8.3 FIRMWARE VERSION UPGRADE
6.
FOLLOW THE INDICATIONS OF THE PROGRAM AND SELECT THE BOOT PROGRAM BIN FILE.
7.
WHEN REQUIRED BY THE PROGRAM SWITCH OFF AND BACK ON THE RELAY.
8.
CONTINUE WITH THE PROCESS AND SET THE IP ADDRESS AND GATEWAY WHEN REQUIRED.
1.
INSTALL THE PROPER VERSION OF THE ENERVISTA 650 SETUP PROGRAM.
2.
CONNECT ONE ETHERNET CABLE AT THE REAR ETHERNET PORT (CROSSOVER CABLE FOR BACK-TO-
BACK CONNECTION AND STRAIGHT-THROUGH ETHERNET CABLE FOR HUB OR SWITCH).
3.
SET THE APPROPRIATE IP ADDRESS IN THE RELAY.
4.
SET THE APPROPRIATE IP ADDRESS IN THE PC.
5.
FROM THE ENERVISTA 650 SETUP PROGRAM SELECT "Communications > Upgrade Firmware Version".
6.
ENTER THE IP ADDRESS, SERIAL NUMBER AND ORDERING CODE OF THE RELAY TO UPGRADE.
7.
WHEN REQUIRED BY THE PROGRAM SWITCH OFF AND BACK ON THE RELAY.
8.
LOCATE THE UPGRADE.TXT FILE ACCORDING TO THE MODEL OF THE RELAY.
9.
PRESS UPGRADE FIRMWARE AND INITIATE THE UPGRADE PROCESS.
10. TO COMPLETE THE PROCEDURE, SWITCH OFF AND BACK ON THE RELAY WHEN REQUIRED BY THE
PROGRAM.
11. SET CALIBRATION SETTINGS (FROM THE PC TO THE RELAY).
12. THE SETTINGS AND CONFIGURATION ARE NOW SET TO FACTORY DEFAULT.
13. SEND THE NEW SETTINGS AND CONFIGURATION FILES TO THE RELAY IF NECESSARY.
(*) The boot code upgrade must be performed using a crossed copper cable (RJ45) connected to the PC. It is not
necessary to modify the internal fiber/cable switch, as the upgrade is carried out at 10 Mb/s, and thus there is not cable/
fiber conflict.This fact does not apply to the firmware upgrade, which can be performed either with the Ethernet fiber
connection, or with the cable connection.
Note: Please see chapter 8 TROUBLESHOOTING GUIDE if there is any problem during the upgrading process.
8
8-12
G650 Generator Protection & Control System
8 BOOTCODE AND FIRMWARE UPGRADE

8.3.3 FIRMWARE UPGRADE (*)

GEK-113285A

Hide quick links: