Parameter

6
Parameter
6.1

Parameter overview

For simple variable-speed operation of the inverter, the initial setting of the parameters may be
used as they are. Set the necessary parameters to meet the load and operational specifications.
Parameter setting, change and check can be made from the operation panel FR-DU07.
indicates simple mode parameters. (initially set to extended mode)
The abbreviations in the explanations below are as follows:
V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux
Sensorless
Sensorless
Sensorless
Vector
Vector
Vector
Parameters without any indication are valid for all control. The half-tone screened parameters
allow its setting to be changed during operation even if "0" (initial value) is set in Pr. 77 "Param-
eter write selection".
Parameter
Func-
Name
tion
0
Torque boost
Second torque boost
46
Third torque boost
112
1
Maximum frequency
2
Minimum frequency
High speed maximum
18
frequency
Tab. 6-1:
Parameter overview (1)
FR-A700 EC
V/f control
Advanced magnetic flux vector control
Real sensorless vector control
Vector control
Incre-
Initial
ments
Value
6/4/3/
0.1%
2/1 *
0.1%
9999
0.1%
9999
120/
0.01Hz
60Hz *
0.01Hz
0Hz
120/
0.01Hz
60Hz *
Setting
Description
Range
Set the output voltage at 0Hz as %
* Initial values differ according to
the inverter capacity:
Inverter capacity
0–30%
00023/00038
00052–00126
00170/00250
00310–01800
02160 or more
Set the torque boost when the RT
0–30%
signal is on.
9999
Without second torque boost
Set the torque boost when the X9
0–30%
signal is on.
9999
Without third torque boost
Set the upper limit of the output
frequency
0–120Hz
* The setting depends on the
inverter capacity:
(01800 or less/02160 or more)
Set the lower limit of the output
0–120Hz
frequency
Set when performing operation at
120 Hz or more
120–400Hz
* The setting depends on the
inverter capacity:
(01800 or less/02160 or more)
Parameter overview
All
Para-
Para-
para-
meter
meter
meter
copy
clear
clear
✔: enabled
—: disabled
Initial
value
6%
4%
3%
2%
1%
Refer
to
page
6-168
6-168
6 - 1