Mitsubishi Electric FR-A700 Instruction Manual page 188

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Parameter overview
Parameter
Func-
Name
tion
Torque limit level
812
(regeneration)
Torque limit level
813
(3rd quadrant)
Torque limit level
814
(4th quadrant)
Torque limit level 2
815
Torque limit level
816
during acceleration
Torque limit level
817
during deceleration
OLT level setting
874
24
Refer to Pr. 4 to Pr. 6
27
Multi-speed input com-
28
pensation selection
Tab. 6-1:
Parameter overview (8)
6 - 8
Incre-
Initial
Setting
ments
Value
Range
0–400%
0.1%
9999
9999
0–400%
0.1%
9999
9999
0–400%
0.1%
9999
9999
0–400%
0.1%
9999
9999
0–400%
0.1%
9999
9999
0–400%
0.1%
9999
9999
0.1%
150%
0–200%
0
1
0
1
Description
Set the torque limit level for for-
ward rotation regeneration.
Pr. 22 value is used for limit.
Set the torque limit level for
reverse rotation driving.
Pr. 22 value is used for limit.
Set the torque limit level for
reverse rotation regeneration.
Pr. 22 value is used for limit.
When the torque limit selection
(TL) signal is on, the Pr. 815 value
is a torque limit value regardless
of Pr. 810.
Pr. 22 value is used for limit.
Set the torque limit value during
acceleration.
Same torque limit as at constant
speed
Set the torque limit value during
deceleration.
Same torque limit as at constant
speed
This function can make an alarm
stop if the torque limit is activated
to stall the motor. Set the output
torque at which an alarm stop is
made in Pr. 874.
Without compensation
With compensation
Parameter
All
Para-
Para-
para-
meter
meter
meter
copy
clear
Refer
clear
to
page
✔: enabled
—: disabled
6-80
6-190

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a740 ecFr-a700 ec