7.3 Pressure controlled supply fan + ESM fixed speed

Macro 105 "Pressure controlled supply fan + ESM
fixed speed"
Pressure in air duct regulated by integrated PID
controller
Flying restart and automatic restart activated
Essential service mode (in the event of fire) with
fixed frequency
Error message: Digital output 0
Status display: Digital output 2
When selecting this application using macro 105, the
technological unit remains unchanged at [%]. If
necessary, adapt the unit as described in the parameter
list. Select the values depending on the used sensor.
Notice:
In the case of the extended emergency mode, the
customer can no longer lodge any claims for warranty.
Extended emergency mode and the faults which arise
during this mode are logged in a password-protected
memory and can be read by the repair center.
Parameter
Value
p596
500
p0010
5
p595
5
p0010
0
p756[0]
0
p0840
r722.0
p1015[0]
1350 rpm
p1113[0]
0
p1200[0]
1
p1210
26
p2200[0]
1
p2201[0]
200 Pa
p2253[0]
p2201
p2257
30s
p2258
30s
p2264[0]
r755[0]
p2265
10 s
p2267
600 Pa
p2268
-50 Pa
p2293
30 s
p3880
r722.1
p3881
1
Siemens
Building Technologies
Description
Reference variable of the technological unit
Parameter filter change, technological unit
Selection of technological unit: Pa
Parameter filter ready
Unipolar voltage input (0...10 V)
ON / OFF (OFF1)
Fixed speed setpoint 15
Setpoint inversion
Flying restart always active (start in setpoint direction)
Acknowledging all faults and restarting for an ON command
Technology controller enable
Technology controller fixed value 1
Technology controller setpoint 1
Technology controller setpoint ramp-up time
Technology controller setpoint ramp-down time
Technology controller actual value
Technology controller actual value filter time constant
Technology controller upper limit actual value
Technology controller lower limit actual value
Technology controller ramp-up/ramp-down time
ESM activation
ESM setpoint source: Fixed setpoint 15 (p1015)
Pressure controlled supply fan + ESM fixed speed
Application examples