Section 9: Intelligent Detector Bases And Wireless Gateway; Description; Setting The Detector Address - Honeywell SLC Installation Manual

Intelligent control panel
Table of Contents

Advertisement

Section 9: Intelligent Detector Bases and Wireless

9.1 Description

The following bases provide connection between the SLC and these detector heads:
AD350 and AD355 Multi-criteria Photoelectric Smoke Detector
CP350 and CP355 Ionization Smoke Detector
H350, H350R, H355, H355R and H355HT Thermal Detector
SD350, SD350T, SD355 and SD355T Photoelectric Smoke Detector
The B501 and B210LP bases are standard plug-in detector bases.
The B501BH, B501BHT, B501BH-2, B501BHT-2, B200SR, and B200SR-LF Sounder Detector
Bases include a horn that will sound when the sensor's visible LEDs are latched on for approxi-
mately 10 seconds.
On the MS-9200 Control Panel, the sounder will activate when the sensor's visible LEDs are
latched on for approximately 10 seconds (Alarm Verification does not delay sounder).
If the MS-9600, MS-9600LS, MS-9600UDLS, MS-9200UD, MS-9200UDLS, or MS-9050UD
Control Panel is set with Alarm Verification ON, the sounder will activate at the end of the
verification cycle, providing an alarm is verified, approximately 10 seconds after the sensor's
LEDs are latched on. If Alarm Verification is OFF, the sounder will activate when the sensor's
visible LEDs are latched on for approximately 10 seconds.
The B224RB Relay Detector Base includes Form-C latching relay contacts for the control of an
auxiliary function. The relay operates 12 seconds (nominally) after activation of the sensor head
remote annunciator output.
The B224BI Isolator Detector Base prevents an entire communications loop from being disabled
when a short circuit occurs.
The W-GATE Wireless Gateway acts as a bridge between a group of wireless fire devices and a
LiteSpeed SLC loop on the MS-9200UDLS. The gateway can be powered by the SLC loop or by a
regulated, external UL-listed, 24VDC power supply. See Section 9.7.
NOTE: When using a Wireless Gateway on the SLC loop, the panel cannot have ANY modules
(wired or wireless) in the address range from 140 to 159.
For details about the wireless network and its devices, see the SWIFT™ Smart Wireless Integrated
Fire Technology Instruction Manual #LS10036-000FL-E.

9.2 Setting the Detector Address

Each intelligent detector is factory preset with an address of "00." To set an SLC address, use a
common screwdriver to adjust the rotary switches on the detector to the desired address (see "Set-
ting an SLC address for a Single Point Module" on page 34). When finished, mark the address in
the place provided on the base and the detector.
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014
Gateway
59

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents