18.1.1 Connection diagram of the synchronism inputs
19

Dry Contact Relays

RPV311-TM-EN-7
To synchronize the equipment using fiber-optic input, use the appropriate fiber-optic
type, considering its minimum curvature radius.
The use of a twisted pair cable is recommended for the electrical input.
For distances greater than 3 m, to minimize EMC effects, the use of fiber-optic cable
is recommended.

Figure 133: Connection diagram of electrical synchronism inputs

For information about electrical synchronism input specifications, Chapter 17:
Technical Specifications.

Figure 134: Connections diagram of optical synchronism inputs

Information about optical synchronism inputs specifications, see Chapter 17:
Technical Specifications.
The RPV311 has 4 electromechanical signaling relays. Each relay has one dry
contact, as shown in
The first relay contact is normally closed and it opens when the unit goes into
operation and it is not configurable by the user.
The other three contacts are normally open and can be individually configured using
the Web Interface. For information about relays output configuration, Chapter 17:
Technical Specifications.
Figure 135.
Chapter 15 – Installation
240