GE C30 Instruction Manual page 158

Ur series
Hide thumbs Also See for C30:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
spontaneous responses from the C30 when any current values change by 15 A, the
ting should be set to 15. Note that these settings are the default values of the deadbands. P_ME_NC_1 (parameter of mea-
sured value, short floating point value) points can be used to change threshold values, from the default, for each individual
M_ME_NC_1 analog point. Whenever power is removed and re-applied to the C30, the default thresholds are in effect.
The
IEC REDUNDANCY
two simultaneous connections can be active at any given time.
When the IEC port number is set to 0, the change takes effect when the C30 is restarted.
NOTE
The C30 relay does not support power metering. As such, the
cable.
NOTE
The C30 relay does not support energy metering. As such, the
cable.
NOTE
The IEC 60870-5-104 and DNP protocols cannot be used simultaneously. When the IEC 60870-5-104 FUNCTION
setting is set to "Enabled", the DNP protocol does not operate. When this setting is changed, it takes effect when
power to the relay is cycled (off-to-on).
NOTE
PATH: SETTINGS
PRODUCT SETUP
ADDRESSES
 IEC NETWORK
 CLIENT ADDRESSES
5
The UR can specify a maximum of five clients for its IEC 104 connections. These are IP addresses for the controllers to
which the UR can connect.
A maximum of two simultaneous connections are supported at any given time.
l) EGD PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
 EGD PROTOCOL
The C30 Controller System is provided with optional Ethernet Global Data (EGD) communications capa-
bility. This feature is specified as a software option at the time of ordering. See the Ordering section of
chapter 2 for additional details.
5-42
setting decides whether multiple client connections are accepted or not. If redundancy is set to Yes,

COMMUNICATIONS
CLIENT ADDRESS 1:
0.0.0.0
CLIENT ADDRESS 2:
MESSAGE
0.0.0.0
CLIENT ADDRESS 3:
MESSAGE
0.0.0.0
CLIENT ADDRESS 4:
MESSAGE
0.0.0.0
CLIENT ADDRESS 5:
MESSAGE
0.0.0.0

COMMUNICATIONS
 FAST PROD EXCH 1
 CONFIGURATION
 SLOW PROD EXCH 1
MESSAGE
 CONFIGURATION
 SLOW PROD EXCH 2
MESSAGE
 CONFIGURATION
C30 Controller System
IEC CURRENT DEFAULT THRESHOLD
IEC POWER DEFAULT THRESHOLD
IEC ENERGY DEFAULT THRESHOLD

IEC 60870-5-104 PROTOCOL
Range: Standard IPV4 address format
Range: Standard IPV4 address format
Range: Standard IPV4 address format
Range: Standard IPV4 address format
Range: Standard IPV4 address format

EGD PROTOCOL
5 SETTINGS
set-
setting is not appli-
setting is not appli-

IEC NETWORK CLIENT
GE Multilin

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents