Analog Input Selection (Pr. 73, Pr. 267) - Mitsubishi Electric FR-A700 Instruction Manual

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Parameter
6.20.2

Analog input selection (Pr. 73, Pr. 267)

You can select the function that switches between forward rotation and reverse rotation
according to the analog input selection specifications, the override function and the input signal
polarity.
The following settings are possible:
● Select reference voltages and currents: 0 to ±10V, 0 to ±5V or 0/4 to 20mA
● Select an arithmetical or percentage compensation
● Suppress motor reversing when there is a negative set point signal voltage at terminal 1
Pr.
Name
No.
Analog input
73
selection
Terminal 4 input
267
selection
FR-A700 EC
Frequency/torque setting by analog input (terminals 1, 2 and 4)
Voltage/current
Initial
Setting
Value
Range
input switch
Switch 2 - OFF
0 to 5,
10 to 15
(initial status)
1
6/7/16/17 Switch 2 - ON
Switch 1 - ON
0
(initial status)
0
1
Switch 1 - OFF
2
Description
Parameters referred to
You can select the input
specifications of terminal
2 (0 to 5V, 0 to 10V, 0 to
20mA) and input speci-
fications of terminal 1 (0
to ±5V, 0 to ±10V).
Override and reversible
operation can be selected.
Terminal 4 input 4 to
20mA
Terminal 4 input 0 to 5V
Terminal 4 input 0 to 10V
Refer to
Section
22
Stall prevention
6.7.4
operation leve
125
Terminal 2
6.20.5
frequency setting
gain frequency
126
Terminal 4
6.20.5
frequency setting
gain frequency
252
Override bias
6.20.3
253
Override gain
6.20.3
858
Terminal 4 func-
6.20.1
tion assignment
868
Terminal 1 func-
6.20.1
tion assignment
6 - 371

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a740 ecFr-a700 ec

Table of Contents