Measurements On The Main Circuit; Insulation Resistance Test Using Megger; Pressure Test - Mitsubishi Electric FR-A700 Instruction Manual

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Maintenance and inspection
8.2

Measurements on the main circuit

This section describes the measurement of the main circuit voltages, currents, powers and in-
sulation resistance.
8.2.1

Insulation resistance test using megger

For the inverter, conduct the insulation resistance test on the main circuit only as shown below
and do not perform the test on the control circuit. (Use a 500V DC megger.).
Fig. 8-14: Insulation resistance test
b
CAUTION:
Before performing the insulation resistance test on the external circuit, disconnect
the cables from all terminals of the inverter so that the test voltage is not applied to
the inverter.
NOTE
For the continuity test of the control circuit, use a tester (high resistance range) and do not
use the megger or buzzer.
8.2.2

Pressure test

Do not conduct a pressure test. Deterioration may occur.
FR-A700 EC
Power
supply
500V DC
megger
Earth
Measurements on the main circuit
M
3~
I001312E
8 - 15