Bosch PSI 6XXX.350 L1 Series Technical Information page 82

Timer and i/o level
Table of Contents

Advertisement

<Proportional valve selection, 1 through 128>
<Current scaling/check finished>
<Pressure calibration/check finished>
1070 080 067-101 (2001.03) GB
PSI 6XXX.350 L1
The pressure control value is output in digital form (8 bit resolution) via the serial outputs.
Thus, the 0 through 100% setting range is subdivided into 256 segments.
The digitized pressure value is output with <Spot selection>. If <Spot selection> = 0,
the digital value that was output previously is retained.
Successful completion of a <Current scaling> operation is indicated at the output level
by a <Current scaling/check finished> signal, which stays high until the <Current
scaling> input signal is reset. Cf. <Current scaling>, page 7-24.
Successful completion of a <Current check> operation is indicated at the output level by
a <Current scaling/check finished> signal, which stays high until the <Current check>
input signal is reset. No <WC> signal is output during a <Current check>. Cf. <Current
check>, page 7-27.
Successful completion of a <Pressure calibration> operation is indicated at the output
level by a <Pressure calibration/check finished> signal, which stays high until the
<Pressure calibration> input signal is reset. Cf. <Pressure calibration>, page 7-31.
Successful completion of a <Pressure check> operation is indicated at the output level
by a <Pressure calibration/check finished> signal, which stays high until the <Pres-
sure check> input signal is reset. A <WC> signal is output during <Pressure calibration
/ Pressure check>. Cf. <Pressure check>, page 7-34.
Electrical connection
7-41