2: Wiring A Nfpa Style D Idc With An Mmf-300 - Honeywell SLC Installation Manual

Intelligent control panel
Table of Contents

Advertisement

MMF-300 Wiring Diagrams
5.3.2 Wiring a NFPA Style D IDC with an MMF-300
Connect the SLC wiring to the module terminals 1 (–) and 2 (+).
Each module takes one address on the SLC. Use the rotary switches on the module to set it to the
required SLC address. Refer to "Setting an SLC address for a Single Point Module" on page 34.
The figure below shows typical wiring for a supervised and power-limited NFPA Style D (Class A)
IDC using an MMF-300 module.
Refer to the Device Compatibility Document for compatible smoke detectors.
See "Power Considerations" on page 68 for information on supervising 24 VDC power.
Manual pull
station
Heat
detector
FireLite SLC Wiring Manual — P/N 51309:P4 9/17/2014
IDC
Figure 5.10 Typical Style D IDC Wiring with an MMF-300
From
Supply
24 VDC
Four-wire
24 VDC Power
Detector Base
Filtered, Regulated,
Resettable
To Next IDC
or
Supervision Device
SLC
MMF-300
Monitor Modules
37