3 Functions
3.5.7.2

Selection of command source

Selection of
P0700 =...
command source
Selects digital command source.
0
Factory fault setting
1
BOP (keypad)
2
Terminal
4
USS on BOP link
5
USS on COM link
6
CB on COM link
3.5.7.3

Digital input (DIN)

Function digital input 1
P0701 = ...
Terminal 5
1
ON / OFF1
Function digital input 2
P0702 = ...
Terminal 6
12
Reverse
Function digital input 3
P0703 = ...
Terminal 7
9
Fault acknowledge
Function digital input 4
P0704 = ...
Terminal 8
15
Fixed setpoint (Direct selection)
P0705 = ...
Function digital input 5
Terminal 16
15
Fixed setpoint (Direct selection)
Function digital input 6
P0706 = ...
Terminal 17
15
Fixed setpoint (Direct selection)
Function digital input 7
P0707 = 0
Via analog input, Terminal 3
0
Digital input disabled
Function digital input 8
P0708 = 0
Via analog input, Terminal 10
0
Digital input disabled
P0724 = ...
Debounce time for digital inputs
Defines debounce time (filtering time) used for digital inputs.
0
No debounce time
1
2.5 ms debounce time
2
8.2 ms debounce time
3
12.3 ms debounce time
P0725 = ...
PNP / NPN digital inputs
Change-over (toggles) between high active (PNP) and low active (NPN). This applies to all
digital inputs simultaneously.
0
NPN mode ==> low active
1
PNP mode ==> high active
98
2
BOP
Terminals
P0700 = 2
USS
BOP link
USS
COM link
CB
COM link
1
Possible Settings:
0
Digital input disabled
1
ON / OFF1
2
ON + Reverse / OFF1
12
3
OFF2 – coast to standstill
4
OFF3 – quick ramp-down
9
Fault acknowledge
10
JOG right
9
11
JOG left
12
Reverse
13
MOP up (increase frequency)
14
MOP down (decrease frequency)
15
15
Fixed setpoint (Direct selection)
16
Fixed setpoint (Direct selection + ON)
17
Fixed setpoint (Binary coded selection + ON)
21
Local/remote
15
25
DC brake enable
29
External trip
33
Disable additional freq setpoint
99
Enable BICO parameterization
15
0
ON > 3,9 V, OFF < 1,7 V
DIN7
1
2
0
3
4
MICROMASTER 440
Issue 10/06
Sequence control
Setpoint
Motor
channel
control
DIN8
1
2
10
11
3
1
Operating Instructions