GE C30 Instruction Manual page 326

Ur series
Hide thumbs Also See for C30:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 16 of 46)
ADDR
REGISTER NAME
42FC
...Repeated for User-Programmable LED 21
42FF
...Repeated for User-Programmable LED 22
4302
...Repeated for User-Programmable LED 23
4305
...Repeated for User-Programmable LED 24
4308
...Repeated for User-Programmable LED 25
430B
...Repeated for User-Programmable LED 26
430E
...Repeated for User-Programmable LED 27
4311
...Repeated for User-Programmable LED 28
4314
...Repeated for User-Programmable LED 29
4317
...Repeated for User-Programmable LED 30
B
431A
...Repeated for User-Programmable LED 31
431D
...Repeated for User-Programmable LED 32
4320
...Repeated for User-Programmable LED 33
4323
...Repeated for User-Programmable LED 34
4326
...Repeated for User-Programmable LED 35
4329
...Repeated for User-Programmable LED 36
432C
...Repeated for User-Programmable LED 37
432F
...Repeated for User-Programmable LED 38
4332
...Repeated for User-Programmable LED 39
4335
...Repeated for User-Programmable LED 40
4338
...Repeated for User-Programmable LED 41
433B
...Repeated for User-Programmable LED 42
433E
...Repeated for User-Programmable LED 43
4341
...Repeated for User-Programmable LED 44
4344
...Repeated for User-Programmable LED 45
4347
...Repeated for User-Programmable LED 46
434A
...Repeated for User-Programmable LED 47
434D
...Repeated for User-Programmable LED 48
Installation (Read/Write Setting)
43E0
Relay Programmed State
43E1
Relay Name
User Programmable Self Tests (Read/Write Setting)
4441
User Programmable Detect Ring Break Function
4442
User Programmable Direct Device Off Function
4443
User Programmable Remote Device Off Function
4444
User Programmable First Ethernet Fail Function
4445
User Programmable Secondary Ethernet Fail Function
4446
User Programmable Battery Fail Function
4447
User Programmable SNTP Fail Function
4448
User Programmable IRIG-B Fail Function
444A
Process Bus Failure Operand
444C
PTP Fail Function
444D
User Programmable Third Ethernet Fail Function
444E
User Programmable SFP Fail Function
Breaker control (read/write settings)
47D0
Breaker 1 function
47D1
Breaker 1 name
47D4
Breaker 1 mode
47D5
Breaker 1 open
47D7
Breaker 1 close
47D9
Breaker 1 phase A / three-pole closed
47DB
Breaker 1 phase B closed
47DD
Breaker 1 phase C closed
B-24
RANGE
0 to 1
---
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 4294967295
0 to 1
0 to 1
0 to 1
0 to 1
---
0 to 1
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
C30 Controller System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F133
---
---
F202
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
1
F300
---
1
F102
---
1
F102
---
1
F102
---
1
F102
---
---
F206
---
1
F157
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
DEFAULT
0 (Not
Programmed)
"Relay-1"
1 (Enabled)
1 (Enabled)
1 (Enabled)
0 (Disabled)
0 (Disabled)
1 (Enabled)
1 (Enabled)
1 (Enabled)
0
1 (Enabled)
0 (Disabled)
0 (Disabled)
0 (Disabled)
"Bkr 1"
0 (3-Pole)
0
0
0
0
0
GE Multilin

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents