Force Contact Outputs - GE B30 Instruction Manual

Multilin b30 bus differential system ur series
Hide thumbs Also See for B30:
Table of Contents

Advertisement

5 SETTINGS


PATH: SETTINGS
TESTING
 FORCE CONTACT
 OUTPUTS
MESSAGE
MESSAGE
The relay contact outputs can be pre-programmed to respond to the test mode.
If set to "Disabled", the contact output remains fully operational. If operates when its control operand is logic 1 and will
resets when its control operand is logic 0. If set to "Energized", the output will close and remain closed for the entire dura-
tion of the test mode, regardless of the status of the operand configured to control the output contact. If set to "De-ener-
gized", the output will open and remain opened for the entire duration of the test mode regardless of the status of the
operand configured to control the output contact. If set to "Freeze", the output retains its position from before entering the
test mode, regardless of the status of the operand configured to control the output contact.
These settings are applied two ways. First, external circuits may be tested by energizing or de-energizing contacts. Sec-
ond, by controlling the output contact state, relay logic may be tested and undesirable effects on external circuits avoided.
Example 1: Initiating test mode through user-programmable pushbutton 1
For example, the test mode can be initiated from user-programmable pushbutton 1. The pushbutton will be programmed as
"Latched" (pushbutton pressed to initiate the test, and pressed again to terminate the test). During the test, digital input 1
should remain operational, digital inputs 2 and 3 should open, and digital input 4 should close. Also, contact output 1 should
freeze, contact output 2 should open, contact output 3 should close, and contact output 4 should remain fully operational.
The required settings are shown below.
To enable user-programmable pushbutton 1 to initiate the test mode, make the following changes in the
menu:
TESTING
TEST MODE
Make the following changes to configure the contact inputs and outputs. In the
and
INPUTS

FORCE CONTACT OUTPUTS

"Disabled",
FORCE Cont Ip 1:
"Freeze",
FORCE Cont Op 1:
and
"Disabled"
FORCE Cont Op 4:
Example 2: Initiating a test from user-programmable pushbutton 1 or through remote input 1
In this example, the test can be initiated locally from user-programmable pushbutton 1 or remotely through remote input 1.
Both the pushbutton and the remote input will be programmed as "Latched". Write the following FlexLogic equation:
Set the user-programmable pushbutton as latching by changing
PUSHBUTTONS
USER PUSHBUTTON 1
input 1 to initiate the Test mode, make the following changes in the
"Enabled" and
TEST MODE FUNCTION:
GE Multilin
FORCE CONTACT OUTPUTS
FORCE Cont Op 1
:Disabled
FORCE Cont Op 2
:Disabled
FORCE Cont Op xx
:Disabled
"Enabled" and
TEST MODE FUNCTION:
menus, set:
"Open",
FORCE Cont Ip 2:
FORCE Cont Ip 3:
"De-energized",
FORCE Cont Op 2:
PUSHBUTTON 1 FUNCTION
TEST MODE INITIATE:
B30 Bus Differential System
5.10.3 FORCE CONTACT OUTPUTS
Range: Disabled, Energized, De-energized, Freeze
Range: Disabled, Energized, De-energized, Freeze
Range: Disabled, Energized, De-energized, Freeze
"
PUSHBUTTON 1 ON
TEST MODE INITIATE:

SETTINGS
"Open", and
FORCE Cont Ip 4:
"Energized",
FORCE Cont Op 3:
SETTINGS
PRODUCT SETUP
to "Latched". To enable either pushbutton 1 or remote

SETTINGS
TESTING
"
"
VO1
5.10 TESTING

SETTINGS
"

TESTING
FORCE CONTACT
"Closed"

USER-PROGRAMMABLE
menu:
TEST MODE
5-199
5

Advertisement

Table of Contents
loading

Table of Contents