all unchanged settings will preserve the same values in the new settings file.
  • Page 389: C.5.3 About Icd Files

    Although configurable transmission GOOSE can also be created and altered by some third-party system con- figurators, we recommend configuring transmission GOOSE for GE Multilin IEDs before creating the ICD, and strictly within EnerVista UR Setup software or the front panel display (access through the Settings > Product Setup > Com- munications >...
  • Page 390 Furthermore, it defines the capabilities of an IED in terms of communication services offered and, together with its LNType, instantiated data (DO) and its default or configuration values. There should be only one IED section in an ICD since it only describes one IED. C-14 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 391 Other ReportControl elements DOI (name) SDI (name) DAI (name) Text Other DOI elements SDI (name) DAI (name) Text Other LN elements Other LDevice elements 842797A1.CDR Figure 0–4: ICD FILE STRUCTURE, IED NODE GE Multilin B90 Low Impedance Bus Differential System C-15...
  • Page 392 Other BDA elements Other BDA elements Other DAType elements Other DAType elements EnumType (id) Text EnumVal (ord) Other EnumVal elements Other EnumType elements 842798A1.CDR Figure 0–5: ICD FILE STRUCTURE, DATATYPETEMPLATES NODE C-16 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 393: C.5.4 Creating An Icd File With Enervista Ur Setup

    The EnerVista UR Setup will prompt to save the file. Select the file path and enter the name for the ICD file, then click OK to generate the file. The time to create an ICD file from the offline B90 settings file is typically much quicker than create an ICD file directly from the relay.
  • Page 394 Like ICD files, the Header node identifies the SCD file and its version, and specifies options for the mapping of names to signals. The Substation node describes the substation parameters: Substation PowerSystemResource EquipmentContainer Power Transformer GeneralEquipment EquipmentContainer VoltageLevel Voltage PowerSystemResource Function SubFunction GeneralEquipment 842792A1.CDR Figure 0–7: SCD FILE STRUCTURE, SUBSTATION NODE C-18 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 395 IdInst is the instance identification of the logical device within the IED on which the control block is located, and cbName is the name of the control block. GE Multilin B90 Low Impedance Bus Differential System C-19...
  • Page 396: C.5.6 Importing An Scd File With Enervista Ur Setup

    Figure 0–9: SCD FILE STRUCTURE, IED NODE C.5.6 IMPORTING AN SCD FILE WITH ENERVISTA UR SETUP The following procedure describes how to update the B90 with the new configuration from an SCD file with the EnerVista UR Setup software. Right-click anywhere in the files panel and select the Import Contents From SCD File item.
  • Page 397 The software will open the SCD file and then prompt the user to save a UR-series settings file. Select a location and name for the URS (UR-series relay settings) file. If there is more than one GE Multilin IED defined in the SCD file, the software prompt the user to save a UR-series set- tings file for each IED.
  • Page 398: C.6.1 Acsi Basic Conformance Statement

    Buffered report control M7-1 sequence-number M7-2 report-time-stamp M7-3 reason-for-inclusion M7-4 data-set-name M7-5 data-reference M7-6 buffer-overflow M7-7 entryID M7-8 BufTm M7-9 IntgPd M7-10 Unbuffered report control M8-1 sequence-number M8-2 report-time-stamp M8-3 reason-for-inclusion C-22 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 399: C.6.3 Acsi Services Conformance Statement

    UR FAMILY PUBLISHER SERVER (CLAUSE 6) ServerDirectory APPLICATION ASSOCIATION (CLAUSE 7) Associate Abort Release LOGICAL DEVICE (CLAUSE 8) LogicalDeviceDirectory LOGICAL NODE (CLAUSE 9) LogicalNodeDirectory GetAllDataValues DATA (CLAUSE 10) GetDataValues SetDataValues GetDataDirectory GetDataDefinition GE Multilin B90 Low Impedance Bus Differential System C-23...
  • Page 400 (dupd) GetURCBValues SetURCBValues LOGGING (CLAUSE 14) LOG CONTROL BLOCK GetLCBValues SetLCBValues QueryLogByTime QueryLogByEntry GetLogStatusValues GENERIC SUBSTATION EVENT MODEL (GSE) (CLAUSE 14.3.5.3.4) GOOSE-CONTROL-BLOCK SendGOOSEMessage GetReference GetGOOSEElementNumber GetGoCBValues SetGoCBValues GSSE-CONTROL-BLOCK SendGSSEMessage GetReference C-24 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 401 (SendGOOSEMessage or SendGSSEMessage) NOTE c9: shall declare support if TP association is available c10: shall declare support for at least one (SendMSVMessage or SendUSVMessage) GE Multilin B90 Low Impedance Bus Differential System C-25...
  • Page 402: C.7.1 Logical Nodes Table

    RDRE: Disturbance recorder function RADR: Disturbance recorder channel analogue RBDR: Disturbance recorder channel binary RDRS: Disturbance record handling RBRF: Breaker failure RDIR: Directional element RFLO: Fault locator RPSB: Power swing detection/blocking RREC: Autoreclosing C-26 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 403 T: LOGICAL NODES FOR INSTRUMENT TRANSFORMERS TCTR: Current transformer TVTR: Voltage transformer Y: LOGICAL NODES FOR POWER TRANSFORMERS YEFN: Earth fault neutralizer (Peterson coil) YLTC: Tap changer YPSH: Power shunt YPTR: Power transformer GE Multilin B90 Low Impedance Bus Differential System C-27...
  • Page 404 ZGEN: Generator ZGIL: Gas insulated line ZLIN: Power overhead line ZMOT: Motor ZREA: Reactor ZRRC: Rotating reactive component ZSAR: Surge arrestor ZTCF: Thyristor controlled frequency converter ZTRC: Thyristor controlled reactive component C-28 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 405 Not Present (Balanced Transmission Only)   Unbalanced Transmission One Octet  Two Octets  Structured  Unstructured Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard GE Multilin B90 Low Impedance Bus Differential System...
  • Page 406  <18> := Packed start events of protection equipment with time tag M_EP_TB_1  <19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1  <20> := Packed single-point information with status change detection M_SP_NA_1 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 407  <103> := Clock synchronization command (see Clause 7.6 in standard) C_CS_NA_1  <104> := Test command C_TS_NA_1  <105> := Reset process command C_RP_NA_1  <106> := Delay acquisition command C_CD_NA_1  <107> := Test command with time tag CP56Time2a C_TS_TA_1 GE Multilin B90 Low Impedance Bus Differential System...
  • Page 408 •‘X’ if only used in the standard direction TYPE IDENTIFICATION CAUSE OF TRANSMISSION MNEMONIC <1> M_SP_NA_1 <2> M_SP_TA_1 <3> M_DP_NA_1 <4> M_DP_TA_1 <5> M_ST_NA_1 <6> M_ST_TA_1 <7> M_BO_NA_1 <8> M_BO_TA_1 <9> M_ME_NA_1 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 409 <35> M_ME_TE_1 <36> M_ME_TF_1 <37> M_IT_TB_1 <38> M_EP_TD_1 <39> M_EP_TE_1 <40> M_EP_TF_1 <45> C_SC_NA_1 <46> C_DC_NA_1 <47> C_RC_NA_1 <48> C_SE_NA_1 <49> C_SE_NB_1 <50> C_SE_NC_1 <51> C_BO_NA_1 <58> C_SC_TA_1 <59> C_DC_TA_1 <60> C_RC_TA_1 GE Multilin B90 Low Impedance Bus Differential System...
  • Page 410 <121> F_SR_NA_1 <122> F_SC_NA_1 <123> F_LS_NA_1 <124> F_AF_NA_1 <125> F_SG_NA_1 <126> F_DR_TA_1*) BASIC APPLICATION FUNCTIONS Station Initialization:  Remote initialization Cyclic Data Transmission:  Cyclic data transmission Read Procedure:  Read procedure B90 Low Impedance Bus Differential System GE Multilin...
  • Page 411  Mode B: Local freeze with counter interrogation  Mode C: Freeze and transmit by counter-interrogation commands  Mode D: Freeze by counter-interrogation command, frozen values reported simultaneously  Counter read  Counter freeze without reset GE Multilin B90 Low Impedance Bus Differential System...
  • Page 412 Maximum number of outstanding I-format APDUs k and latest acknowledge APDUs (w): PARAMETER DEFAULT REMARKS SELECTED VALUE VALUE 12 APDUs Maximum difference receive sequence number to send state variable 12 APDUs 8 APDUs 8 APDUs Latest acknowledge after receiving I-format APDUs B90 Low Impedance Bus Differential System GE Multilin...
  • Page 413: D.1.2 Iec 60870-5-104 Points

    The IEC 60870-5-104 data points are configured through the    SETTINGS PRODUCT SETUP COMMUNICATIONS DNP / menu. Refer to the Communications section of Chapter 5 for additional details. IEC104 POINT LISTS GE Multilin B90 Low Impedance Bus Differential System...
  • Page 414 D.1 IEC 60870-5-104 APPENDIX D D-10 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 415: E.1.1 Dnp V3.00 Device Profile

    Maximum Data Link Re-tries: Maximum Application Layer Re-tries:  None  None  Fixed at 3  Configurable  Configurable Requires Data Link Layer Confirmation:  Never  Always  Sometimes  Configurable GE Multilin B90 Low Impedance Bus Differential System...
  • Page 416 FlexLogic™. The On/Off times and Count value are ignored. “Pulse Off” and “Latch Off” operations put the appropriate Virtual Input into the “Off” state. “Trip” and “Close” operations both put the appropriate Virtual Input into the “On” state. B90 Low Impedance Bus Differential System GE Multilin...
  • Page 417  16 Bits (Counter 8) Default Variation: 1  32 Bits (Counters 0 to 7, 9)  Point-by-point list attached  Other Value: _____  Point-by-point list attached Sends Multi-Fragment Responses:  Yes  No GE Multilin B90 Low Impedance Bus Differential System...
  • Page 418: E.1.2 Implementation Table

    17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the B90 is not restarted, but the DNP process is restarted. B90 Low Impedance Bus Differential System GE Multilin...
  • Page 419 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the B90 is not restarted, but the DNP process is restarted. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 420 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the B90 is not restarted, but the DNP process is restarted. B90 Low Impedance Bus Differential System GE Multilin...
  • Page 421 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the B90 is not restarted, but the DNP process is restarted. GE Multilin B90 Low Impedance Bus Differential System...
  • Page 422: E.2.1 Binary Input Points

    Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time), Configurable Change Event Scan Rate: 8 times per power system cycle Change Event Buffer Size: 500 Default Class for All Points: 1 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 423: E.2.2 Binary And Control Relay Output

    Virtual Input 59 Virtual Input 28 Virtual Input 60 Virtual Input 29 Virtual Input 61 Virtual Input 30 Virtual Input 62 Virtual Input 31 Virtual Input 63 Virtual Input 32 Virtual Input 64 GE Multilin B90 Low Impedance Bus Differential System...
  • Page 424: E.2.3 Analog Inputs

    Change Event Variation reported when variation 0 requested: 1 (Analog Change Event without Time) Change Event Scan Rate: defaults to 500 ms Change Event Buffer Size: 256 Default Class for all Points: 2 E-10 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 425: F.1.1 Revision History

    Updated ENVIRONMENTAL specifications section 5-18 5-18 Update Updated IEC 61850 PROTOCOL section 5-85 5-85 Update Updated BREAKER FAILURE section Table F–4: MAJOR UPDATES FOR B90 MANUAL REVISION U2 (Sheet 1 of 2) PAGE PAGE CHANGE DESCRIPTION (U1) (U2) Title Title...
  • Page 426 F.1 CHANGE NOTES APPENDIX F Table F–4: MAJOR UPDATES FOR B90 MANUAL REVISION U2 (Sheet 2 of 2) PAGE PAGE CHANGE DESCRIPTION (U1) (U2) Update Updated INSPECTION CHECKLIST section 2-11 2-11 Update Updated USER-PROGRAMMABLE ELEMENTS specifications section 2-15 2-15 Update...
  • Page 427 APPENDIX F F.1 CHANGE NOTES Table F–6: MAJOR UPDATES FOR B90 MANUAL REVISION T1 (Sheet 2 of 2) PAGE PAGE CHANGE DESCRIPTION (S3) (T1) 5-16 5-17 Update Updated IEC 61850 PROTOCOL section 5-66 5-67 Update Updated FLEXLOGIC OPERANDS table 5-120...
  • Page 428 F.1 CHANGE NOTES APPENDIX F Table F–9: MAJOR UPDATES FOR B90 MANUAL REVISION S1 (Sheet 2 of 2) PAGE PAGE CHANGE DESCRIPTION (R3) (S1) Update Updated PASSWORD SECURITY section (now titled SECURITY) 5-27 Added ETHERNET SWITCH sub-section 5-35 5-37 Update...
  • Page 429 APPENDIX F F.1 CHANGE NOTES Table F–12: MAJOR UPDATES FOR B90 MANUAL REVISION R1 (Sheet 2 of 2) PAGE PAGE CHANGE DESCRIPTION (P2) (R1) Update Updated CONFIGURABLE GOOSE section Table F–13: MAJOR UPDATES FOR B90 MANUAL REVISION P2 PAGE PAGE...
  • Page 430: F.2.1 Standard Abbreviations

    MVA ....MegaVolt-Ampere (total 3-phase) FDH....Fault Detector high-set MVA_A ... MegaVolt-Ampere (phase A) FDL ....Fault Detector low-set MVA_B ... MegaVolt-Ampere (phase B) FLA....Full Load Current MVA_C... MegaVolt-Ampere (phase C) FO ....Fiber Optic B90 Low Impedance Bus Differential System GE Multilin...
  • Page 431 RST ....Reset WRT....With Respect To RSTR ..... Restrained RTD....Resistance Temperature Detector X .....Reactance RTU....Remote Terminal Unit XDUCER..Transducer RX (Rx) ..Receive, Receiver XFMR....Transformer s ..... second Z......Impedance, Zone S..... Sensitive GE Multilin B90 Low Impedance Bus Differential System...
  • Page 432: F.3.1 Ge Multilin Warranty

    APPENDIX F F.3WARRANTY F.3.1 GE MULTILIN WARRANTY If the B90 system is ordered as part of an engineered solution, the warranty is void if the relay logic is changed. NOTE For products shipped as of 1 October 2013, GE Digital Energy warrants most of its GE manufactured products for 10 years.
  • Page 433 FlexLogic™ operands ............. 5-70 BUS REPLICA Modbus registers .......... B-9, B-11, B-39 Modbus registers ............B-19 settings ............... 5-117 BUS REPLICA MECHANISM ..........9-2 CONTROL ELEMENTS ........... 5-104 BUS ZONE CONTROL POWER GE Multilin B90 Low Impedance Bus Differential System...
  • Page 434 ..............6-6 settings ............... 5-124 configuration ..............1-8 DIRECT I/O error messages ............... 7-6 see also DIRECT INPUTS and DIRECT OUTPUTS Modbus registers ............B-10 application example ...........5-125, 5-126 quick connect ..............1-10 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 435 INSPECTION CHECKLIST ..........1-1 outputs ............3-14, 3-15, 3-20 INSTALLATION specifications ..............2-13 communications ............. 3-23 FORM-C RELAY CT inputs ............... 3-13 outputs ..............3-14, 3-20 RS485 ................3-24 specifications ..............2-13 settings ................. 5-55 GE Multilin B90 Low Impedance Bus Differential System...
  • Page 436 Fast Form-C relay ............2-13 flex state parameters ............. 5-45 Form-A relay ........2-13, 3-14, 3-15, 3-20 function code 03/04h ............B-3 Form-C relay ..........2-13, 3-14, 3-20 function code 05h ............B-4 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 437 SIGNAL TYPES ..............1-3 error messages ............... 7-7 SINGLE LINE DIAGRAM ..........2-1, 2-2 FlexLogic™ operands ............ 5-71 SITE LIST, CREATING ............4-1 Modbus registers ........ B-10, B-11, B-45, B-49 SNTP PROTOCOL settings ............... 5-120 GE Multilin B90 Low Impedance Bus Differential System...
  • Page 438 VOLTAGE ELEMENTS ............5-93 VOLTAGE METERING ............6-9 Modbus registers ............B-21 VT INPUTS ...............5-56 VT WIRING ..............3-14 UL APPROVAL ..............2-17 VTFF UNAUTHORIZED ACCESS see VT FUSE FAILURE commands ..............5-11 resetting ................7-2 B90 Low Impedance Bus Differential System GE Multilin...
  • Page 439 INDEX WARRANTY ...............F-8 WEB SERVER PROTOCOL ..........5-27 WEBSITE ................1-1 WIRING DIAGRAM ............. 3-7 WARNINGS ............... 1-1 GE Multilin B90 Low Impedance Bus Differential System...
  • Page 440 INDEX viii B90 Low Impedance Bus Differential System GE Multilin...

Table of Contents