Section 8: Multiple Input/Output Modules

8.1 Description

The CDRM-300 is an addressable module that functions as two individual relay control modules
(two isolated sets of Form-C relay contacts) and two Class B monitor modules.
Ratings for the relay contacts on the module are:
NOTE: For more information on the module specifications refer to the Installation Instructions
provided with these devices.
8.2 CDRM-300 Installation & Wiring
8.2.1 Setting an SLC address for a CDRM-300 Module
Each module is factory preset with an address of "00". To set an SLC address, use a screwdriver to
adjust the rotary switches on the module to the desired address. Each module can use up to four (4)
addresses. The base address selected via the rotary address switches will be assigned to relay output
#1 from 00 to 156. The module will automatically assign the next three addresses as appropriate to
monitored input #1, relay output #2, and monitored input #2.
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/20149/17/2014
Load Description
Inductive (PF = 0.35)
Non-Coded
Resistive
Non-Coded
Resistive
Coded
Inductive (L/R = 20ms)
Non-Coded
Inductive (PF = 0.35)
Non-Coded
Resistive
Non-Coded
Inductive (PF = 0.75)
Non-Coded
Inductive (PF = 0.35)
Non-Coded
Maximum
Application
Voltage
25 VAC
30 VDC
30 VDC
30 VDC
70.7 VAC
125 VDC
125 VAC
125 VAC
Current
Rating
2.0 A
3.0 A
2.0 A
0.46 A
0.7 A
0.9 A
0.5 A
0.3 A