5.5 CONTROL ELEMENTS
5
The G650 includes eight pulse counters, each pulse counter stores the activation number of the input set to that pulse
counter. This value can be multiplied for a factor selectable by setting.
The inputs used in this pulse counter function can be selected from all the available in the G650 device. Take into account
that the input/output settings are both set for the generic input as well as for the pulse counter input, e.g. Debounce time.
The settings for this function can be found at Setpoint > Control Elements > Pulse Counters
Table 5–87: PULSE COUNTERS SETTINGS
SETPOINT > CONTROL ELEMENTS > PULSE COUNTERS
SETTING DESCRIPTION
Pulse counter enabling setting
Name of the pulse counter
Multiplier factor for the pulse counter
Overflow value for the pulse counter
Board selection for the pulse counter
Input index inside the selected board
Note: X is the pulse counter index, up to 8.
Pulse Counters settings are:
CntPulses Enabled:
CntPulses Name:
CntPulses Factor:
5-92
Figure 5–21: FUSE FAILURE ELEMENT BLOCK DIAGRAM
NAME
CntPulses Enabled X
CntPulses Name X
CntPulses Factor X
CntPulses Overflow X
CntPulses Board Origin X
CntPulses Input Origin X
Enable/disable each pulse counter.
Each pulse counter can have a configurable user name.
This is the factor multiplier applied to the input activations number stored in the
pulse counter, providing possibilities to adjust the obtained value to any scale. It the
"CntPulses Factor X" is set to zero it will take no effect.
G650 Generator Protection & Control System
DEFAULT VALUE
STEP
RANGE
DISABLED
N/A
[DISABLED – ENABLED]
Pulse Counter X
N/A
N/A
1.000
0.001 [0.000 : 65000.000]
65535
1
[0 : 1000000]
F
N/A
[F,G,H,I]
1
1
[1 : 32]
5 SETTINGS

5.5.7 PULSE COUNTERS

GEK-113285A