Transfer D20/D200 configurations to the D20MX

76
3.2.
Click the Interface tab; in the Connection Type group select Direct Serial. If
necessary, select the Communication Port, and in the Port Setting tab, select
the Baud Rate as follows:
Baud Rate
The baud rate of the D20MX console port which is either
9600 or 19200 baud and can be changed with the JBAUD
command.
The baud rate configured for COM0 in WESMAINT
Result: The Direct Serial option is selected.
3.3.
Click OK to close D2x Device Communication Options dialog box
Result: The dialog box closes.
4.
Click the SGConfig ribbon Configure group > Communications > Connect to open the
terminal emulator.
Result: The Terminal Emulator tab appears.
5.
If WESMAINT is running, press Enter to get the WESMAINT login screen.
Result: The WESMAINT login screen appears
6.
Enter a User Name and Password of a user account having SHELL access level of
Maintenance or higher.
7.
If WESMAINT is running, navigate to the D20MX SHELL using the WESMAINT menu
items 2 followed by 3. Wait for the countdown then press Enter several times.
Result: The D20M> prompt appears
8.
Apply the HSP by clicking the SGConfig ribbon Configure group > Actions > Apply HSP.
Result: A dialog box displaying a warning opens.
9.
Read the warning then click Yes to close the warning dialog box.
Result: The warning dialog box closes and the Applying HSP dialog box opens.
10. The terminal emulator screen shows the progress of the HSP update.
11. This process can take 5 minutes to 1/2 hour to apply the HSP depending on which
components are updated.
12. When complete, there are two possibilities
An Information dialog box asks you to toggle the power switch on the D20MX. If
so, perform the following steps:
12.1. Click OK to close the information dialog box.
Result: The dialog box closes.
12.2. Toggle the power switch on the D20MX.
Result: The D20MX restarts with the new JMON, Bootrom and FPGA.
An information dialog indicates the operation is complete. If so, just click OK to
close the information dialog box.
13. Close the SGConfig Terminal Emulator.
Use this information to transfer existing D20 and D200 device configurations to the
D20MX.
Transferring a multi-processor D200 only transfers the application configurations on the
first processor.
CHAPTER 5: CONFIGURING THE SOFTWARE
GE INFORMATION
When to set this baud rate
If the D20MX is configured
for device redundancy
If the D20MX is configured
for standalone operation
D20MX INSTRUCTION MANUAL