Pump Pressure Control - Siemens G120P Technical Manual

Variable speed drive
Table of Contents

Advertisement

Application examples
7

Pump pressure control

7.2 Pump pressure control
Macro 103 "Pump pressure control"
Differential pressure regulated by integrated PID
controller
Flying restart and automatic restart activated
Error message: Digital output 0
Status display: Digital output 2
When selecting this application using macro 103, the
technological unit remains unchanged at [%]. If
necessary, adapt the unit as described in the parameter
list. Select the values depending on the used sensor.
Parameter
Value
p596
4
p0010
5
p595
3
p0010
0
p756[0]
0
p0840
r722.0
p1200[0]
1
p1210
26
p2200[0]
1
p2201[0]
2 bar
p2253[0]
p2201
p2257
30s
p2258
30s
p2264[0]
r755[0]
p2265
10 s
p2267
4.2 bar
p2268
-1 bar
p2293
30 s
68 | 98
Siemens
Building Technologies
Description
Reference variable of the technological unit
Parameter filter change, technological unit
Selection of technological unit: bar
Parameter filter ready
Unipolar voltage input (0...10 V)
ON / OFF (OFF1)
Flying restart always active (start in setpoint direction)
Acknowledging all faults and restarting for an ON command
Technology controller enable
Technology controller fixed value 1
Set the pressure setpoint to suit the application. This example uses a 0 to 4 bar sensor (e.g. QBE64).
Technology controller setpoint 1
Technology controller setpoint ramp-up time
Technology controller setpoint ramp-down time
Technology controller actual value
Technology controller actual value filter time constant
Technology controller upper limit actual value
Technology controller lower limit actual value
Technology controller ramp-up/ramp-down time
A5E36496664A_d
2016-03-17