Generate A System Default Configuration For The D20Mx - GE D20MX Instruction Manual

Hide thumbs Also See for D20MX:
Table of Contents

Advertisement

D20MX Processor
Chapter 8: Generating a System
Default Configuration for the D20MX
Prerequisites
Generate a system default configuration for the
D20MX
D20MX INSTRUCTION MANUAL
Generating a System Default Configuration for the D20MX
In the event that it is necessary to generate a system default configuration for the D20MX
(for example, the username, password or both are unavailable), this chapter provides the
procedure.
Prerequisites for generating a system default configuration for the D20MX:
A Windows PC with SGConfig 8.1 or higher software.
A NULL modem cable (GE Energy part number 977-0529) connecting the RS-232
connector on the front panel of the D20MX to the serial communications port of a PC
or terminal.
To generate a system default configuration for the D20MX:
1.
Set up Tera Term on a PC. See "Set up Tera Term on a PC" on page 64.
2.
Restart the D20MX by turning the power off and on.
Result: The startup messages appear.
3.
When the message "Press Ctrl-F to reset to factory defaults" appears, enter Ctrl-F
within 3 seconds.
Result: The prompt: "Do you wish to reset to Factory Defaults (yes/no)?:" appears
4.
Enter yes.
Be sure to enter the whole word "yes", not just "y".
Result: This causes the configuration to be defaulted and the password file to be
deleted. The system reboots and eventually the "User:" prompt appears.
GE INFORMATION