6.4 RECORDS

6.4RECORDS
PATH: ACTUAL VALUES
 USER-PROGRAMMABLE
 FAULT REPORT
This menu displays the user-programmable fault report actual values. See the User-Programmable Fault Report section in
chapter 5 for additional information on this feature.
PATH: ACTUAL VALUES
 EVENT RECORDS
6
The event records menu shows the contextual data associated with up to the last 1024 events, listed in chronological order
from most recent to oldest. If all 1024 event records have been filled, the oldest record will be removed as a new record is
added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated with the
event trigger. Refer to the
PATH: ACTUAL VALUES
 OSCILLOGRAPHY
This menu allows the user to view the number of triggers involved and number of oscillography traces available. The
value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillog-
CYCLES PER RECORD
raphy section of chapter 5 for additional details.
A trigger can be forced here at any time by setting "Yes" to the
menu for information on clearing the oscillography records.
CLEAR RECORDS
6-18

RECORDS
USER-PROGRAMMABLE FAULT REPORT
NEWEST RECORD
NUMBER: 0
LAST CLEARED DATE:
MESSAGE
2002/8/11 14:23:57
LAST REPORT DATE:
MESSAGE
2002/10/09 08:25:27


RECORDS

EVENT RECORDS

EVENT: XXXX
RESET OP(PUSHBUTTON)
EVENT: 3
MESSAGE
POWER ON
EVENT: 2
MESSAGE
POWER OFF
EVENT: 1
MESSAGE
EVENTS CLEARED
COMMANDS
CLEAR RECORDS


RECORDS

OSCILLOGRAPHY

FORCE TRIGGER?
No
NUMBER OF TRIGGERS:
MESSAGE
0
AVAILABLE RECORDS:
MESSAGE
0
CYCLES PER RECORD:
MESSAGE
0.0
LAST CLEARED DATE:
MESSAGE
2000/07/14
B30 Bus Differential System

6.4.1 USER-PROGRAMMABLE FAULT REPORTS

menu for clearing event records.
Range: No, Yes
15:40:16
command. Refer to the
FORCE TRIGGER?
6 ACTUAL VALUES
6.4.2 EVENT RECORDS
EVENT 3
DATE: 2000/07/14
EVENT 3
TIME: 14:53:00.03405
Date and Time Stamps
6.4.3 OSCILLOGRAPHY
COMMANDS