Toshiba GR200 Series Instruction Manual page 382

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Trigger modes
7.2.2
We can simplify the trigger signals into four: 'On', 'Off ', 'On and Off ', and 'Change' modes. Thus,
the user can should set a mode for respective triggers using [Trigger Mode1] and others.
'On' mode
(i)
In the 'On' mode, the event recorder can take an action when the trigger signal is switched to
'On', as shown in Figure 7.2-2. For the operation, set On for the [Trigger Mode*].
On
Off
Triggers generated
'Off' mode
(ii)
The 'Off ' mode is the other way of the 'On' mode; set Off for the operation.
On
Off
Figure 7.2-3 Trigger generated at 'Off' mode
'On-Off' mode
(iii)
In the 'On-Off ' mode, the trigger signal is generated when the pulse train is changed from 'On
to Off ' and 'Off to On' both, as shown in Figure 7.2-4. Set On-Off for the operation
On
Off
Triggers generated
Figure 7.2-4 Trigger generated at 'On-Off' mode
'Change' mode
(iv)
The 'Change mode' is provided to detect the increment or the decrement of a number, when
new number is generated in the PLC logic. For example, this mode allows to detect the change
Triggers generated
Figure 7.2-2 Trigger generated at 'On' mode
Triggers generated
Triggers generated
- 368 -
Triggers generated
Triggers generated Triggers generated
Triggers generated
6F2S1931 (0.20)
Pulse train
Pulse train
Pulse train
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)