Table B–9: MODBUS MEMORY MAP (Sheet 27 of 46)
ADDR
REGISTER NAME
A508
PID 1 Integ Time Const
A509
PID 1 Antiwindup
A50A
PID 1 AW Time Const
A50B
PID 1 Deriv Time Const
A50C
PID 1 Derivative Limit
A50D
PID 1 Max
A50E
PID 1 Min
A50F
PID 1 T Min
A510
PID 1 Dead Time
A511
PID 1 Block
A513
PID 1 Target
A514
PID 1 Events
A515
...Repeated for PID 2
A52A
...Repeated for PID 3
A53F
...Repeated for PID 4
PID Regulator Actual Values (Read Only) (4 modules)
A560
PID 1 Out
A562
PID 1 Delta Out
A564
PID 1 Setpoint
A566
...Repeated for PID 2
A56C
...Repeated for PID 3
A572
...Repeated for PID 4
Non Volatile Latches (Read/Write Setting) (16 modules)
A700
Non-Volatile Latch 1 Function
A701
Non-Volatile Latch 1 Type
A702
Non-Volatile Latch 1 Set
A704
Non-Volatile Latch 1 Reset
A706
Non-Volatile Latch 1 Target
A707
Non-Volatile Latch 1 Events
A708
Reserved (4 items)
A70C
...Repeated for Non-Volatile Latch 2
A718
...Repeated for Non-Volatile Latch 3
A724
...Repeated for Non-Volatile Latch 4
A730
...Repeated for Non-Volatile Latch 5
A73C
...Repeated for Non-Volatile Latch 6
A748
...Repeated for Non-Volatile Latch 7
A754
...Repeated for Non-Volatile Latch 8
A760
...Repeated for Non-Volatile Latch 9
A76C
...Repeated for Non-Volatile Latch 10
A778
...Repeated for Non-Volatile Latch 11
A784
...Repeated for Non-Volatile Latch 12
A790
...Repeated for Non-Volatile Latch 13
A79C
...Repeated for Non-Volatile Latch 14
A7A8
...Repeated for Non-Volatile Latch 15
A7B4
...Repeated for Non-Volatile Latch 16
IEC 61850 received analog settings (read/write) (32 modules)
AA00
IEC 61850 GOOSE analog 1 default value
AA02
IEC 61850 GOOSE analog input 1 mode
AA03
IEC 61850 GOOSE analog input 1 units
AA05
IEC 61850 GOOSE analog input 1 per-unit base
AA07
...Repeated for IEC 61850 GOOSE analog input 2
AA0E
...Repeated for IEC 61850 GOOSE analog input 3
AA15
...Repeated for IEC 61850 GOOSE analog input 4
GE Multilin
RANGE
0 to 600
0 to 1
0 to 600
0 to 600
1 to 20
-10000 to 10000
-10000 to 10000
100 to 9999
1 to 20
0 to 4294967295
0 to 2
0 to 1
0 to 999999
0 to 999999
-99999.99 to 99999.99
0 to 1
0 to 1
0 to 4294967295
0 to 4294967295
0 to 2
0 to 1
---
–1000000 to 1000000
0 to 1
---
0 to 999999999.999
C30 Controller System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
sec
0.01
F001
---
1
F102
sec
0.01
F001
sec
0.01
F001
---
1
F001
---
1
F002
---
1
F002
ms
1
F001
sec
1
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F004
---
1
F004
---
0.01
F004
---
---
1
F102
---
1
F519
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
---
F001
---
0.001
F060
---
1
F491
0 (Default Value)
---
---
F207
---
0.001
F060
DEFAULT
100
0 (Disabled)
100
100
10
10
10
500
1
0
0 (Self-reset)
B
0 (Disabled)
0
0
0
0 (Disabled)
0 (Reset
Dominant)
0
0
0 (Self-reset)
0 (Disabled)
0
1000
(none)
1