NOTE: The trigger selection for "strobe" follows the same timing as selected in the bell test option
(chirp/non-chirp) (Question 10, Location L1). This is in addition to its normal operation of a latched
output on alarm that is reset after the system is disarmed.
TWO-WAY VOICE - This trigger activates when line seizure occurs if the event is any of the following:
burglary, fire, duress, keypad panic, keypad fire, or keypad auxiliary. It does not activate for CS test,
openings/closing, trouble, bypass, cancel, or restore. It deactivates about 1 second before disconnecting
the telephone line. Also, at the time of release, keypad sounders are silenced for the remaining duration
of the bell output cycle. The bell times out or a valid user code terminates.
NOTE: The trigger outputs are limited to approximately 50mA each.
U L
Two-Way Voice has not been evaluated by UL and must not be used for UL installations.
NONINVERT TRIGGER - The trigger output (positive to negative) is normally floating, and actively
sinks (becomes a negative) on activation.
INVERT TRIGGER - The trigger output (positive to negative) is normally sinking (negative with
respect to positive), and actively floats on activation.
TRIGGER TYPE DEFINITION
Smoke Power (Trigger #1 Only)
Smoke Power - No Verification
2-Way Voice
Burglary Bell Trigger
Ready
Armed
Exit Time
Entry Time
Fire-Only Latch
Burglary-Only Latch
Strobe (see note below)
Panic Alarm
Shock Asterisk Reset
Duress
RF Trouble
RF Button Toggle
Alarm/Restore
Chime
Keypad Sounder
RF Momentary
Section 7 - System Programming
DESCRIPTION OF OPERATION
Used in fire verification to reset smoke power
Used to power smoke detectors with no verification
See below
Follows burglary bell timer
Follows READY LED; used for keyfob
Follows ARM LED; used for keyfob
On during exit time
On during entry time
Pulses w/fire bell, off w/code
On w/burglary bell, off w/code
On steady w/burglary bell, pulse w/fire bell
Follows keypad panic
Asterisk "*" activates for 2-6 seconds
Pulses for 2-6 seconds following entry of Duress code
Active if any RF zone is in tamper, supervision, or low
battery, or the bell is in supervision
Any keyfob button can toggle this trigger; intended for
lighting control
Active on any zone alarm. Inactive on alarm restore
Active when a zone programmed with chime activates
Active when keypad sounder activates
Active when keyfob momentary Trigger 1 or 2 activates
7–33