Toshiba GR200 Series Instruction Manual page 137

Centralized busbar protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Setting
2.5.3
Setting of CBP_EFP (Function ID: 457B01)
Setting item
EFPTP-FS
Common
EFP-EN_CH1
Off / On-Zone / On-TR
OCEFP_CH1
CH1
TEFP_CH1
TDLD_CH1
EFP-EN_CH2
Off / On-Zone / On-TR
OCEFP_CH2
CH2
TEFP_CH2
TDLD_CH2
EFP-EN_CH3
Off / On-Zone / On-TR
OCEFP_CH3
CH3
TEFP_CH3
TDLD_CH3
(CH4 to CH23 are omitted)
EFP-EN_CH24
Off / On-Zone / On-TR
OCEFP_CH24
CH24
TEFP_CH24
TDLD_CH24
Un
Range
its
Off/ On
-
Fail safe for EFP trip enable
-
EFP enable
0.10 - 5.00
-
OCEFP relay operating level (multiplied by CT secondary
rating)
0.00 - 300.00
s
EFP trip delay time
0.00 - 300.00
s
Dead line detection timer
-
EFP enable
0.10 - 5.00
-
OCEFP relay operating level (multiplied by CT secondary
rating)
0.00 - 300.00
s
EFP trip delay time
0.00 - 300.00
s
Dead line detection timer
-
EFP enable
0.10 - 5.00
-
OCEFP relay operating level (multiplied by CT secondary
rating)
0.00 - 300.00
s
EFP trip delay time
0.00 - 300.00
s
Dead line detection timer
-
EFP enable
0.10 - 5.00
-
OCEFP relay operating level (multiplied by CT secondary
rating)
0.00 - 300.00
s
EFP trip delay time
0.00 - 300.00
s
Dead line detection timer
- 123 -
Contents
Centralized GRB200
(Soft: 030, 031, 032, 033, 034)
6F2S1931 (0.20)
Default
setting
Notes
value
Off
Off
1.00
0.20
10.00
Off
1.00
0.20
10.00
Off
1.00
0.20
10.00
Off
1.00
0.20
10.00

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Grb200