CHAPTER 5: CONFIGURING THE SOFTWARE
Prerequisites
Procedure
D20MX INSTRUCTION MANUAL
This is manually resolved by moving applications from other processors to the first
processor using the SGConfig device editing functions BEFORE converting the device to a
D20MX in the instructions below.
The word "transfer" is used within the context of this guide to mean that the device
configuration files are moved and modified, in order to work properly on a D20 with a
D20MX processor.
Before you can transfer a D20 or D200 device configuration, the following components
must be present:
SGConfig installed on the configuration computer. The minimum SGConfig version
supported is 8.1.
D20MX Documentation CD (part number 588-0075 V14X) in either of the following
formats:
Physical CD media, or
Zip file
D20 or D200 Configuration has been migrated to SGConfig with the Migration Wizard
(Refer to the Migration Wizard screencast).
Note: The Migration Wizard supports ConfigPro 2.0 and higher configurations.
To save time, you may upgrade the firmware definition of your D20 or D200
Configuration to SAN0001 or SAN0002 in ConfigPro
take this option, follow the instructions provided in Section: "Updating D20/D200
configurations to use the D20MX firmware definition with ConfigPro" on page 83,
before migrating the D20 configuration to SGConfig.
A NULL modem cable (GE part number 977-0529) connecting the RS-232 connector
on the front panel of the D20MX to the serial communications port of the
configuration computer.
To transfer a D20 or D200 device configuration to the D20MX:
In the event that you have selected dialog checkbox "Do not show this message again",
some of the following steps do not appear. Accordingly, ignore the affected steps.
1.
Start SGConfig.
Result: The Welcome to SGConfig screen appears.
2.
Choose the D20MX Factory Default Configuration file, D20MX01-14X.7zip or
D20MX02-14X.7zip. based on the following criteria:
If transferring a configuration containing B009 versions greater than 310 and
B021 versions greater than 912 use the file D20MX01-14X.7zip
If transferring a configuration containing B009 versions less than or equal to 310
and B021 versions less than or equal to 912, use the file D20MX02-14X.7zip.
3.
If the D20MX01-14X or D20MX02-14X default configuration has already been
imported, go to step 4 to open the default configuration. Otherwise perform these
sub-steps:
3.1.
Click GE button > Archive > Project > Restore.
Result: The Restore Project Details window appears.
3.2.
Click ... .
Result: The Select a File window appears.
3.3.
Navigate to the DVD/CD drive or the ISO Image sub-folder nested two levels
into the folder extracted from the D20MX Documentation CD zip file. Then
navigate to Configuration Files > SGConfig.
GE INFORMATION
TM
5.03 or higher. If you choose to