Logic Operands - GE Multilin G650 Manual

Generator protection & control system
Hide thumbs Also See for Multilin G650:
Table of Contents

Advertisement

APPENDIX A
APPENDIX A LOGIC OPERANDSA.1LOGIC OPERANDS
OPERANDS - G650 - MODEL FX - GX
INTERNAL SYSTEM STATUS
AUTOCHECK INTERNAL STATES (CRITICAL)
DSP Internal States (Critical to metering and
protection)
Flash Internal States (Critical to Relay configuration
and stored data)
IO Board States (Critical to operation and
protection)
IEC61850 INTERNAL STATES (NON CRITICAL)
OTHER INTERNAL STATES (NON CRITICAL)
Other internal states
Autocheck Internal States (Not available)
GEK-113285A
DSP COMM ERROR
MAGNETIC MODULE
ERROR
CALIBRATION ERROR
E2PROM STATUS
BOARD F STATUS
BOARD G STATUS
BOARD H STATUS
BOARD J STATUS
USER MAP STATUS
FACTORY
CALIBRATION
FLEXCURVE A STATUS User curve A: (0) Not configured (1) Configured
FLEXCURVE B STATUS User curve B: (0) Not configured (1) Configured
FLEXCURVE C STATUS User curve C: (0) Not configured (1) Configured
FLEXCURVE D STATUS User curve D: (0) Not configured (1) Configured
Green Zone
Yellow Zone
Orange Zone
Red Zone
UpTime
TIMER STATUS
GRAPHIC STATUS
ALARM TEXT ARRAY
G650 Generator Protection & Control System
A.1 LOGIC OPERANDS
DSP Communication Error: (0) Rignt communications
between DSP and main processor; (1) Communication
Error between DSP and main processor
Magnetic Module Error: (0) Right Communication
between DSP and magnetic module processor; (1)
Communication Error between DSP and magnetic
module processor
Calibration Error: (0) Right calibration values stored; (1)
The calibration values stored are out of the calibration
limits.
E2prom status :(0) Not configured or problems during
writing process ; (1) Configured and OK
Board F status: (0) Inactive - There is no communication
with the board (1) Active - There is communication with
the board.
Board G status: (0) Inactive - There is no communication
with the board (1) Active - There is communication with
the board.
Board H status: (0) Inactive - There is no communication
with the board (1) Active - There is communication with
the board.
Board J status: (0) Inactive - There is no communication
with the board (1) Active - There is communication with
the board.
User map status: (0) Not configured ; (1) Configured
Calibration status (0) Not calibrated ; (1) Relay calibrated
Memory internal status
Memory internal status
Memory internal status
Memory internal status
System Time
Real time clock autocheck (not available)
Graphic display status (not available)
Text display status (not available)
A
A-1

Hide quick links:

Advertisement

Table of Contents
loading