Service, maintenance and fault rectification
8
Fault rectification
84 | 98
Siemens
Building Technologies
Number
Cause
F01662
CU hardware fault
A01910
Setpoint timeout: p2040 ≠ 0
ms and one of the following
F01910
causes:
The bus connection is
interrupted
The MODBUS master
is switched off
Communications error
(CRC, parity bit, logical
error)
F03505
Analog input, wire break
F06310
Supply voltage (p0210)
incorrectly parameterized
F07011
Motor overtemperature
F07016
Motor temperature sensor
fault
F07086
Switching over units:
Parameter limit violation
F07088
F07320
Automatic restart aborted
F07330
Search current measured
too low
F07426
Technology controller
actual value limited
F07801
Motor overcurrent
Solution
1.
Switch the CU off and on again.
2.
Update the firmware.
3.
Contact Technical Support.
1.
Establish the bus connection and switch on the
communication partners.
2.
Possibly adapt p2040.
3.
Set the PROFIBUS master to RUN.
1.
Check the connection with the signal source for
interruptions.
2.
Check the level of the signal which is fed in.
The input current measured by the analog input can be
read in r0752.
1.
Check the supply voltage and change the parameter
(p0210), if necessary.
2.
Check the line voltage.
1.
Reduce the motor load.
2.
Check the ambient temperature and the motor
ventilation.
3.
Check the wiring and the connection of the sensor.
1.
Check that the sensor is correctly connected.
2.
Check the parameter assignment (p0601).
3.
Switch off the temperature sensor error (p0607 = 0).
Check the adapted parameter value and correct it, if
necessary.
1.
Increase the number of restart attempts (p1211). The
actual number of start attempts is shown in r1214.
2.
Increase the waiting time in p1212 or the monitoring
time in p1213.
3.
Apply the ON command (p0840).
4.
Increase the monitoring time of the power unit or
disable the monitoring time (p0857).
5.
Reduce the waiting time for resetting the fault
counter p1213[1] so that fewer faults are registered
in the time interval.
1.
Increase the search current (p1202).
2.
Check that the motor is correctly connected.
The actual value for the technology controller which is
interconnected via connector input p2264 has reached a
limit.
1.
Adjust the limits to the signal level (p2267, p2268).
2.
Check the actual value (p2264).
The permissible motor limit current has been exceeded.
1.
Check the current limits (p0640).
2.
Vector control: Check the settings for the current
controller (p1715, p1717).
3.
V/f control: Check the settings for the current limiting
controller (p1340...p1346).
4.
Increase the up ramp (p1120) or reduce the load.
5.
Check the motor and the motor cables for short-
circuits or ground faults.
6.
Check the motor for star-delta connection and rating
plate parameterization.
7.
Check the combination of the power unit and motor.
8.
Select the flying restart function (p1200) if switched
to rotating motor.
A5E36496664A_d
2016-03-17