Table 4.4-4 Threshold voltage of picking-up / dropping-off for binary inputs
(a) In the case of DC rated voltage "110-250 Vdc"
Voltage level
High
Low
(b) In the case of DC rated voltage "24-60 Vdc"
Voltage level
High
Low
As the threshold voltage is expressed with Table 4.4-4, the user should set High or Low to
match to the voltage value to input to binary inputs. Table 4.4-5 shows the recommended
settings.
This matter means that the user should also set a threshold voltage at the power supply unit
to determine the degree of the power failure (see
module
).
Table 4.4-5 Recommended setting for the voltage level
(a) In the case of DC rated voltage "110-250 Vdc"
Voltage value
to input to binary inputs
250V
220V
125V
110V
(b) In the case of DC rated voltage "24-60 Vdc"
Voltage value
to input to binary inputs
60V
48V
30V
24V
Threshold voltage of picking-up / dropping-off for binary inputs
Typical 136V
Typical 71V
Threshold voltage of picking-up / dropping-off for binary inputs
Typical 30V
Typical 15V
Recommended setting for the voltage level
Recommended setting for the voltage level
- 280 -
How to set
Selection switch
[THRES_Lvl] = High
Selection switch
[THRES_Lvl] = Low
How to set
Selection switch
[THRES_Lvl] = High
Selection switch
[THRES_Lvl] = Low
Chapter: Technical description: Power supply
High
Low
High
Low
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
6F2S1931 (0.20)
Note
This is default.
Note
This is default.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Grb200

Table of Contents